GENERAL
This device is used as an indication of a fire panel
that provides a warning audio signal from the
siren and visual indication using the beacon. The
loudness and the luminous signal it produces
covers an area of several square meters. It is
compatible with any conventional panel.
CONNECTION AND MOUNTING
1.
Unscrew the screw and remove the plastic
cover using a flat screwdriver to the point under
the screw (Picture 1 page 2).
2.
Unscrew the four screws and detach the plastic
from the base (Picture 2).
3.
Drill the holes needed to pass the connection
cables. Place the cable glands and open a hole to
the center with a small screwdriver. Pass the
connection cables through the glands of the device
(Picture 3).
4.
Use the supplied mounting materials to place
the base of the siren in height up to 2.4 meters from
the gound (Figure 1 page 2). Install the plastic
plugs and fasten the screws in the mounting holes.
CAUTION!!
Make sure that the base of the siren is
installed in the correct orientation.
5
.
To
adjust the type of the sound indication
use
DIP switches 1 to 5, according to Table 1 (page 4)
and Table 4 (page 5). Depending on the input from
which the device is powered.
6.
To
adjust the sound level
use DIP switches 6
to 7, according to Table 2 (page 5).
7.
To
adjust the frequency of the flashing LED
use DIP switch 8 according to Table 3 (page 5).
8.
Refit the plastic and fasten the 4 screws you
removed in step 2.
9.
Refit the plastic cover and fasten the screw.
10.
Test the operation of the device through the
panel after the installation.
Note:
The siren can be supplied from the input N1
or N2. In case it is supplied from both inputs then
N1 has priority. Depending on the connection you
will choose and the setting of DIP switches 1 to 5
the corresponding pattern will sound. By
connecting the siren to input N1 and configuring
DIP switches 1 to 5 the pattern that will sound is
shown in Table 1. By connecting the siren to input
N2 and configuring DIP switches 1 to 5 the pattern
that will sound is shown in Table 4. The difference
in the patterns between N1 and N2 allows the
device to be used both as a pre-alarm and alarm
indication.
Waterproof sounder with beacon
Β
S-532/WP
Page
1 from
6
921532001_09_002
Thank you for your trust in our products
Olympia Electronics - European manufacturer
1
8-
30
V DC
103dB
12
to
49
m
Α
IP65
EN 54-3,
EN 54-23
127x137x82 mm
ABS/PC,PC
GUARANTEE
RELATIVE HUMIDITY
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS
TYPICAL WEIGHT
FLASHING RATE
FLASHING COLOUR
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATING TEMPERATURE RANGE
MOUNTING
COVER AREA
MOUNTING HEIGHT (x)
COVER AREA CODE
MAXIMUM SOUND LEVEL IN 1 METER
ENVIROMENTAL TYPE
BEACON
MAIN VOLTAGE
ALARM CONSUMPTION
TECHNICAL CHARACTERISTICS
Type B
1 power
LED
Wall mounted
27.7m³
maximun
2
.
4
meters max
Adjustable to 1 Hz or 0.5 Hz
White
o
-2
5 to
70
C
Up to 95%
2 years
30
6
gr.
20
1293
Ο-2.4-2.4-4.8