GENERAL
o
These luminaires are used indoors
(
ta 40 C
)
on the wall, where emergency light is needed.
E a c h l u m i n a i r e m u s t b e p e r m a n e n t l y
connected to mains power supply
.
In normal
operation the illumination LEDs are lit as well
as the green indicating charge LEDs, when
the battery is charging.
In case of a mains power supply failure the
luminaire will light the led strip automatically
in emergency mode. When the mains power
supply is restored the device turns to normal
operation.
Non Maintained / maintained operation
there is an option to select the non maintained
or maintained operation by placing the jumper
to the appropriate place according to the
figure 3 (see page 2)
.
INSTALLATION
To install the luminaire follow the installation
instructions on page 2.
ΑΤΤΕΝΤΙΟΝ
!!!
1. Operations for installation, maintainance or
testing must be done by authorized personnel
only
.
2.
The device must be connected to the
mains power supply through a fuse dependent
by the total amount of the line’s power load
.
3.
It is suggested to check every month the
indication LED for battery charging, and by
pushing the TEST button to check the
emergency circuit. The led strip should light as
long as the TEST button is pressed.
If the
luminaire doesn’t work as described above
contact the installer.
4.
It is suggested to check every 6 months the
m i n i m u m a u t o n o n o u s d u r a t i o n b y
disconnecting the mains power supply
.
Count
the time that the led strip lights and in case of
less time than the nominal autonomy, the
battery must be replaced. If the measured time
i s c o n s i d e r a b l y l e s s t h a n t h e n o m i n a l
autonomy
In case of
contact the installer.
battery or led strip replacement, these must be
replaced by parts of the same type,
by the
manufacturer or
by a competent person.
5.
In case of inactive use for a period greater
than 2 months, disconnect the battery by
pulling out the battery’s connector.
6.
I s not allowed to discard batteries in to
t i
common trash bins, they must be
discarded only
in battery recycling
points.
Do not incinerate.
The light source contained in this
luminaire shall only be replaced by the
manufacturer, or his agent, or a similar
qualified person.
NOTE! The light source is non-user
replaceable.
NON
MAINTAINED / MAINTAINED EMERGENCY LUMINAIRES
923378005
_09_008
Page 1 from
3
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
EXTERNAL DIMENSIONS
CONSTRUCTION MATERIALS
TYPICAL WEIGHT
GUARANTEE
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERIES (Ni-Cd)
CHARGING TIME
INDICATIONS
-
CONTROLS
MINIMUM AUTONOMOUS DURATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
ILLUMINATION
(230V AC
/ emergency)
ILLUMINATION SOURCE
1.5 h
3
h
24 h
Battery charge indication LEDs
,
TEST button
IP 42
12
white LEDs
EN 60598-1, EN 60598-2-22
, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
o
5 to 40 C
Up to 95%
Bayblend FR3010
,
transparent
polycarbonate
3 years
(1
year for the battery
)
240 x 90 x 44 mm
345gr.
220-240VAC/50-60Hz
350gr.
GR-8/leds
GR-9/leds
3.6V/0.6Ah
3.6V/1Ah
2.7W/3VA
3W/3.5VA
40lm / 100lm
38lm / 100lm
TECHNICAL CHARACTERISTICS
(
for led module spcifications see page 2
)
Thank you
for your
trust in our
product
s
.
Olympia Electronics - European manufacturer.