Motor Protective Relay

K2CM

Solid-state Relay Enables Choice of Three 

Operating Functions (Overcurrent, Open-

phase, and Reverse-phase)

• Protects 3-phase induction motors and their loads from damage.
• Selection and combination of operating functions from overcur-

rent, open-phase, and reverse-phase.

• Circuit and output relay operation can be checked by just operat-

ing the test button.

• The set time value can be checked easily because operation time 

is indicated from the start of operation.

• Space-saving, integrated construction.

Note:

If the K2CM is used with an inverter, the operating conditions will 

depend on the load wiring length, inverter carrier frequency, basic 

frequency, and load conditions. Error will occur in the operating 

values of the overload elements. It is recommended to test operation 

before using the K2CM.

Model Number Structure

Model Number Legend

1. Model

K2CM: Motor relay

2. Mounting style

None: Surface-mounting, integrated type

3. Operating time characteristics

None: Inverse type
Q:

Instantaneous type

4. Supply voltage of control circuit

1:

100/110/120 VAC

2:

200/220/240 VAC

4:

400/440 VAC

5. Current setting range

LS:

2 to 8 A

L:

8 to 26 A

M:

20 to 65 A

H:

50 to 160 A

6. Operating time

None:

×

1 (2 to 10 s)/ 

×

4 (8 to 40 s) Switchable

7. Resetting method

None: Manual reset
A:

Automatic reset

8. Reverse-phase detection type

None: Current reverse-phase detection
V:

Voltage reverse-phase detection

Ordering Information

List of Models

Voltage Reverse-phase Detection Models

1

2 3 4

5 6

K2CM-

@@@

-

@@

Time specification

Inverse type

Instantaneous type

Resetting

 method

Current setting range

8 to 26 A

20 to 65 A

50 to 160 A

8 to 26 A

20 to 65 A

50 to 160 A

Operating voltage

Manual

200/220/240 VAC

K2CM-2LV

K2CM-2MV

K2CM-2HV

K2CM-Q2LV

K2CM-Q2MV

K2CM-Q2HV

Automatic 200/220/240 VAC

K2CM-2LAV

K2CM-2MAV

K2CM-2HAV

K2CM-Q2LAV

K2CM-Q2MAV

K2CM-Q2HAV

Summary of Contents for K2CM Series

Page 1: ...ng the K2CM Model Number Structure Model Number Legend 1 Model K2CM Motor relay 2 Mounting style None Surface mounting integrated type 3 Operating time characteristics None Inverse type Q Instantaneou...

Page 2: ...AC 2 A 440 VAC 1 A 110 VDC 0 2 A 220 VDC 0 1 A Contact form of output contact Current reverse phase detection models SPST NO SPST NC Voltage reverse phase detection models SPDT Operating current range...

Page 3: ...Current reverse phase detection models 6 000 V between current carrying terminals and mounting panel 4 500 V between current carrying terminals and between control power supply terminals Waveform 1 2...

Page 4: ...Manual Operation High voltage Circuit Note Connect the phase advancing capacitor on the power supply side of the Motor Protective Relay as shown in the above dia grams Ta Tc Tb U V W Output contacts...

Page 5: ...t High capacity Motor Automatic Operation Low voltage Circuit Manual Operation High voltage Circuit S1 C2 b2 a1 c1 S2 Output contacts NO and NC Control power supply R S T BZ R U A 1 S V B 2 T W C 3 a1...

Page 6: ...ens of seconds to settle to the rated current This time varies largely depending on type of motor and the nature of motor load wt There fore it is necessary to obtain the motor s starting time for ope...

Page 7: ...required for the detection of inter nal open phases in delta connected motors Consult your OMRON representative before using this method When a transformer is con nected as a load the harmonics increa...

Page 8: ...n is released after the motor circuit has tripped the circuit remains tripped whereas with automatic resetting models the motor circuit continues operating and the output relay releases Deciding the N...

Page 9: ...is made at the load side far from the current transformer and the motor rotates in the re verse direction the K2CM does not detect the reverse phase Reverse detectable Range The OR phase circuit in th...

Page 10: ...aracteristics for Inverse Type Overload Operating Time Characteristics for Instantaneous Type 2 0 1 0 0 100 200 300 400 500 600 700 This graph shows the behavior when the current changes from 100 of t...

Page 11: ...ive motor full load characteristics of 200 VAC 4 pole totally enclosed Note When using a large capacity or high voltage motor whose capacity is 45 kW or more calculate the rated current alternating cu...

Page 12: ...the input phases for the cur rent transformer 2 Turn ON SW1 and SW2 Gradually increase the current by adjusting the voltage regulator 3 Confirm that the K2CM operates at a current no greater than 85 o...

Page 13: ...3 Using the voltage regulator abruptly increase the current to 140 of the set current value Confirm that the K2CM performs the instantaneous operation 4 Turn OFF SW1 and SW2 Open phase 1 Open disconn...

Page 14: ...ection of a high voltage motor or low voltage high capacity motor use an external rectifier that does not saturate at currents up to 600 of the rated motor current and thus permits a large overcurrent...

Page 15: ...ase with the K2CM Connection Method Pass wires through any two of the three holes on the K2CM If a single phase is used set the open phase and reverse phase switch to OFF Make the overload settings so...

Page 16: ...ther in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted Suitability of Use Omron Companies shall not be responsible for conformity...

Page 17: ...2CM 1LA K2CM 1LS K2CM 1M K2CM 1MA K2CM 2H K2CM 2HA K2CM 2L K2CM 2LA K2CM 2LS K2CM 2M K2CM 2MA K2CM 4H K2CM 4HA K2CM 4L K2CM 4LA K2CM 4M K2CM 4MA K2CM Q1H K2CM Q1HA K2CM Q1L K2CM Q1LA K2CM Q1LS K2CM Q1...