GENERAL
o
This device is used indoors
(
ta 40 C
)
in places
where emergency luminaires are needed.
Each device must be permanently connected
to mains power supply
.
The GR-292/M/HL is
suitable for corridors lighting and the GR-
293/M/HL for open area lighting. In normal
operation the battery is charging. In case of a
mains power supply failure, the device enters
emergency mode and the illumination LED
turns on. When the mains power supply is
restored, the device turns to normal operation.
INSTALLATION
To install the luminaire follow the installation
instructions
ο
n page 3.
Battery Charging
The battery charging is completely controlled
.
In this case, is
achieved the perfect battery
maintenance
,
as well as the elongation of its
duration
.
When the battery has completely
charged
,
it charges with a maintenance
current.
Battery Cut-off
The device enters this mode when the mains
power supply has failed
and battery has lost its
energy
.
During this mode the device enters in
idle state
and battery consumption is
negligible, in order to be protected from deep
discharge.
Manual
Test
This test can be done by pushing the test
button. The light source and the emergency
circuit of the device are monitored. The manual
test can be conducted only if the main power
supply and the battery are connected. During
this test period all indication LEDs are OFF.
Automatic Operational Test
This test includes all the operations that provide
the manual test and is conducted automatically
every 15 days. In order to be performed, the
mains power supply and the battery should be
connected.
Automatic Autonomous Test
This test monitors the device’s back up
operation and emergency duration. The
BATTERY FAULT LED blinks during the test,
indicating this process to the user. This test is
conducted automatically every six months
.
In
order to be performed, the mains power supply
should be connected and the battery must be
fully charged
.
If the battery is not fully charged
,
the test is postponed
until the battery is
completely charged. If during this test, the
autonomy is less than the nominal then the
SELF TESTING N
ON
-M
AINTAINED
EMERGENCY CEILING MOUNTED
LUMINAIRE
S
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIAL
EXTERNAL DIMENSION
WEIGHT
GUARANTEE
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY (Ni-MH)
CHARGE TIME
INDICATIONS - CONTROLS
BATTERY PROTECTION
MINIMUM DURATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
EMERGENCY ILLUMINATION
LIGHT SOURCE
220-240V AC / 50-60Hz
24 hours
Deep discharge and overcharge protection
IP20
4.8V/
4
Ah
1 white
power LED
o
5 to 40 C
Up to 95%
ABS/PC
3 years
(1
year for the battery
)
737gr.
Ø125 x 72 mm
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
Charge, lamp fault, battery fault
,
TEST button
4.9W / 5.2 VA
TECHNICAL CHARACTERISTICS
(for LED MODULE specifications see page 5)
Thank you for your trust in our products
Olympia Electronics - European manufacturer
3 hours
330lm
GR-292/M
/
HL
GR-293/M/HL