GENERAL

o

This device is used indoors 

(

ta 40 C

)

 in places 

where  emergency  luminaires  are  needed. 
Each  device  must  be  permanently  connected 
to  mains  power  supply

.

  The  GR-292/M/HL  is 

suitable  for  corridors  lighting  and  the  GR-
293/M/HL  for  open  area  lighting.  In  normal 
operation the battery is charging. In case  of a 
mains  power  supply  failure,  the  device  enters 
emergency  mode  and  the  illumination  LED 
turns  on.  When  the    mains    power    supply  is 
restored, the device turns to normal operation.

INSTALLATION

To  install  the  luminaire  follow  the  installation 
instructions 

ο

n page 3.

Battery Charging

The  battery  charging  is  completely  controlled

In  this  case,  is

 

achieved  the  perfect    battery 

maintenance 

as  well  as  the  elongation  of  its 

duration

When  the  battery  has  completely 

charged

it  charges  with  a  maintenance 

current.

Battery Cut-off

The  device  enters  this  mode  when  the  mains 
power supply has failed

 

and battery has lost its 

energy

During  this  mode  the  device  enters  in 

idle  state

 

and  battery  consumption  is 

negligible,  in  order  to  be  protected  from  deep 
discharge.

Manual

 Test

This  test  can  be  done  by  pushing  the  test 
button.  The  light  source  and  the  emergency 
circuit of the device are monitored. The manual 
test  can  be  conducted  only  if  the  main  power 
supply  and  the  battery  are  connected.  During 
this test period all indication LEDs are OFF.
 

Automatic Operational Test

This test includes all the operations that provide 
the manual test and is conducted automatically 
every  15  days.  In  order  to  be  performed,  the 
mains  power  supply  and  the  battery  should  be 
connected.
      

Automatic Autonomous Test

This  test  monitors  the  device’s  back  up 
operation  and  emergency  duration.  The 
BATTERY  FAULT  LED  blinks  during    the  test, 
indicating  this  process  to  the  user.  This  test  is 
conducted  automatically  every  six  months

In 

order to be performed, the mains power supply 
should  be  connected  and  the  battery    must  be 
fully charged

If the battery is not fully charged

the  test  is  postponed

 

until  the  battery  is   

completely  charged.  If  during  this  test,  the 
autonomy  is  less  than  the  nominal  then  the 

SELF TESTING N

ON

-M

AINTAINED

 EMERGENCY CEILING MOUNTED 

LUMINAIRE

S

OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIAL

EXTERNAL DIMENSION
WEIGHT

GUARANTEE

OPERATION VOLTAGE

MAXIMUM POWER CONSUMPTION
BATTERY (Ni-MH)

CHARGE TIME

INDICATIONS - CONTROLS

BATTERY PROTECTION

MINIMUM DURATION

DEGREES OF COVER PROTECTION

PRODUCED IN ACCORDANCE WITH

EMERGENCY ILLUMINATION

LIGHT SOURCE

220-240V AC / 50-60Hz

24 hours

Deep discharge and overcharge protection

IP20

4.8V/

4

Ah

  1 white

 

power LED

o

5 to 40  C

Up to 95% 

ABS/PC

3 years

 (1 

year for the battery

)

737gr.

Ø125 x 72 mm

EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3

Charge, lamp fault, battery fault

TEST button

4.9W / 5.2 VA

TECHNICAL CHARACTERISTICS

 

(for LED MODULE specifications see page 5)

Thank you for your trust in our products  

Olympia Electronics - European manufacturer

3 hours

  330lm 

 GR-292/M

/

HL

 GR-293/M/HL