background image

Page 1 from 4

 

923940000_09_009

GENERAL

These  luminaires  are  used  in  places  where 
emergency  luminaires  are  needed.  Each 
luminaire  must  be  permanently  connected  to 
mains  power  supply.  In  normal  operation  (L1 
connected  to  L)  the  led  strip  lights  and  the 
battery  is  charging.  In    case    of    a    mains   
power  supply  failure  the luminaire   will   light 
the led strip automatically in emergency mode 
(powered  by      its  battery).    When  the    mains   
power  supply  is  restored the device turns to 
normal operation. 

INSTALLATION

To  install  the  luminaire  follow  the  installation 
instructions on page 3.

OPERATION
Battery Charging

The  battery  charging  is  completely  controlled. 
Thereby, 

the 

best 

possible 

battery 

maintenance  is  achieved,  as  well  as  the 
elongation  of  its  duration.  When  the  battery 
has  completely  charged,  it  charges  with  a 
maintenance current.

Battery Cut-off

The  luminaire  enters  in  this  operation  when 
the mains power supply fails and battery has 

lost  its  energy.  During  this  operation  the 
luminaire  enters  the  idle  state  and  battery 
consumption  is  negligible,  in  order  to  be 
protected from deep discharge.

Manual Test

The  manual  test  can  be  conducted  only  if  the 
mains  power  supply  and  the  battery  is 
connected.  By  pressing  the  TEST/RESET 
button  briefly  (page  3)  an  operation  test  is 
initiated.  During  this  test  period  all  indication 
LEDs are OFF.

Tests

Normally  the  illumination  source  and  the 
autonomy  tests  are  programmed  by  the 
control  panel  and  the  test  results  are  sent  to 
the control panel.

Automatic Operational Test

This  test  includes  all  the  operations  that 
provide  the  manual  test  and  is  conducted 
automatically  every  15  days.  In  order  to  be 
performed,  the  mains  power  supply  and  the 
battery should be connected. 

Automatic Autonomous Test

The Automatic Autonomous Test  is  conducted 
and measures the device’s back up operation 

High Quality European based Manufacturers

220-240V AC/50-60Hz

Bayblend FR3010, transparent  polycarbonate

TECHNICAL CHARACTERISTICS 

(for LED MODULE Specs. see page 4)

OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY

EXTERNAL DIMENSIONS 

CONSTRUCTION MATERIALS 

TYPICAL WEIGHT

GUARANTEE 

OPERATION VOLTAGE

MAXIMUM POWER CONSUMPTION
BATTERIES (Ni-Cd)

CHARGING TIME

INDICATIONS

BATTERY PROTECTION

MINIMUM AUTONOMOUS DURATION

DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH

ILLUMINATION (MAINS / EMERGENCY)

ILLUMINATION SOURCE 

24h

Charge, Lamp Fault, Battery Fault indication LED

From overcharge and deep discharge

IP 65

3.6V/3Ah

EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3

5 to 40  C

o

Up to 95% 

3 years (1 year for the battery)

945gr.

363 x 145 x 73 mm

GR-940/15L

  105lm / 105lm 

480min

4.1W /4.5VA

  15 white LEDs 

Thank you for your trust in our products  

Olympia Electronics -  European manufacturer

                       WATERPROOF SELF TESTING  EMERGENCY LUMINAIRE 