background image

GENERAL

o

These  devices  are  used  indoors 

(

ta  40 C

)

 

in places where emergency luminaires are 
needed.  The  luminaires

 

GR-470  and  GR-

472  are  suitable  for  corridors  lighting  and 
the

 

GR-471  and  GR-473  for  open  area 

lighting

.

 Each device must be permanently 

connected  to  mains  power  supply

.

  In 

normal operation the battery is charging. In 
case  of a mains power supply failure  the 
device  will  light  the  illumination  led 
automatically  in  emergency  mode.  When 
the    mains    power    supply  is  restored  the 
device turns to normal operation.

INSTALLATION

To install the luminaire follow the 
installation instructions 

ο

n page 2.

ΑΤΤΕΝΤΙΟΝ

!!!

1. Operations for installation, maintainance 
or  testing  must  be  done  by  authorized 
personel only

.

2. 

The  device  must  be  connected  to  the 

mains power supply thru a fuse dependent 
by  the  total  amount  of  the  line’s    power 
load

.

3. It is sug

g

ested to check every month the 

indication LED for battery charging, and by 
placing  the test card 

 (page  5) an 

(

A-1900)

operation test is initiated, to check the 
emergency  cirquit.  The  illumination  source 
should  light  as  long  as  the  card  is  present

In  the  opposite  condition  contact  the 
installer.

 

 

4. 

It  is  sugested  to  check  every  6  months 

the  minimum  autononous  duration  by 
disconnecting  the  mains  power  supply

.

 

 

Count the time that  the luminaire lights and 
in  case  of  less  time  than  the  minimum 
autonomous  duration  the  battery  must  be 
r e p l a c e d .   I f   t h e   m e a s u r e d   t i m e   i s  
considerably  less  than  the  minimum 
autonomous duration 

contact the installer.

  I n   c a s e   o f   b a t t e r y   o r   l i g h t   s o u r c e  
replacement,  these  must  be  replaced  by 
parts of the same type, by the manufacturer 
or by a competent person.

5. 

In  case  of  inactive  use  for  a  period 

greater  than  2  months,  disconnect  the 
b a t t e r y   b y   p u l l i n g   o u t   t h e   b a t t e r y ’s  
connector.

 

6. 

I s not allowed to discard batteries in 

t i

to  common  trash  bins,  they  must 
be  discarded  only 

 

in  battery 

recycling points. Do not incinerate.

Page

 1

 from

 

5

923473001

_0

9

_00

1

NON-MAINTAINED LUMINAR

IES

OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIAL

EXTERNAL DIMENSION
WEIGHT
GUARANTEE

OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY

 (

Ni-Cd

)

CHARGE TIME

INDICATIONS 

BATTERY PROTECTION

MINIMUM DURATION

DEGREES OF COVER PROTECTION

PRODUCED IN ACCORDANCE WITH

EMERGENCY ILLUMINATION

LIGHT SOURCE

24 hours

 

Charge LED, Magnetic Test Contact

Deep discharge and overcharge protection

IP42

3,6V/1

 

Ah

1

 

white

 

power LED

2,

6

W / 2

,9

VA

o

5

 to 40  C

Up to 95% 

3 years

 (1 

year for the battery

)

EN 60598-1, EN 60598-2-22

, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3

3 hour

1,5

 hour

  145lm 

  80lm 

470gr.

220-240V AC

 

/ 50-60Hz

TECHNICAL CHARACTERISTICS

 

(for LED MODULE specifications see page 4)

Thank you for your trust in our products.  

Olympia Electronics -  European manufacturer

.

 GR-47

0

 GR-471

 GR-472

 GR-473

ABS/PC

PC

158 x 158 x 60,4mm (without decorative bezel)-195 x 195 x 60,4 (with decorative bezel)

Reviews: