background image

Multifunction Timer

H3DE

Analog Set Multifunction Timers

In Slim 22.5 mm Design

For Track Mounting

H

Wide AC/DC power supply range
(24 to 230 VAC/DC) minimizes inventory

H

12 VDC available in H3DE-M model

H

Programmable contacts (available in
-M2 and -S2 models) can enable and
disable a self-holding relay circuit

H

Eight operating modes in the H3DE-M
(four in the H3DE-S) offer wide
application flexibility

H

Time setting range 0.10 sec to 120 hrs

H

Finger protection terminal block

Ordering Information

J

TIMER

Description

Part number

Contact output

Supply voltage

Multifunctional

Standard

DPDT (time-limit output SPDT);

and switchable SPDT

(time-limit

←→

instantaneous)

12 VDC

H3DE-M2 DC12

(time-limit

←→

instantaneous)

24 to 230

VAC/DC

H3DE-M2 AC/DC24-230

H3DE-S2 AC/DC24-230

SPDT (time-limit output SPDT)

H3DE-M1 AC/DC24-230

H3DE-S1 AC/DC24-230

J

MODEL NUMBER LEGEND

H3DE-

j

-

j

-

j

1 2 3

1. M: Multifunction type

S: Standard type

2. 1: SPDT

2: DPDT

3. Supply voltage

J

ACCESSORIES (ORDER SEPARATELY)

Item

Description

Part number

Mounting track

50 cm (l) x 7.3 mm (t)

PFP-50N

1 m (l) x 7.3 mm (t)

PFP-100N

1 m (l) x 16 mm (t)

PFP-100N2

End plate

PFP-M

Spacer

PFP-S

Summary of Contents for H3DE-M1

Page 1: ...n terminal block Ordering Information J TIMER Description Part number Contact output Supply voltage Multifunctional Standard DPDT time limit output SPDT and switchable SPDT time limit instantaneous 12 VDC H3DE M2 DC12 time limit instantaneous 24 to 230 VAC DC H3DE M2 AC DC24 230 H3DE S2 AC DC24 230 SPDT time limit output SPDT H3DE M1 AC DC24 230 H3DE S1 AC DC24 230 J MODEL NUMBER LEGEND H3DE j j j...

Page 2: ...s 1 and 2 24 to 230 VAC DC 50 60 Hz 12 VDC H3DE M2 model only Operating voltage range 85 to 110 of rated supply voltage Power reset Minimum power off time 0 1 s Reset voltage 2 4 VAC DC max Power consumption S N t 3 H3DE M1 AC approx 4 3 VA 2 2 W at 230 VAC DC approx 0 7 W at 24 VDC p See Note 3 H3DE M2 AC approx 4 8 VA 2 4 W at 230 VAC DC approx 1 0 W at 24 VDC H3DE S1 AC approx 2 7 VA 1 6 W at 2...

Page 3: ...mulator pulse width 100 ns 1 µs 1 ns rise 1 5 kV Static immunity Malfunction 4 kV Destruction 8 kV Life expectancy Mechanical 10 million operations min under no load at 1 800 operations h Electrical 100 000 operations min 5 A at 250 VAC resistive load at 360 operations h See Note 2 EMC EMI Emission Enclosure EN55011 Group 1 class A Emission AC Mains EN55011 Group 1 class A Harmonic Current EN61000...

Page 4: ...ndicator orange Lit while Timer gives output Operating mode selector select a mode from A B C B2 D E J and G for the H3DE M1 M2 from A E J and B2 for the H3DE S1 S2 Power on indicator green Lit while the power is on Nameplate 20 x 5 4 mm white panel Time unit selector select one from sec min hrs and 10 h Main dial for setting a time value Time scale selector select 0 1 or 1 Time scale indicator Ti...

Page 5: ...ctors Counting circuit Operating mode selector Output circuit Indicator circuit Power ON indicator Output indicator H3DE S1 S2 J I O FUNCTIONS Item H3DE M1 M2 H3DE S1 S2 Input Start Starts operation No input is available Output Control output Outputs are turned ON according to designated output mode when preset value is reached See Note Note When the output type selector switch on the bottom of th...

Page 6: ...played in the time unit display window above the time setting dial by turning the time unit selector located at the upper right corner of the front panel The time scale 0 1 or 1 is selected with the time scale selector at the upper left corner of the front panel It appears in the scale range display window above the selector Scale range selector Scale range display window Time unit selector Time u...

Page 7: ...t t t t a t t t a For power on operation impose voltage to the Start input The Timer starts operating at the moment the power is turned on Start input is invalid while the Timer is in opera tion Output relay NC 15 and 16 25 and 26 Output relay NO output indicator 15 and 18 25 and 28 C Signal ON OFF delay Basic operation Power Start Output t t t t Power A1 and A2 Start B1 and A2 See Note Power indi...

Page 8: ...N OFF delay Power A1 and A2 Start B1 and A2 See Note Power indicator Power Start Output Basic operation Start input is valid and re triggerable while the Timer is in operation t t t t Output relay NC 15 and 16 25 and 26 Output relay NO output indicator 15 and 18 25 and 28 J One shot output ON delay Power A1 and A2 Start B1 and A2 See Note Power indicator Power Start Output Basic operation For powe...

Page 9: ...R1 R2 See Note 1 18 16 18 16 A2 B1 28 24 26 22 28 24 26 22 A1 15 25 21 H3DE M1 H3DE S1 H3DE M2 H3DE S2 15 R1 18 16 18 16 A2 B1 A1 15 15 R1 18 16 18 16 A2 A1 15 See Note 2 See Note 2 See Note 2 See Note 2 Note 1 The contact symbol for the H3DE is indicated with because it offers multiple operating modes and is different from the delayed contact for conventional timers 2 DC supply voltage does not r...

Page 10: ... Voltage Input Signal Levels No contact input 1 Transistor ON Residual voltage 1 V max voltage between terminals B1 and A2 must be more than the rated H level voltage 20 4 VDC min 2 Transistor OFF Leakage current 0 01 mA max voltage between terminals B1 and A2 must be less than the rated L level voltage 2 4 VDC max Contact input Use contacts that can adequately switch 0 1 mA at each voltage to be ...

Page 11: ...ote Important Do not change the time unit time scale operating mode or output type selector switch while the Timer is in operation J MOUNTING AND REMOVAL The H3DE should be mounted as horizontally as possible When mounting the H3DE on a socket mounting track hook portion A of the Timer to an edge of the track first and then depress the Timer in the direction of B A B When removing the H3DE pull ou...

Page 12: ...e Timer may not be reset or a timer error could result For the power supply of an input device use an isolating transformer of which the primary and secondary windings are mutually isolated and the secondary winding is not grounded H3DE Power supply Circuit Isolation transformer is required Rectifier circuit Start input B1 A1 A2 J MOUNTING CLEARANCE If the load current is continuously being suppli...

Page 13: ...2 H3DE B1 A1 A2 Short circuit current Contact or transistor for external input signal H3DE Power supply B1 A1 A2 H3DE B1 A1 A2 Short circuit current Note The H3DE Series is provided with a transformerless pow er supply system J INPUT WIRES The input wires must be as short as possible If the floating capacity of wires exceeds 2 000 pF approx 17 m for cables with 120 pF m the operation will be affec...

Page 14: ...ure and humidity are within the rated values Leave the Timer at room temperature for at least three hours before using the Timer if it has been stored at an ambient temperature of 10 C or below J RELAY LIFE EXPECTANCY Built in relay for the H3DE G6RN 50 000 operations min 8 A at 250 VAC resistive load at 360 operations h Cat No GC TMCN1 3 02 Specifications subject to change without notice Printed ...

Reviews: