SPOT LIGHT
EMERGENCY
MAINTAINED
LUMINAIRE WITH WHITE LEDs
High Quality European based Manufacturers
TECHNICAL CHARACTERISTICS
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIAL
EXTERNAL DIAMENTION
WEIGHT
GUARANTEE
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY
(
Ni-MH
)
CHARGE TIME
INDICATIONS - CONTROLS
BATTERY PROTECTION
MINIMUM DURATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
EMERGENCY ILLUMINATION
LIGHT SOURCE
220-240V AC/50-60Hz
3 hours
24 hours
Discharge and over charge protection
IP 40
4.8V/1.2Ah
330lm / 110lm
White
LEDs
5.9W / 7.3VA
5 to 40 C
o
Up to 95%
Bayblend FR3010
,
clear
polycarbonate
3 years
(1
year for the battery
)
470gr.
Ø125 x 65 mm
EN 60598-1, EN 60598-2-22
, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
Battery charging LED
,
TEST button
GR-297/60L/180
Thank you for purchasing this product of
O l y m p i a E l e c t r o n i c s . A E u r o p e a n
manufacturer.
GENERAL
o
These luminaires are used indoors
(
ta 40 C
)
where emergency light is needed.
E a c h l u m i n a i r e m u s t b e p e r m a n e n t l y
connected to mains power supply
.
In normal operation the battery is charging and
the illumination source, lights
.
In case of a mains power supply failure the
luminaire will light the illumination source
automatically in emergency mode. When the
mains power supply is restored the device
turns to normal operation.
INSTALLATION
To install the luminaire follow the installation
instructions on page 2.
ΑΤΤΕΝΤΙΟΝ
!!!
1. Operations for installation, maintainance or
testing must be done by authorized personel
only
.
2.
The device must be connected to the mains
power supply thru a fuse dependent by the
total amount of the line’s power load
.
3.
It is sugested to check every month the
indication LED for battery charging, and by
pushing the TEST button (use a pointy tool
with diameter of 2mm max.) to check the
emergency cirquit. The illumination LEDs
should light as long as the TEST button is
pressed
4.
It is sugested to check every 6 months the
minimum autononous duration by disconnecting
the mains power supply
.
Count the time that
the luminaire lights and in case of less time
than the minimum autonomous duration the
battery must be replaced. If the measured time
i s c o n s i d e r a b l y l e s s t h a n t h e m i n i m u m
autonomous duration
In
case of battery or light source replacement,
these must be replaced by parts of the same
type, by the manufacturer or by a competent
person.
t i
in battery recycling
points. Do not incinerate.
NOTE:
LED= Light Emitting Diode
LABELING EXPLANATION:
X: Self contained
1: Maintained (*)
A: Including test device
180: 3 hour duration
(*)
Maintained operation: The luminaire lights its
illumination source, when it is powered by the
mains power supply or not
.
Non-Maintained operation: The luminaire lights
its illumination source,
only in power supply’s
failure.
. In the opposite condition contact the
installer.
contact the installer.
5.
In case of inactive use for a period greater
than 2 months, disconnect the battery by pulling
out the battery’s connector.
6.
I
s not allowed to discard batteries in to
common trash bins, they must be
discarded only