SELF TESTING MAINTAINED EMERGENCY LUMINARIES

GENERAL

o

These luminaires are used indoors 

(

ta 40 C

)

 

where emergency light is needed.
Each  luminaire  must  be  permanently 
connected to mains power supply

.

 In normal 

operation the illumination LEDs are lit as well 
as  the  green  indicating  charge  LEDs  when 
the  battery  is  charging.  In  case  of  a  mains 
power  supply  failure  the  luminaire    will  light 
the  led  strip  automatically  in  emergency 
mode.  When  the  mains  power  supply  is 
r e s t o r e d   t h e   d e v i c e   t u r n s   t o   n o r m a l  
operation.

INSTALLATION

To  install  the  luminaire  follow  the  installation 
instructions on page 3.

Battery Charging

The 

battery 

charging 

is 

completely 

controlled

Thereby, the best possible battery 

maintenance  is

 

achieved

as  well  as  the 

elongation  of  its  duration

When  the  battery 

has  completely  charged

it  charges  with  a 

maintenance current.

Battery Cut-off

The  luminaire  enters  in  this  operation  when 

the mains power supply fails

 

and battery has 

lost  all  its  energy

During  this  operation  the 

luminaire  enters  the  idle  state

 

and  battery 

consumption  is  negligible,  in  order  to  be 
protected from deep discharge.

Manual

 

Operational 

Test

This test can be done by pressing the test 
button.  The  light  source  and  the  emergency 
circuit  of  the  device  is  monitored  for  3  sec. 
The manual test can be conducted only if the 
mains  power  supply  and  the  battery  is 
connected.  During  this  test  period  all 
indication LEDs are OFF. 

Automatic Operational Test

This  test  includes  all  the  operations  that 
provide  the  manual  test  and  is  conducted 
automatically  every  15  days.  In  order  to  be 
performed,  the  mains  power  supply  and  the 
battery should be connected. 

Automatic Autonomous Test

The Automatic Autonomous Test is conducted 
and measures the device’s back up operation 
and  emergency  duration.  This  test  is 
conducted  automatically  every  6  months

In 

order  to  be  performed,  the  mains  power 

Thank you for your trust in our products  

Olympia Electronics -  European manufacturer

220-240V AC/50-60Hz

3 h

24 h

IP30

3.6V/1.5Ah 

(

Ni-Cd

)

3.4W / 3.6VA

EN 60598-1, EN 60598-2-22

, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3

5 to 40  C

o

up to 95% 

ABS/PC,PC

532gr.

453

gr.

2

92

 

x 111 x 54 mm

  110lm / 110lm

  12 White LEDs

TECHNICAL CHARACTERISTICS

 (

for LED MODULE Specs. see page 

3

)

OPERATION TEMPERATURE RANGE

RELATIVE HUMIDITY

EXTERNAL DIMENSIONS 

CONSTRUCTION MATERIALS 

TYPICAL WEIGHT

GUARANTEE 

OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY

 

CHARGING TIME

INDICATIONS 

CONTROLS

MINIMUM AUTONOMOUS DURATION

DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH

ILLUMINATION

 

(230V AC

 

/ emergency) 

VIEWING DISTANCE

22m

ILLUMINATION SOURCE 

Battery charge Fault indication LEDs

TEST button

3 years 

(1 

year for the battery

)

1.5 h

16 h

3.6V/600mAh

(

Ni-Cd

)

GR-2100/ST

GR-2110/ST