 SLD-34/DZ

SLD-44/DZ

 SLD-28/DZ

220-240V AC/50-60Hz

3h

24h

Overcharging and deep discharging protection

Charge LED, Lamp LED, Fault LED, Test Button

IP30

3.6V/1.5Ah

100lm /100lm 

125lm /125lm 

9.5 VA

9 VA

5 to 40  C

o

up to 95% 

ABS/PC, aluminum, Acrylic plate

280x120x15mm

3 years (1 year for the battery)

680gr.

1020gr.

1380gr.

340x190x15mm

440x240x15mm

289x65x34mm

TECHNICAL CHARACTERISTICS 

(for LED MODULE specifications see page 4)

Operation  temperature range

Relative humidity
Construction materials

External panel's dimensions
External unit’s dimensions

Typical weight

Guarantee

Mains voltage

Maximum power consumption
Battery (Ni-MH)

Recharging  time

Battery protection
Indications

Minimum emergency duration

Degrees of cover protection
Produced in accordance with 

Light source intensity (230V) / (emerg.)

Page 1 from 4

Description

The  Automatic  Autonomous  Test  is  conducted  and  measures  the 

The luminaire consists mainly from two parts.

luminaire`s  back  up  operation.  This  test  is  conducted  automatically 

The  body,  where  all  the  electronics  are  located  and  the  lamp-head 

every  six  months.  In  order  to  be  performed,  the  mains  power  supply 

where the indication sign and the high efficiency LEDs are located.

and the battery should be connected (the battery should be charged). 
If the battery is not charged, the test is postponed until the battery is 

Maintained/Non maintained selection capability

completely  charged.  If  during  the  Automatic  Autonomous  Test  the 

Power on the device and press continuously the TEST button for 10 

luminaire’s  duration  is  lower  than  the  nominal,  then  the  battery  must 

seconds,  until  the  led  strip  turns  off.  Release  the  button  and  after  a 

be replaced. 

short emergency test, the device operates as non-maintained. If you 
want to restore the previous condition (maintained  operation), press 

Back Up Operation

continuously  the  TEST  button  for  10  seconds,  until  the  led  strip 

The  autonomous  duration  of  battery  during  emergency  mode  is  at 

lights.  Release  the  button  and  after  a  short  emergency  test,  the 

least  the  one  that  is  stated  in  the  list  of  the  first  page.  During 

device operates as maintained illumination sign.

emergency mode, a LED strip test is also performed.

Installation

Resetting Errors

To  install  the  illumination  sign  follow  the  installation  instructions  on 

Push  the Test  button  for  >5  seconds,  to  delete  all  the  indicated  LED 

page 2.

errors. Then the luminaire enters regular operation mode.

Battery Charging

Indication LED status (with connected mains power supply).

The  battery  charging  is  completely  controlled.  In  this  case,  is 

Charge 

achieved the perfect  battery maintenance , as well as the elongation 

On: 

Good charge current.

of its duration. When the battery has completely charged, it charges 

Οff: 

No battery (No charging current or disconnected battery).

with a maintenance current.

Lamp Fault
Οn: 

Faulty LED strip or back up circuit.

Battery Cut-off

Off:

 Good LED strip or back up circuit.

The luminaire enters in this operation when

Battery Fault 

the mains power supply fails and battery has lost its energy. During 

Οff: 

Battery OK. 

this  operation  the  luminaire  enters  the  idle  state  and  battery 
consumption  is  negligible,  in  order  to  be  protected  from  deep 

Blink 

(With

 Charge LED

 ON): Autonomy or low battery problem 

(the 

discharge.

battery must be replaced).
Blink
 

(With

 Charge LED

 Off): 

Manual Test

No charging current or disconnected battery.

The  manual  test  can  be  conducted  only  if  the  mains  power  supply 
and  the  battery  is  connected.  By  pressing  the  test  button  briefly  an 
operation  test  is  initiated.  During  this  test  period  all  indication  LEDs 
are OFF.

Automatic Test

This test includes all the operations that provide the manual test and 
is conducted automatically every 15 days. In order to be performed, 
the mains power supply and the battery should be connected.

Automatic Autonomous Test

SELF TESTING MAINTAINED EMERGENCY ILLUMINATION SIGNS WITH WHITE LEDs

922044000_09_027

Thank you for your trust in our products  

Olympia Electronics - European manufacturer

EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3