nVent.com | 1
Raychem-IM-H
56046
-JBS
100
A
100
A
6
-ML-
1805
JBS-100-A, A6
SINGLE ENTRY POWER CONNECTION WITH JUNCTION BOX
INSTALLATION INSTRUCTIONS
–WS
RA
YCHEM
©2001
www
.nVen
t.com
APPROVALS
CLI, ZN1, AEx e II T*
(1)
Ex e II T*
Hazardous Locations
(1)
Except VPL
* For system Temperature Code, see heating cable or design documentation
.
(2)
Except KTV-CT
Class I, Div. 2, Groups A, B, C, D
Class II, Div. 2, Groups E, F, G
Class III
JBS-100-A is IECEx certified for use with:
BTV-CR/BTV-CT:
IECEx BAS 06.0043X
QTVR-CT:
IECEx BAS 06.0045X
XTV-CT:
IECEx BAS 06.0044X
KTV-CT:
IECEx BAS 06.0046X
VPL-CT:
IECEx BAS 06.0048X
– WS
(JBS-100-A only*) Ex e IIC T* Gb
(2)
IECEx
KIT CONTENTS
Item Qty Description
A
1
Stand assembly
B
1
Core sealer
C
1
Green/yellow tube
D
1
Cable lubricant
E
1
Cable tie
F
1
Lid
G
1
Box with terminal blocks
DESCRIPTION
The nVent RAYCHEM JBS-100-A and nVent RAYCHEM JBS-100-A6 are NEMA
4X-rated power connection kit. It is designed for use with nVent RAYCHEM BTV-CR,
BTV-CT, QTVR-CT, XTV-CT, KTV-CT and VPL-CT industrial parallel heating cables.
The JBS-100-A6 utilizes larger terminal blocks to accommodate up to 6 AWG
power wires.
This kit may be installed at temperatures as low as –40°F (–40°C). For easier
installation store above freezing until just before installation.
For technical support call nVent (800) 545-6258.
TOOLS REQUIRED
• Wire cutters
• Adjustable pliers
• Utility knife
• Needle nose pliers
• Large slotted screwdriver
• Marker
• Wire stripper (for VPL-CT)
• 1/4 in or smaller flat-blade screwdriver
ADDITIONAL MATERIALS REQUIRED
• Pipe strap
• GT-66 or GS-54 glass cloth tape
OPTIONAL MATERIALS
• Recommended conduit drain:
JB-DRAIN-PLUG-3/4IN P/N 278621-000
• Small pipe adapter for 1 in (25 mm) and smaller pipes:
Catalog number JBS-SPA P/N E90515-000
A
D
G
F
E
B
C
–WS
RAYCHEM
RAYC
HEM
WARNING:
CAUTION:
This component is an electrical device that must be
installed correctly to ensure proper operation and to
prevent shock or fire. Read these important warnings and
carefully follow all of the installation instructions.
• To minimize the danger of fire from sustained electrical
arcing if the heating cable is damaged or improperly
installed, and to comply with the requirements of nVent
agency certifications, and national electrical codes,
ground-fault equipment protection must be used. Arcing
may not be stopped by conventional circuit breakers.
• Component approvals and performance are based
on the use of nVent-specified parts only. Do not use
substitute parts or vinyl electrical tape.
• The black heating cable core and fibers are conductive
and can short. They must be properly insulated and
kept dry.
• Damaged bus wires can overheat or short. Do not break
bus wire strands when scoring the jacket or core.
• Keep components and heating cable ends dry before
and during installation.
• Use only fire-resistant insulation materials, such as
fiberglass wrap and flame-retardant foam.
HEALTH HAZARD
: Prolonged or repeated contact with
the sealant in the core sealer may cause skin irritation.
Wash hands thoroughly. Overheating or burning the
sealant will produce fumes that may cause polymer fume
fever. Avoid contamination of cigarettes or tobacco.
Consult MSDS VEN 0058 for further information.
CHEMTREC 24-hour emergency telephone:
(800) 424-9300
Non-emergency health and safety information:
(800) 545-6258.