background image

NOVUS AUTOMATION 

1/3 

 

 

 

 

TXMINI-M12 / TXMINI TRANSMITTER 

OPERATING MANUAL – V1.0x H 

INTRODUCTION  

The 

TxMini-M12 Transmitter

  is a 4-20 mA 2-wires  temperature 

transmitter for head mount, powered by the current loop. Its 

configuration is accomplished by connecting the TxConfig-M12 

interface configuration. The configuration does not require that the 

transmitter be powered. 
The output current is linearized according to the selected input 

sensor and adjusted to the configured range. 

SPECIFICATIONS 

Sensor Input: 

User defined. The supported sensors are listed in 

Table 

1

, along with their maximum ranges. 

Pt100

:  Type  3-wire, Excitation 0.8 mA, 

α

= 0.00385, according 

IEC 60751 (ITS-90). 

Pt1000

: Type 3-wire, Excitation 0.8 mA, 

α

= 0.00385, according 

NBR 13773. IEC 60751 (ITS-90). 

 

For 2-wire sensors, tie terminals 3 and 4 together. 

Switch-on delay

: < 2.5 s. The accuracy is only guaranteed after 15 

minutes. 

 

Terms of reference

:

 

ambient: 25 ° C  (77 °F); voltage: 24 Vdc, load: 

250 

; settling time: 15 minutes. 

 

Temperature Effect

:

 

<

 

± 

0.2 % / 25 °C 

 

Response time

: typical 1.6 s 

 

Maximum voltage allowed at input terminals no sensor

:

 

3 V.

  

RTD current

:

 

800 

µ

A.  

RTD cable resistance effect

: 0.005 °C / 

.

 

Maximum allowable cable resistance for RTD

: 25 

.

 

Sensor Type 

Typical 

Accuracy 

Minimum 

Accuracy 

Pt100 / Pt1000 

0.1 % 

0.2 % 

Table 1

 – Calibration error, percentage of the full measurement range

 

Power supply influence

: 0.006 % / V typical (percentage of the full 

measure range). 

Output

:

 

4-20 mA or 20-4 mA current, 2-wire; linear in relation to the 

temperature measurement by the selected sensor. 

Output Resolution: 

µ

A.

 

Power supply

: 8 to 35 Vdc, across the transmitter; 

Maximum load (RL)

: RL (max.) = (Vdc – 8) / 0.02 [

]

 

 

Where: Vdc= Power supply voltage (8-35 Vdc) 

Operating Temperature

: -40 to 85 °C (-40 to 185 °F) 

Humidity

: 0 to 90 % RH 

Electromagnetic Compatibility

:

 

EN 61326-1:2006 

No electrical isolation between input and output

.

 

Internal protection against polarity inversion

.

 

Cold junction compensation for thermocouples

 

Connection Wire Cross Section

: 0.14 a 1.5 mm²

 

Screw Tightening

: 0.8 Nm. 

 

Housing

: Polyamide. 

 

 

Sensor Type 

Maximum 

Measurement Range 

Minimum 

Measurement Range 

Pt100 

-200 to 650 °C  

(-328 to 1202 °F) 

40 °C 

(104 °F) 

Pt1000 

-200 to 650 °C 

(-328 to 1202 °F) 

40 °C 

(104 °F) 

Table 2

 – Sensors accepted by the transmitter 

Order Codes: 

-

 

P/N: 

8806060406

: TxMini-M12 transmitter; 

-

 

P/N: 

8816021079

: TxConfig-M12 Interface. 

-

 

P/N

: 8806060506

: TxMini  Transmitter  (transmitter  can only be 

configured during production). 

-

 

P/N: 

8806065000

: M12 Connector Cable for TxMini-M12 

(accessory) 

CONFIGURATION 

The sensor offset can be adjusted through the 

TxConfig II

 software. 

The USB cable may be connected to the transmitter without causing 

any measurement errors.  
The user must select the sensor and most suitable range to the 

process. The chosen range must not exceed the maximum range 

specified for that sensor and should not be narrower than the 

minimum range for that same sensor. 

SOFTWARE CONFIGURATION:

 

 

Fig. 1

 – 

TxConfig II

 software main screen 

 

The communication interface TxConfig-M12 is not 

electrically isolated from the transmitter’s input. 