background image

1

Single-phase Overvoltage/Undervoltage Relays

K8AK-VW

Ideal for voltage monitoring for 

industrial facilities and equipment.

• Monitor for overvoltages and undervoltages simultaneously.

Separate settings and outputs supported for overvoltages and 

undervoltages.

• Manual resetting and automatically resetting supported by one 

Relay.

• Pre-alarm Monitoring Mode.

• Two SPDT output relays, 5 A at 250 VAC (resistive load).

• Process control signal (0 to 10 V) and current splitter input 

supported.

• Output status can be monitored using LED indicator.

• Input frequency of 40 to 500 Hz supported.

• Inputs are isolated from the power supply.

Ordering Information

List of Models

Ratings and Specifications

Input Range

* The range is selected using connected terminals.

Refer to 

Safety Precautions for the K8AK Series

 on page 86.

Refer to page 38 for commonly asked questions.

For the most recent information on models that have been certified for 

safety standards, refer to your OMRON website.

Setting range

Supply voltage

Model

1 to 10 V AC/DC

3 to 30 V AC/DC

15 to 150 V AC/DC

24 VAC/DC

K8AK-VW2 24 VAC/DC

100 to 240 VAC

K8AK-VW2 100 to 240 VAC

20 to 200 V AC/DC

30 to 300 V AC/DC

60 to 600 V AC/DC

24 VAC/DC

K8AK-VW3 24 VAC/DC

100 to 240 VAC

K8AK-VW3 100 to 240 VAC

Model

Range 

*

Connection terminal

Setting range

Input impedance

Overload capacity

K8AK-VW2

0 to 10 V AC/DC

V1-COM

1 to 10 V AC/DC

3 to 30 V AC/DC

15 to 150 V AC/DC

Approx. 120 k

Ω 

Continuous input at 115% of 

maximum input.

10 s at 125%

(up to 600 VAC)

0 to 30 V AC/DC

V2-COM

Approx. 320 k

Ω

 

0 to 150 V AC/DC

V3-COM

Approx. 1.6 M

Ω

K8AK-VW3

0 to 200 V AC/DC

V1-COM

20 to 200 V AC/DC

30 to 300 V AC/DC

60 to 600 V AC/DC

Approx. 1.2 M

Ω

0 to 300 V AC/DC

V2-COM

Approx. 1.7 M

Ω

0 to 600 V AC/DC

V3-COM

Approx. 3.1 M

Ω

Summary of Contents for K8AK-VW2

Page 1: ...s for the K8AK Series on page 86 Refer to page 38 for commonly asked questions For the most recent information on models that have been certified for safety standards refer to your OMRON website Setti...

Page 2: ...e load 5 A at 250 VAC 5 A at 30 VDC Maximum contact voltage 250 VAC or 30 VDC Max switching current 5 A Maximum switching capacity 1 250 VA 150 W Mechanical life 10 million operations min Electrical l...

Page 3: ...SA C22 2 No 14 CCC GB14048 5 Insulation resistance 20 M min Between all external terminals and the case Between all power supply terminals and all input terminals Between all power supply terminals an...

Page 4: ...riod when the power is first turned on There is no relay output during timer operation Note There is no polarity when a DC current input is used T T1 T AL1 alarm indicator Overvoltage AL1 relay Input...

Page 5: ...s 1 and 2 Terminal block See notes 1 and 2 Item Meaning Power indicator PWR Green Lit when power is being supplied Relay status indicator RY Yellow Lit when relay operates Not light when both AL1 and...

Page 6: ...Example K8AK VW3 Using Input Terminal V3 COM The maximum setting range will be 600 VAC VDC and the setting range will be 60 to 600 V 2 Operating Time The operating time is set using the operating time...

Page 7: ...phase Voltage Relays Optional Parts for DIN Track Mounting 22 5 90 100 72 5 K8AK VW2 K8AK VW3 Dimensions in parentheses are for the PFP 50N 4 5 15 25 25 10 10 1 000 500 25 25 15 5 35 0 3 7 3 0 15 27...

Page 8: ...onnection Diagram How to Measure the Operating Time Overvoltage Change the input suddenly from 0 to 120 of the set value and measure the time until the Unit operates Undervoltage Change the input sudd...

Page 9: ...s 2 Use and store the product in a location where the ambient temperature and humidity are within the specified ranges If applicable provide forced cooling 3 Mount the product in the correct direction...

Page 10: ...will be large if the K8AK AS K8AK AW K8AK VS or K8AK VW is used for thyristor or inverter control The K8AK PH K8AK PA K8AK PM K8AK PW or K8DS PH cannot be used on the secondary side of an inverter To...

Page 11: ...nt or addition to the above warranty See http www omron247 com or contact your Omron representative for pub lished information 14 Limitation on Liability Etc OMRON COMPANIES SHALL NOT BE LIABLE FOR SP...

Page 12: ...rasil 55 11 2101 6300 www omron com br OMRON ARGENTINA SALES OFFICE Cono Sur 54 11 4783 5300 OMRON CHILE SALES OFFICE Santiago 56 9 9917 3920 OTHER OMRON LATIN AMERICA SALES 54 11 4783 5300 OMRON INDU...