background image

 
 
 
E-AVDS-CELC   
Automatic Voice Dialer 
INSTALLATION AND OPERATION 
MANUAL

 

 
 
 
 
 
 
 

INTRODUCTION 

 

The E-AVDS-CELC Automatic Voice Dialer is used to send voice alert messages from an ENVIROMUX Enterprise Environment 
Monitoring System (SYSTEM) to any user’s cell phone or device capable of receiving voice messages.   
 
The E-AVDS-CELC

P

 includes a 12VDC power supply for connection to E-MINI-LXO, E-DI16DOR16 or any other SYSTEM where an 

external power supply will be needed.  

 

 
 
OPEN THE E-AVDS-CELC 

 
There are four tabs that hold the case together.  Two on the top side, and two on the bottom side.  To open the case for jumper 
placement, press down firmly on the seam of the case near the tabs on one side of the case and snap the case halves apart.    
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 
 
 
 
 
 

Tabs 

With the rear of the case removed, two counter-sunk 
mounting holes are provided on the rear cover.   Use 
these to secure the E-AVDS-CELC to your desired 
mounting location.  

Mounting Holes 

Rear Cover

Summary of Contents for E-AVDS-CELC

Page 1: ...n to E MINI LXO E DI16DOR16 or any other SYSTEM where an external power supply will be needed OPEN THE E AVDS CELC There are four tabs that hold the case together Two on the top side and two on the bo...

Page 2: ...J3 jumper to the center and left pin In this configuration a relay closure will trigger an alert state activating the dialer To set the normal relay state to Normally Closed apply the J2 and J3 jumpe...

Page 3: ...THODS Connect the cable from the E AVDS CELC to the E xD according to one of the following diagrams Note The attached cable is 30 long but can be extended up to 250 feet with any 4 conductor 22AWG min...

Page 4: ...4...

Page 5: ...lue yellow Digital Contact wire 1 green Digital Contact wire 2 Second cable with RJ11 plug will go into telephone jack 6 Buttons used to enter programming GENERAL INFORMATION Recording Duration 20 sec...

Page 6: ...ramming Mode the screen displays S Press E1 the phone number ENTER For instance if the telephone number is 93953399 the procedure is as follows Press E1 939533399 ENTER After pressing ENTER to save th...

Page 7: ...of the recorded message will begin immediately The procedure is as follows 3 2 Play back the pre saved 20 second message A beep will indicate when it has ended 5 Save and search the password A Save th...

Page 8: ...ed If the password is correct the alarm will terminate indicated by beeps Note If the password contains less than three digits then 0 can be used as a substitute For instance if the password is 1 and...

Page 9: ...12V Operating current 170mA MAX Based on operating voltage DC 12V Triggering mode N C N O or voltage signal Voice recording 20 seconds maximum Phone numbers Up to 4 contact numbers Private password p...