background image

USER’S MANUAL

Cat. No. V084-E1-01

NT11

Programmable Terminal

Summary of Contents for NT11 - 01-2004

Page 1: ...USER S MANUAL Cat No V084 E1 01 NT11 Programmable Terminal ...

Page 2: ...NT11 Programmable Terminal User s Manual Produced January 2004 ...

Page 3: ...iv ...

Page 4: ...n in this sense The abbreviation PLC means Programmable Controller PC is used however in some Program ming Device displays to mean Programmable Controller Host means a personal computer that controls the NT11 Visual Aids The following headings appear in the left column of the manual to help you locate different types of information Note Indicates information of particular interest for efficient an...

Page 5: ...vi ...

Page 6: ...4 Connection to a PLC by the Host Link RS 232C Type 22 2 5 Connection to a PLC by the Host Link RS 422A Type 38 2 6 Connection to a PLC by the NT Link RS 232C Type 50 2 7 Connection to a PLC by the NT Link RS 422A Type 55 2 8 Connecting a Printer 57 SECTION 3 System Menu Operation 59 3 1 Operation Flow by the System Menu 60 3 2 Starting the NT11 60 3 3 Operation Modes and the System Menu 61 3 4 In...

Page 7: ...ne of Host Link NT Link Operation 109 5 3 Memory Table Entries and Bar Graph 115 5 4 Numeral Setting 126 5 5 NT11 Status Control 129 5 6 Notification of the Operating Status to the PLC Determining the NT11 Operating Status 132 SECTION 6 Troubleshooting and Maintenance 135 6 1 Troubleshooting 136 6 2 Responding to Displayed Error Messages 138 6 3 Inspection and Cleaning 142 Appendices A Specificati...

Page 8: ...ion 3 describes the operation of the System Menu and the maintenance of the NT11 Section 4 describes the functions of the NT11 when it is connected to a PLC Section 5 describes how to use the NT11 when it is connected to the PLC using the host link or NT link Section 6 describes the procedures to follow when the NT11 does not operate correctly APPENDIX describes the specifications and the method f...

Page 9: ... This manual This user s manual is the manual for the NT11 V itself The NT11 is a unit which integrates a programmable terminal body This user s manual describes the functions and handling of the programmable terminal body Creating and transferring screen data NT series Support Tool Operation Manual V061 E1 The screens displayed on the NT11 are created with the support tool and transferred to the ...

Page 10: ...contained in this section is important for the safe and reliable application of the Programmable Terminal You must read this section and understand the information contained before attempting to set up or operate a Programmable Terminal 1 Intended Audience xii 2 General Precautions xii 3 Safety Precautions xii ...

Page 11: ...ormation for using the Programmable Terminal Be sure to read this manual before attempting to use the software and keep this manual close at hand for reference during operation WARNING It is extremely important that Programmable Terminals and related devices be used for the specified purpose and under the specified conditions especially in applications that can directly or indirectly affect human ...

Page 12: ...heeded could result in relatively serious or mi nor injury damage to the product or faulty operation WARNING Do not attempt to take the Unit apart and do not touch any internal parts while the power is being supplied Doing either of these may result in electrical shock ...

Page 13: ...xiv Safety Precautions 3 ...

Page 14: ...1 so that you will understand the applications of the NT11 1 1 Getting Starting 2 1 2 Role and Operation of NT11 2 1 2 1 Operations of NT11 3 1 3 Functions of NT11 4 1 3 1 Features 4 1 3 2 Principal Functions of NT11 5 1 3 3 Displays 6 1 3 4 System Keys 7 1 4 System Configuration 8 1 4 1 Peripheral Devices That Can Be Connected 8 1 5 Direct Connection Function 9 1 5 1 NT Link 9 1 5 2 Functions of ...

Page 15: ...vents such as benzene thinner or a chemically treated cloth Their use will cause deformation or discoloration Cautions on Afterimage If the same screen contents are kept displayed for a long time an afterimage may occur To prevent this problem either set the afterimage prevention func tion or make a program which periodically changes the displayed screen Cautions on Operating the System Keys Do no...

Page 16: ... and stored in the NT11 The screen data can be dis played on the NT11 in response to the instructions from a PLC or system keys operation Receives Data from a PLC NT11 can be connected to a PLC by a host link or NT link and receive neces sary data from the PLC Sends Data to a PLC Data input through a numeric key can be sent to a PLC Assembly line B Positioning pin A l a r m Positioning Z AXIS 80 p...

Page 17: ...422A and printer output The tool connectors and the PLC communication connectors are used in common Construction Best Suited to the FA Environment Easy to read screen even in direct sunlight Waterproofed to a standard equivalent to IP65 and NEMA4 A Host I F Unit Screen Data Memory and a system program transfer ROM are All Incorporated There is no complicated installation work except a simple conne...

Page 18: ...tting function The screen data can be created by using support tools on the computer and stored in the unit The system setting and maintenance can be executed by using the System Menu on the screen The numeric values can be input at the operation site by the system key and sent to the PLC Data can be input and the displayed screen changed by using the numeric keys function keys and arrow keys on t...

Page 19: ...table A percentage value can also be displayed simulta neously Marks Marks can be designed created and handled like characters by the user Comparison with the NT11S Emergency transfer mode When power to the NT11 is turned ON with DIP switch pin 3 turned ON data transfer mode will be entered directly without any other operation Line 1 Status Machine NT11 SF121 Product 137 units 75 Numeric value Num...

Page 20: ...r notifications from the NT11 to the PLC Also used to switch between the RUN mode and the system menu when the power is switched on Caution Do not use input functions such as PT function keys for applications where danger to human life or serious property damage is possible or as the emer gency stop switch Caution If function keys are pressed in rapid succession their inputs may not be suc cessful...

Page 21: ...max An RS 422A 485 cable 500 m max can be connected through an RS 232C RS 422A Adapter Used to create screens for the NT11 at the personal computer and transfer them to the NT11 and to make NT11 settings Controls the NT11 as required while controlling machines and monitoring the production line Host NT Link C series PLCs CVM1 CV series PLCs SRM1 Can be connected to CPU Units and SRM1 However conne...

Page 22: ...and words referring to operating status and work instruction infor mation and those for storing input data can be freely allocated to almost any part of the PLC memory Bits and words in the PLC can be refer enced from any memory table The NT11 can directly refer to PLC bit and word data so that it can be connected to a PLC without changing the PLC program which controls currently running productio...

Page 23: ...iting to a memory table copying from a memory table to another memory table etc System control ON OFF of backlight control of output of daily reports and display histories at a printer Notifying from the NT11 to a PLC Data in the NT11 is sent to a PLC when a numeric key is pressed The fol lowing types of data are sent to a PLC NT11 status Password input status Numeric values input by the numeral k...

Page 24: ...n the PLC the NT11 reads the contents and operates according to the contents Example of the PT status control area application When data is written to the PT status control area the NT11 will operate as given below Functions of the PT Status Notify Area NT11 to PLC The PT status notify area is used to notify the changes of the NT11 status When a change is made in the NT11 status the change is writ...

Page 25: ...ord numeral table 13 PLC NT11 Support tool Check and change the PLC settings Connect to the NT11 Create the PLC program Set the DIP switches Install to the operation panel Connect the power sup ply Connect to the PLC Check the settings and communications Transfer the screen data Transfer the system program by using the system transfer tool refer to Section 4 and the manuals for the support tools C...

Page 26: ...ide W302 E1 SYSMAC C200HX HG HE Operation Manual W303 E1 SYSMAC C200HX HG HE Z Operation Manual W322 E1 SYSMAC CQM1 CPM1 CPM1A SRM1 Programming Manual W228 E1 SYSMAC CQM1H Operation Manual W363 E1 SYSMAC CVM1 CV500 CV1000 CV2000 CVM1 Operation Manual Ladder Dia grams W202 E1 CS Series Programmable Controllers Operation Manual W339 E1 CJ Series CJ1G CPU E Programmable Controllers Operation Manual W...

Page 27: ...14 Before Operating Section 1 6 ...

Page 28: ...rt Tool 22 2 4 Connection to a PLC by the Host Link RS 232C Type 22 2 4 1 Compatible PLCs 23 2 4 2 Connecting the NT11 24 2 4 3 PLC Switch Settings 27 2 5 Connection to a PLC by the Host Link RS 422A Type 38 2 5 1 Compatible PLCs 38 2 5 2 Parts Required for Connection 40 2 5 3 Method for Connection 40 2 5 4 Connector Specifications and Wiring for Each Unit 41 2 5 5 PLC Switch Settings 42 2 6 Conne...

Page 29: ...omes in two body colors NT11 SF121 EV1 Beige NT11 SF121B EV1 Black Function keys Used for direct notifications to the PLC POWER LED Lit when the power is supplied Display An LCD screen with a backlight Arrow keys Used to select the required numerical value input field when there is more than one on the screen Numeric keys Used for inputting numerical values on screens that require numerical value ...

Page 30: ...nnection Connect the printer cable here Interface conforms to Centronics specifications Contrast control Use a fine phillips screwdriver Turn clockwise to increase the brightness DIP switch Set various system statuses with these switches RS 422A terminal block Connect the PLC cable here RS 232C connector Connect the cable that connects the PLC or support tool here ...

Page 31: ...he Memory Switches page 71 Caution After changing the switch settings always press the reset switch or turn the power off and back on Otherwise the system will not operate as expected Caution Confirm system safety before turning the power ON OFF or resetting Otherwise the system may operate unpredictably Correct Use Use the System program erase function only when changing the system program It the...

Page 32: ...ct may malfunction Static electricity or noise from other equipment Strong electromagnetic fields Nearby power cables Potential exposure to radioactivity 2 2 1 Installation to the Operation Panel The NT11 can be flush mounted to an operation panel Use the panel fittings and tools included in the product package and follow the procedure below Caution On unpacking the unit check its external appeara...

Page 33: ...he power input terminals Caution Carefully check the wiring before switching ON the power Caution Do not connect AC power to the DC terminals Caution Use DC and AC power supplies with low voltage and frequency fluctuations Caution Do not perform withstand voltage test Performing withstand voltage test may result in malfunction Noise prevention The NT11 has a noise preventive feature against the po...

Page 34: ...logy Inc STMicroelectronics 2 2 3 Wiring the Ground Wire The PT is provided with a functional ground FG terminal Wire the FG terminal according to the following conditions 1 Ground according to Figure when there is difference in potential between the PT and host Do not ground the functional ground of the PT if it is far from the host and one point grounding is difficult 2 Do not ground the functio...

Page 35: ...ool are started Recommended Connector Cable Use the cable indicated below XW2Z S002 length 2 m made by OMRON D SUB 9 pin male Û D SUB 9 pin female For details on making a connector cable refer to Appendix E Making the Cable for Connecting a Personal Computer page 155 2 4 Connection to a PLC by the Host Link RS 232C Type Connect the NT11 to an OMRON PLC by using RS 232C type the host link method In...

Page 36: ... CS1H H CJ Series CJ1G CPU44 45 CJ1G CPU44 45 CJ1W SCU41 CJ1G C Series C200HS CPU01 03 21 23 31 33 E C200HE CPU11 32 42 E C200HE CPU11 32 42 ZE C200HG CPU33 43 53 63 E C200HG CPU33 43 53 63 ZE C200HX CPU34 44 54 64 E C200HX CPU34 44 54 64 65 85 ZE C200H LK201 EV1 C200HS C200HE C200HE Z C200HG C200HG Z C200HX C200HX Z C200HS CPU21 23 31 33 E C200HS C200HE CPU42 E C20HE CPU42 ZE C200HE CPU32 42 E C2...

Page 37: ...this Otherwise a discontinuity may occur causing operation to fail Connecting to a PLC with a 25 pin Connector Use a connector cable with a 25 pin connector on one end and a 9 pin con nector on the other end NT11 side to connect the NT11 to a PLC with a 25 pin connector Connecting to a PLC with a 9 pin Connector Use a connector cable with a 9 pin connector on both ends to connect the NT11 to a PLC...

Page 38: ... XW2Z 500S 9 pin Û 25 pin 5 m Name Model Remarks Delivered with Connector XM2A 0901 9 pin Made by OMRON CS series CS1G CS1H CS1G H CS1H H CJ series CJ1G C series CQM1 C200HS C200HX HG HE Z E CVM1 CV series CPU Units CV500 LK201 XM24 2501 25 pin Made by OMRON CV500 LK201 C200H LK201 EV1 Connector hood XM2S 0911 9 pin Made by OMRON C series CQM1 C200HS C200HX HG HE Z E CVM1 CV series CPU Units CV500...

Page 39: ... 10 CPM2C 20 CQM1 CPU21 E CQM1 CPU41 EV1 CQM1 CPU42 EV1 CQM1 CPU43 EV1 CQM1 CPU44 EV1 CQM1H CPU11 CQM1H CPU21 CQM1H CPU51 CQM1H CPU61 CS1G CPU42 E V1 CS1G CPU43 E V1 CS1G CPU44 E V1 CS1G CPU45 E V1 CS1H CPU63 E V1 CS1H CPU64 E V1 CS1H CPU65 E V1 CS1H CPU66 E V1 CS1H CPU67 E V1 CS1G CPU42H CS1G CPU43H CS1G CPU44H CS1G CPU45H CS1H CPU63H CS1H CPU64H CS1H CPU65H CS1H CPU66H CS1HCPU67H CJ1G CPU44 CJ1G...

Page 40: ...or respective units for the details of the switch settings 1 Set the host link baud rate up to 115 200 bps with the memory switch for host link baud rate For the details refer to 3 7 2 Selecting the Host Link Communication Speed page 74 2 The 1 to N setting enables BCC Block Check Character The 1 to 1 con nection cannot be used to connect the NT11 to a host link unit 1 6 5 9 1 6 5 9 FG 5V CS RS RD...

Page 41: ...tors at these ports are of different types a cable that matches the connector must be pre pared Communication port 1 Communication port 1 is a 25 pin connector for RS 232C use only Communication port 2 Communication port 2 is a 9 pin connector that allows selection of the RS 232C or RS 422A method When this port is used with the RS 232C method the I O port selector switch on the front of the Unit ...

Page 42: ...Front Switches Set the unit number of the Serial Communications Unit by using the rotary switch located on the front panel Set each switch with a flat blade screwdriver Item Setting at Host Baud rate Set the same baud rate as set at the NT11 1 Transfer code ASCII 7 data bits 2 stop bits Parity Even 1 to 1 1 to N 1 to N 2 Command level Level 1 2 3 RS 232C Communications port 1 RS 232C Communication...

Page 43: ...es CPU Unit set the following communi cation conditions for the PLC Setup 1 Set the Host Link baud rate at 9 600 bps with the memory switch at the NT11 For details refer to Setting the Host Link Method page 74 Set the unit number to 0 through F so that it will not duplicate the numbers used in other Units SCU21 RUN ERC SD1 RD1 RDY ERH SD2 RD2 UNIT No FE C 1 0 CS1W SCU21 CJ1W SCU41 Set the unit num...

Page 44: ...ial Communications Board CQM1H Connect to the CPU Unit s built in RS 232C port Connect to the peripheral port through a CS1W CN118 Connecting Cable Connect to the RS 232C port port 1 on a Serial Commu nications Board CPM1 Connect to the peripheral port through a CPM1 CIF01 RS 232C Adapter RS 232C I O port selector switch RS 422A Host Link Communication method System setting Pin 4 DIP switch settin...

Page 45: ...M1 Peripheral port connection CPM2A SRM1 Connect to the CPU Unit s built in RS 232C port Connect to the peripheral port through a CPM1 CIF01 RS 232C Adapter CPM2C Connect to the CPU Unit s RS 232C port or the peripheral port through a Connecting Cable CPM2C CN111 CS1W CN118 or CS1W CN114 The CPM2C CN111 splits the Unit s Communication Port into a RS 232C port and a peripheral port A CPM1 CIF01 RS ...

Page 46: ...01 Host Link mode no CTS control Communication conditions set by the contents of DM DM6646 0303 Data length 7 bits 2 stop bits even parity baud rate 9 600 bps 0304 Data length 7 bits 2 stop bits even parity baud rate 19 200 bps DM6648 0000 Unit 00 Word Writing Value Settings DM6555 0001 Host Link mode no CTS control Communication conditions set by the contents of DM DM6556 0303 Data length 7 bits ...

Page 47: ...PM2C When using a CPM2C the switches on the front panel must be set as shown below in order to make the PLC Setup settings effective Port connecting to PT PLC Setup RS 232C port D Sub 9 pin of CPM2C CN111 Built in RS 232C port settings Peripheral port of CPM2C CN111 Peripheral port settings RS 232C port D Sub 9 pin of CS1W CN118 Built in RS 232C port settings Peripheral port of CS1W CN114 Peripher...

Page 48: ...et the Host Link baud rate up to 115 200 bps with the memory switch at the NT11 For details refer to Settings the Host Link Method page 74 When the baud rate is set to 19 200 bps the PLC Setup of the CPU Unit need to be changed Either set the PLC Setup directly from a Programming Device Programming Console or transmit the PLC Setup made at a Programming Device CX Programmer to the CPU Unit The set...

Page 49: ...dress Writing Value Settings CIO 160 8000 Host Link mode data length 7 bits 2 stop bits even parity CIO 161 0000 Baud rate 9 600 bps 0007 Baud rate 19 200 bps 0008 Baud rate 38 400 bps 0009 Baud rate 57 600 bps 000A Baud rate 115 200 bps CIO 166 0000 Unit 00 Word address Writing Value Settings CIO 144 8000 Host Link mode data length 7 bits 2 stop bits even parity CIO 145 0000 Baud rate 9 600 bps 0...

Page 50: ...ports the RS 232C Unit connection RS 232C port This is used mainly for connection to the RS 232C Unit This also supports a CX Programmer connection SYSMAC CS1G PROGRAMMABLE CONTROLLER CPU42 OPEN OPEN PERIPHERAL PORT BUSY RUN ERR ALM INH PRPHL COMM MCPWR CS1G H CS1G H H CJ1G DIP switches inside the battery storage Peripheral port This is used mainly for connection to the Programming Device This als...

Page 51: ...ing the Host Commu nication Method page 73 2 5 1 Compatible PLCs When Using the Host Link Method Compatible Host Units Some models and series of OMRON PLCs have the RS 422A type Host Link function built in With a CS series CJ series and CQM1H Board or Unit and CQM1H the Host Link method can be used by installing a Serial Communica tions Board In addition some C200HX HG HE Z E devices have an integ...

Page 52: ...5H 66H 67H CS1G CS1H CS1G H CS1H H CJ Series CJ1W SCU41 CJ1G CPU44 45 CJ1G C Series C200H LK202 V1 C200HS CPU01 03 21 23 31 33 E C200HS CPU01 21 EC C200HE CPU11 32 42 E C200HE CPU11 32 42 ZE C200HG CPU33 43 53 63 E C200HG CPU33 43 53 63 ZE C200HX CPU34 44 54 64 E C200HX CPU34 44 54 64 65 85 ZE C200HS C200HE C200HE ZE C200HG C200HG ZE C200HX C200HX ZE C200HW COM03 06 EV1 C200HE CPU32 42 E C200HE CP...

Page 53: ...terminals for wiring 2 Before connecting or disconnecting cables between devices make sure that the power supply to all of the connected devices NT11 PLC etc is OFF Examples of applicable terminals 2 5 3 Method for Connection For RS 422A type communication an RS 422A cable is used as the transmis sion channel connecting the NT11 and PLC As shown in the figure below the RS 422A cable is connected d...

Page 54: ...combination among those indicated below For details on making the cable refer to Appendix D Making the Cable page 153 NT11 RS 422A terminal block specifications Connected terminal block RS 422A terminal block M3 5 screws Electrical characteristics Conform to EIA RS 422A Signal direction Signal input and output is relative to the NT11 Connecting an NT11 to a C series host link unit C series host li...

Page 55: ...C200HG Z E C200HX Z E Rack mounting model C200H LK201 V1 Setting the Front Switches Set each switch with a flat blade screwdriver so that the values or symbols in the setting value window agree with the following Connector Pin No Signal Name Abbreviation Signal Direction Input Output 1 Receive data B RDB 3 Signal ground SG 5 Send data B SDB 6 Receive data A RDA 7 Frame ground FG 9 Send data A SDA ...

Page 56: ...the CPU Bus Unit settings 1 Set the Host Link baud rate at 9 600 bps or 19 200 bps with the Comm Speed memory switch at the NT11 For details refer to Setting the Host Link Method page 74 2 The 1 to N setting enables BCC Block Check Character It is not actually possible to connect more than one NT11 in a single Host Link LK201 RUN RCV XMT ERROR SW1 0 0 5 2 Unit SW1 SW2 Set these switches to 0 Comma...

Page 57: ...ramming Device a Programming Console or CX Programmer directly into the allocated DM Area PLC Setup of the Communications port 1 RS 232C Communications port 2 RS 232C RS 422A I O port selector switch RS 422A Unit SW3 SW4 Set these switches to 0 Communication condition setting pin 1 I O port selection selector switch Set this to RS 422A RS 232C Terminating resistance setting selector switch Set thi...

Page 58: ...te at 9 600 bps or 19 200 bps with the Comm Speed memory switch at the NT11 For details refer to Setting the Host Link Method page 74 Set the PLC Setup directly from a Programming Device e g SYSMAC Sup port Software For details on the PLC Setup refer to the SYSMAC CVM1 CV500 CV1000 CV2000 Operation Manual Ladder Diagrams W202 E1 Allocated DM word Value Settings Port 1 m 8000 Host Link mode 2 stop ...

Page 59: ... or CS1W CN114 Connecting Cable through a CPM1 CIF11 RS 422A Adapter The CPM2C CN111 splits the Unit s Communication Port into a RS 232C port and a peripheral port I O port selector switch RS 422A Host Link communication method selection selector switch Set this to RS 422A Host Link default value settings Existing DIP switch settings PLC Setup default values RS 232C Terminator setting pin 6 Set th...

Page 60: ...w When using port A of the Serial Communications Board of C200HX HG HE Z E When using a CPM1 CPM2A CPM2C SRM1 Item Setting at Host I O port RS 422A Communication mode Host Link mode Baud rate Set the same baud rate as for the NT11 1 Stop bits 2 stop bits Parity Even Data length ASCII 7 bits Unit 00 Word Writing Value Settings DM6555 0001 Host Link mode no CTS control Communication conditions set b...

Page 61: ...nications Board as follows Switch 1 Set to 4 4 wire for RS 422A Switch 2 Set to ON for terminator ON terminating resistance applied Setting Switches on a CQM1H Serial Communications Board Set the switches on a CQM1H Serial Communications Board as follows Wire selection WIRE Set to 4 4 wire for RS 422A Terminator TERM Set to ON for termination ON Word Writing Value Settings DM6550 0001 Host Link mo...

Page 62: ...it restarting the communication port or executing the STUP instruction The following table shows the words allocated in the DM Area and the set tings Allocated DM word Value Settings Port 2 DM32010 8000 Host Link mode 2 stop bits data length 7 bits even parity DM32011 0000 Baud rate 9 600 bps 0007 Baud rate 19 200 bps 0008 Baud rate 38 400 bps 0009 Baud rate 57 600 bps 000A Baud rate 115 200 bps D...

Page 63: ... series of OMRON PLCs have the host link function built in Check the model and series of the PLC against the type of host link unit before marking the connections The compatible PLCs are listed in the table below Using the 1 1 NT Link Compatible Host Units Some models and series of OMRON PLCs have the 1 1 NT Link function built in With CQM1H PLCs a Serial Communications Board can be added to pro v...

Page 64: ...tion Board 1 Connectable to C Series C200HS CPU21 E EC C200HS CPU23 E C200HS CPU31 E C200HS CPU33 E C200HS C200HE CPU42 Z E C200HE CPU32 Z E C200HE CPU42 Z E C200HE Z E C200HG CPU43 Z E C200HG CPU63 Z E C200HG CPU33 Z E C200HG CPU43 Z E C200HG CPU53 Z E C200HG CPU63 Z E C200HG Z E C200HX CPU44 Z E C200HX CPU64 Z E X200HX CPU65 ZE C200HX CPU85 ZE C200HX CPU34 Z E C200HX CPU44 Z E C200HX CPU54 Z E C...

Page 65: ...The CPM2C s communication port handles both RS 232C and peripheral port connections which are divided internally Therefore when using the CPM2C it is necessary to select RS 232C or peripheral port con nections according to the kind of cable and port on the cable used as shown in the following table Refer to the CPM2C Operation Manual for more details Host Model Word Writing Value Setting RS 232C p...

Page 66: ...When using a CPM2C the switches on the front panel must be set as shown below in order to make the PLC Setup settings effective C200HX HG HE Z E CQM1 CQM1H RS 232C port communication condition setting Set pin 5 to OFF to make the settings made in PLC Setup effective Set the Communications switch to OFF down position The settings for SW1 and SW2 depend upon the usage of the peripheral port and RS 2...

Page 67: ...unit con nectors and connect the NT11 to the PLC To make a connector cable refer to Appendix D Making the Cable page 153 Caution After connecting a communication cable always secure it with the screws Otherwise the cable may disconnect causing operation to fail Caution The cable s tensile load is 30 N Do not subject it to loads greater than this Otherwise a discontinuity may occur causing operatio...

Page 68: ... equipped with an RS 422A 1 1 NT Link function compatible with the NT11 1 One of the following Serial Communications Boards is required C200HW COM03 EV1 or C200HW COM06 EV1 2 A CQM1H SCB41 Serial Communications Board is required 3 CPU Units of CVM1 CV series PLCs without the suffix EV cannot be connected CPU unit C200HS CQM1 9 pin connector RS 232C connector cable 9 pin connector NT11 Host I F con...

Page 69: ...ramming Device e g CX Programmer in accordance with the host model 1 RS 422A port of the Serial Communications Board 2 RS 422A port of the Serial Communications Board For details on operations relating to the PLC Setup refer to the manual for the PLC you are using Setting the DIP Switches on a C200HX HG HE Z E Serial Communications Board Set the switches on a C200HX HG HE Z E Serial Communications...

Page 70: ...h a Centronics cable The length of the cable should not exceed 3 meters Caution If the connection cable is connected or disconnected while the power of the printer is on the NT11 may malfunction Make sure to turn off the power of the printer before connecting or disconnecting the connection cable Recommended printer EPSON ESC P Printer 25 pin If using other printer such printer should conform to E...

Page 71: ...58 Connecting a Printer Section 2 8 ...

Page 72: ...Memory 64 3 4 1 Initialization of the Screen Data 64 3 4 2 Initialization by Using the DIP Switch Forced Initialization 65 3 5 Transferring the System Program 66 3 6 Registering the Screen Data 69 3 7 Setting the Conditions of Communications with the PLC by Using the Memory Switches 71 3 7 1 Selecting the Host Communication Method 73 3 7 2 Selecting the Host Link Communication Speed 74 3 7 3 Selec...

Page 73: ...3 5 Transferring the System Program page 66 Transfer the Screen Data page 69 Connect a support tool to the NT11 and transfer the screen data from the sup port tool to the NT11 For the connection of a support tool refer to 2 3 Connecting to the NT Sup port Tool page 22 Memory Switch Setting page 71 Select the System Menu and set the conditions for communications with the PLC using the memory switch...

Page 74: ... cursor on the required item with the keys then press Enter to confirm the selection The operation modes with respect to the System Menu are related to each other as shown below For the operations with the System Menu refer to 3 3 3 Operations with the System Menu page 62 SYSTEM MENU Quit Transmit Mode Maintenance Mode Not installed Installed ENTER System Transfer Mode RUN mode No Yes No Yes Trans...

Page 75: ...to OFF enabled If the setting is ON disabled the System Menu will not be displayed by following the procedure given below Displaying the System Menu The system menu can be displayed by switching on the power while any two of the four function keys are held down System Menu Quit Transmit Mode Maintenance Mode 1 0 PT Setting Maintenance Mode I O Check Device Check I F Check Key Input Check LED Check...

Page 76: ...w Switching from the System Menu to the RUN mode The NT11 will exit the System Menu and switch to the RUN mode in the cases mentioned below Selecting Quit in the System Menu The screen System keys is not pressed for over 10 seconds Operation Function Any two function keys Cancel ENTER key Set execute Arrow keys Cursor motion System Menu Quit Transmit Mode Maintenance Mode 1 0 PT Setting I O Check ...

Page 77: ...r rupted will be displayed For the error messages displayed on the screen refer to 6 2 Responding to Displayed Error Messages page 138 Note Initializing the screen data memory will erase entire screen data registered in the NT11 Make sure that there are backup copies of the screen data on floppy disks before starting the initialization 3 4 1 Initialization of the Screen Data The screen data can be...

Page 78: ... Note Be sure to turn the power OFF before setting the NT11 DIP switch Set the DIP switch as follows to initialize the screen data memory Operation 1 Set DIP SW2 2 on the NT11 to ON and turn the power ON Quit Initialize Memory History Data Screen Data Select Screen Data with the key then press ENTER Initialize Screen Data Yes ENT No F3 F4 Are you sure Press ENTER Initializing The message shown to ...

Page 79: ...ctive ineffective Setting this to ON selects effective and OFF ineffective 3 5 Transferring the System Program The system program of NT11 can be changed by the system transfer tool The system transfer tool is automatically installed in the personal computer when the NT11 support tool is installed For details on how to start up the system transfer tool and the system transfer tool operation refer t...

Page 80: ...LC disconnect the PLC and connect the system transfer tool computer to the NT11 and then transmit the screen data Operation 1 Connect the NT11 to the personal computer running the system transfer tool then switch on the power to the NT11 2 Switch on the power to the personal computer and start up the system transfer tool 3 When the power to the NT11 is switched ON the screen shown below is display...

Page 81: ...is terminated by pressing any two of the function keys on the panel of the NT11 Transfer is terminated by pressing the ESC key of the personal computer running the system transfer tool In the event of any of the above there is a possibility that the NT11 will not operate or that unpredictable malfunctions will occur To prevent this switch DIP switch SW2 6 ON to erase the system program after the p...

Page 82: ...ion Manual V061 E1 1 Transmission Transmission in File Units The NT11 uses several screens which are switched on its display The screen data of one NT11 unit corresponds to the screens created by using the sup port tool Select a file which contains the screen data to be transmitted when selecting the screen data to be transmitted to the NT11 so that the required screen data can be transmitted to t...

Page 83: ...on which the support tool is being used and turn ON the NT11 2 Turn ON the computer and start up the support tool 3 Enter the Transmit Mode by operating the menu of the NT11 as men tioned below 4 Specify downloading screen data from the NTST or Transfer Utility With the NTST select connect Download Application 5 The NT11 will display the following screen when the screen data is being transmitted 6...

Page 84: ...en data is checked However if any of the above occurs during the screen data trans mission the screen may disappear and other unexpected problems may occur In the case of such problems set DIP SW2 2 to ON to initialize the memory For the memory initialization by using the DIP switch refer to 3 4 2 Initializa tion by Using the DIP Switch Forced Initialization page 65 3 7 Setting the Conditions of C...

Page 85: ...Link 3 7 1 Selecting the Host Communication Method page 73 Baud Rate 3 7 2 Selecting the Host Link Communication Speed page 74 Comm Port 3 7 4 Selecting the Channel for Communication with the PLC page 76 History Data 3 7 5 Selecting the History Data Property page 77 Memory SW1 Page Backlight OFF 10min Auto restart Yes Memory SW2 Page Com Type Host Link Baud Rate 9600BPS Com Port RS 232C key key Me...

Page 86: ...etting the selection made press any two function keys simultaneously Reference The communication method must be selected according to the method that the connecting PLC supports Quit Transmit Mode Maintenance Mode System Menu 1 0 PT Setting I O Check Initialize Memory Memory Switch Memory SW1 Page Auto restart Yes Backlight OFF 10min History Data Erase Baud Rate 9600BPS Com Port RS 232C Com Type H...

Page 87: ...ing the selection made press any two function keys simultaneously Note If the NT link has been selected the Baud Rate setting does not make any effect Quit Transmit Mode Maintenance Mode System Menu 1 0 PT Setting I O Check Initialize Memory Memory Switch Memory SW1 Page Auto restart Yes Backlight OFF 10min History Data Erase Baud Rate 9600BPS Com Port RS 232C Com Type Host Link Memory SW2 Page Se...

Page 88: ...ng the selection made press any two function keys simultaneously Yes If a communication error has occurred corresponding error mes sage is displayed and the operation stops No If a communication error has occurred corresponding error mes sage will not be displayed and the operation will be automatically reset Quit Transmit Mode Maintenance Mode System Menu 1 0 PT Setting I O Check Initialize Memor...

Page 89: ...the ENTER key To quit with out setting the selection made press any two function keys simultaneously Reference Select the system that is supported by the PLC to be connected Quit Transmit Mode Maintenance Mode System Menu 1 0 PT Setting I O Check Initialize Memory Memory Switch Memory SW1 Page Auto restart Yes Backlight OFF 10min History Data Erase Baud Rate 9600BPS Com Type Host Link Com Port RS ...

Page 90: ...r being completely discharged the system program will delete the history data even if Keep is set Erase The history data will be deleted when the power supply is turned OFF 3 8 Starting the Operation After completing the screen data transmission connect the NT11 to the PLC and start the operation Caution Carefully check the operation of all screen data and host programs before using them If incorr...

Page 91: ... Tool Operation Manual V061 E1 1 Reference The start up screen must be designated when the screen data is created by using the support tool If the start up screen has not been designated the screen with screen number 1 will be displayed If no screen data has been registered at screen number 1 the Screen not registered error message will be displayed For the screen number setting refer to 4 2 Scree...

Page 92: ...perate As long as no operations are performed the same screen will be displayed indefi nitely If 10 min is selected the backlight will be switched OFF if no operations are performed for ten minutes If 60 min is selected the backlight will be switched OFF if no operations are performed for one hour Reference In order to maximize the service life of the backlight select 10 min or 60 min if possible ...

Page 93: ...he LED check by performing the following operations starting from the system menu The RUN LED on the panel of the NT11 will blink To quit the LED check press any two of the function keys simultaneously Quit Transmit Mode Maintenance Mode System Menu 1 0 PT Setting I O Check Initialize Memory Memory Switch Quit I F Check Device Check I O Check Select Maintenance Mode with the key then press ENTER S...

Page 94: ...pleted when all the dots are displayed To abort the LCD check press any two function keys simultaneously Quit Transmit Mode Maintenance Mode System Menu 1 0 PT Setting I O Check Initialize Memory Memory Switch Device Check Key Input Check LCD Check LED Check Select Maintenance Mode with the key then press ENTER Select I O Check with the key then press ENTER Select LCD Check with the key then press...

Page 95: ... when the panel key is pressed it indicates that the key is operating normally To quit the key input check press any two of the function keys simulta neously Quit Transmit Mode Maintenance Mode System Menu 1 0 PT Setting I O Check Initialize Memory Memory Switch Quit I F Check Device Check I O Check Device Check Key Input Check LCD Check LED Check Select Maintenance Mode with the key then press EN...

Page 96: ...e check on communication with the support tool press any two function keys simultaneously SYSTEM MENU Quit Transmit Mode Maintenance Mode PT Setting I O Check Initialize Memory Memory Switch I O Check Quit I F Check Device Check I F Check Quit Tool I F Input Check Print Out Check TOOL I F INPUT CHECK Select Maintenance Mode with the key then press ENTER Select I O Check with the key then press ENT...

Page 97: ...g the communications check 3 10 2 PT Setting Check Display the settings of the NT11 on the screen by performing the following operations starting from the system menu The current settings of the NT11 are displayed To quit the PT setting display press any two function keys simultaneously Quit Transmit Mode Maintenance Mode System Menu 1 0 PT Setting I O Check Initialize Memory Memory Switch Control...

Page 98: ...Exchange in the Host Link NT Link 89 4 3 3 NT11 Status Control and Notification to PLC 90 4 4 Memory Tables 94 4 4 1 Character String Memory Table 94 4 4 2 Numeral Memory Table 95 4 5 Bar Graphs 96 4 5 1 Bar Graph Functions 96 4 6 Numeral Setting 97 4 6 1 The Numeral Setting Function 97 4 6 2 Using Numeric Keys 98 4 7 Menu Screen Function 99 4 8 Password Screen Display Function 100 4 9 Display His...

Page 99: ...s ignating the screen number from the PLC Special Screen Number Screen number 0 is reserved for the system as the no display screen Select this to display nothing on the NT11 screen 4 1 2 Characters and Figures Which can be Displayed The NT11 screen can display characters bar graphs and other various ele ments This section describes the types and attributes of the characters and figures which can ...

Page 100: ... alternates with the nor mal display 4 2 Screen Display This section describes the screen information required for the operation with the NT11 4 2 1 Classification of Screens The NT11 is provided with the following types of screens which are classified by the display method Normal screen System screen The screen type is determined by the screen number Normal screens screen numbers 1 to 250 These s...

Page 101: ...be set For numeral setting the write channel display position and display method must be set Password attribute This attribute ensures security by requesting the input of a password before the screen is displayed If an incorrect password is input the screen will not be displayed The password is set as a four digit numerical value Display history attribute The following three types of data are reco...

Page 102: ...han system use The range of each memory area differs according to the PLC 4 3 2 Data Exchange in the Host Link NT Link There are two main methods for data exchange when using the host link NT link as follows Using the PT status control area PT status notify area Allocating numeral memory table entries character string memory table entries Symbol C series PLCs Allocation CV series PLCs Allocation C...

Page 103: ...and notification which are the basics of the NT11 functions For the detail method of use of the PT status control area and the PT status notify area refer to 5 5 NT11 Status Control page 129 and 5 6 Notification of the Operating Status to the PLC Determining the NT11 Operating Status page 132 Controlling the Display Elements by Using Allocated Bits and Words The NT11 will operate as follows in the...

Page 104: ...owing table to control the back lighting For the bit configuration refer to 5 5 1 Controllable NT11 Func tions page 129 The PT status control area PLC to PT can be allocated to the following PLC areas Words Allocated for the PT Status Control Area Words can be allocated for the PT status control area host PT in the fol lowing host PLC areas Word 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit Screen swi...

Page 105: ...a in the PLC and the PLC will read the data from this area to check the NT11 status The PT status notify area is configured as three consecutive words as shown below The first word word m of the PT status notify area must be set with the sup port tool Currently displayed screen refer to page 112 The screen number displayed on the NT11 is written to this word Simultaneously the PT status screen swi...

Page 106: ...ated to the following PLC areas Words Allocated of the PT Status Notify Area Words can be allocated for the PT status notify area PT host in the follow ing host PLC areas 1 LR 00000 to LR 00199 are converted to CIO 01000 to CIO 01199 Screen switching strobe Password input error flag 15 14 13 12 11 10 9 8 Bit PT status notify bits 0 0 0 0 Word m 2 PT operation status 1 ON RUN 0 OFF STOP Numeral set...

Page 107: ...haracter string memory table entries at up to 8 positions can be regis tered in one screen Displaying a Character string The character string memory table entries are registered with table entry numbers 0 to 127 When creating the screen data by using the support tool set the position on the screen to display a character string and also set a character string num ber to be displayed When the NT11 i...

Page 108: ...played When the NT11 is operated the screen displays the contents of the numeral memory table entry Also by relating the numeral memory table entries with the bar graphs the bar graphs corresponding to the data of the numeral memory table entries can be displayed Numerals Which can be Displayed The power of expression of the screen can be increased by giving various attributes such as the enlarged...

Page 109: ... creating the screen data Position and size The display position and size length of a bar graph can be set The width of the bar graph can be set in the range of 8 dots Orientation and incremental direction The type of bar graph displayed by the NT11 has a horizontal orientation and increments to the right Graph frame Select whether or not the graph frame boundary line of a graph display ar ea whic...

Page 110: ...e input from the screen by using the numeric keys A max imum of 8 numeral settings can be registered for one screen Basic Procedure The procedure for numeral setting is as follows 1 2 3 1 Input the numerical value using numeric keys 2 The input numerical value is displayed in the numeral setting area on the screen 3 Confirm the input numerical value by pressing the ENTER key it will be written to ...

Page 111: ...numeral setting area during operation first select the numeral setting at which the data is to be input and then input the numer ical value by pressing the numeric keys Selecting the Numeral Setting Area for Data Input If there is more than one numeral setting area on the screen select the one where numerical data is to be input using the arrow keys The numeral setting area currently selected for ...

Page 112: ...meric keys is pressed during operation the screen whose number was assigned to the key will be displayed At the same time the screen number of the destination screen is notified to the PLC Up to four destination screens can be registered per screen using the menu screen function The screen numbers of the destination screens are assigned to numeric keys 1 to 4 For details on menu screen setting ref...

Page 113: ...screen is not displayed Password screen setting The password and switching destination screen setting for the password screen are set using the support tool Setting items Number used as the password Display start position Switching destination screen Procedure for displaying the password screen Explained here is the procedure for displaying the password screen by speci fication from the PLC The pa...

Page 114: ...ction that records the display times screen numbers and screen comments of screens for which the dis play history attribute has been set using the support tool in the order in which they were displayed The recorded data can be printed out by using the display history printing function Recording a display history The procedure for recording a display history is presented below Operation 1 Set the s...

Page 115: ...istories in response to instruc tions from the PLC This section describes the procedure for printing daily reports and display his tories Reference Printers of the following type can be connected to the NT11 Models compatible with EPSON standard code ESC P The history data can be backed up by a capacitor for 16 hours at 25 C To enable backing up the history data the setting must be changed from th...

Page 116: ...ing bit 4 of the PT status control area is set to 1 One report is printed each time bit 4 is set to 1 To print the report again the bit status must be returned to 0 and then set to 1 again Setting at the support tool Perform the following setting with the support tool PT status control area allocated word CIO IR 0120 PLC program Create the following PLC ladder program for CQM1H Program operation L...

Page 117: ...corporate a clock Time data is recorded by referring to the PLC clock data Printing procedure Explained here is the procedure for printing a display history in response to an instruction from the PLC The printing instruction from the PLC takes effect by setting the status of bit 5 display history printing of the PT status control area To designate printing bit 5 of the PT status control area is se...

Page 118: ...en bit 5 is set to 1 the display history is printed 2 When CIO IR 0111 comes ON the display history printing bit bit 5 of the PT status control area is set to 0 The status of bits other than bit 5 re mains unchanged ORW 35 123 0020 0110 ANDW 34 123 FFDF 1 PT status control word Set the display history printing bit only to 1 PT status control word 2 PT status control word Set the display history pr...

Page 119: ...106 Daily Report Display History Printing Function Section 4 10 ...

Page 120: ...ords and Display of Memory Table Entries 117 5 3 2 Changing Displayed Numerals or Character Strings Changing the Contents of Allocated Words Direct Specification 120 5 3 3 Copying Memory Table Entries 121 5 3 4 Upgrading Bar Graphs Changing the Contents of Allocated Words 125 5 4 Numeral Setting 126 5 4 1 Notification of Numbers to the PLC 126 5 5 NT11 Status Control 129 5 5 1 Controllable NT11 Fu...

Page 121: ...1 Set NT21 NT31 Set NT31 V2 NT31C Set NT31C V2 NT631 Set NT631 V2 NT631C Set NT631C V2 System Setting Memory Switch Setting Set the memory switches that determine the basic operation of the PT The numeral character string bit memory table entry settings should also be made at this stage Setting for PT Status Control Notify Area Correcting an Existing File File Designation Importing DOS Version Dat...

Page 122: ...cting a Screen Saving a File Save the created screen data to a file Transmitting the Screen Data Transmit the created screen data to the PT After setting the PT in the Transmit mode execute the screen data transmission operation with the Support Tool NT11 Support Tool Setting the Clock Data Area Set the address of the first word to allocate as the Clock Data Area in the host so that the clock data...

Page 123: ...enu Screen Function page 99 To switch the NT11 screen display by controlling from the PLC write a screen number at the screen switch setting in the PT status control area Screen switch setting in the PT status control area Available allocation words The PT status control area PLC to PT can be allocated to the following PLC areas NT11 PLC Designated screen PT status control area Screen number Copy ...

Page 124: ...rating the PT status control area PLC to PT the contents of the currently displayed screen word in the PT status notify area PT to PLC also change Screen switching timing The NT11 screen switches when the contents of the screen switch setting have changed To re specify the number of the currently specified screen first write the value 0000 to clear the screen before writing the appropriate screen ...

Page 125: ...program as follows Program operation 1 2 3 1 Screen No 2 is displayed on the NT11 when bit 00002 turns ON 2 Screen No 3 is displayed on the NT11 when bit 00003 turns ON 3 When the screen switch strobe flag turns ON the number of the currently displayed screen is read and written to the currently displayed screen word in the PT status notify area In this case the NT11 will not write the same screen...

Page 126: ...rea PT host in the follow ing host PLC areas NT11 PLC Currently displayed screen PT status notify area Screen number PT status Screen switch strobe flag Content upgrade memory table entry Currently displayed screen 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit 0 0 0 0 0 Word m 15 14 13 12 11 10 9 8 Bit Screen No 4 digit BCD PT status 0 0 PT status Screen number 0001 to 0250 m 2 m 2 Screen switch strob...

Page 127: ...ber of Currently Display Screen This example gives a PLC program that reads the screen number each time the screen is switched In this example the number of the previous screen is also stored Support tool settings Make the following settings with the support tool PT status notify area Word 0110 PLC ladder program Program operation 1 When the NT11 screen display switches and the screen switch strob...

Page 128: ...bered character string Initialization setting Set whether or not the PLC words are initialized with the character string memory table initial value registered to the screen data memory when the main power supply is turned ON or reset Number of registration words Set the number of words within 8 words required for registering the char acter string data One word can store two characters Setting the ...

Page 129: ...port tool make the following settings for each numbered numeral Initialization setting Set whether or not the PLC words are initialized with the numeral memory table initial value registered to the screen data memory when the main power supply is turned ON or reset Number of registration words Set the number of words within 2 words required for registering the numer al data One word can store up t...

Page 130: ...ing one memory table entry is as mentioned below Numeral memory table entry 1 word max 4 digits or 2 words max 8 dig its Character string memory table entry 1 to 10 words 2 to 20 characters Available allocation words The memory table entries can be allocated to the following PLC areas Symbol C series PLCs Allocation CV series PLCs Allocation CS CJ series PLCs Allocation None IR Area OK CIO Area OK...

Page 131: ...Area Not for Host Link A AR Area OK Auxiliary Area No AR Area OK L LR Area OK LR Area 1 Not for Host Link T TC Area Timer PVs 1 word entries only Timer Area Timer PVs 1 word entries only TC Area Timer PVs 1 word entries only TU TC Area Timer Completion Flags No C TC Area Counter PVs 1 word entries only Counter Area Counter PVs Not for Host Link TC Area Counter PVs 1 word entries only CU TC Area Co...

Page 132: ... to be smaller than the maxi mum number of digits of the registration words 4 digits for 1 word 8 digits for 2 words the contents of the allocated words are not displayed and symbols will be displayed at all digits If the most significant digit is F when decimal with signs has been set the numeral is handled as a negative number The maximum number of digits of the negative number becomes smaller t...

Page 133: ...ister the memory table entries for the numerals and character strings to be displayed when creating the screen data by using the support tool To display a character string use character display and specify the char acter string memory table entry by using the support tool To display numerals use numeral display and specify the numeral mem ory table entry by using the support tool 3 Create a PLC pr...

Page 134: ...5 3 3 Copying Memory Table Entries The following describes the procedure to change displayed numerals or char acter strings by copying the contents of the memory table entry Numerals and character strings can be changed also by changing the con tents of the allocated words Refer to Changing displayed numerals or char acter strings explained before To change the numerals or character strings displa...

Page 135: ... following PLC areas Words Allocated for the PT Status Control Area Words can be allocated for the PT status control area host PT in the fol lowing host PLC areas NT11 PLC Memory table copy source Copy destination for display PT status control area Screen switch setting PT status control setting Copy source number Copy destination number A A A Copy memory table setting 15 14 13 12 11 10 9 8 7 6 5 ...

Page 136: ...e copy destination memory table entry number and then write the copy source memory table entry number to the PT status control area PLC to PT The NT11 reads the area sometimes when the PLC is writing the settings If the copy source memory table entry number has been written first and is changed an unexpected memory table entry may possibly be changed Allocated words that the NT11 reads The NT11 re...

Page 137: ...ngs PLC ladder program Create a PLC ladder program as follows Program operation 1 When an error occurs bit 09000 turns ON the NT11 displays the mes sage Error 2 When the error is cleared bit 09000 turns OFF the NT11 display mes sage reverts to Normal No Contents Number of Character Digits 4 Normal 6 digits 10 Error 6 digits 11 Normal 6 digits Line 1 Character string memory table entry 4 Normal MOV...

Page 138: ...ph will not be displayed By writing a negative number whose most significant digit is F to the al located word of a graph set as Sign display No the graph display will become 0 and the display will show For the procedure to write numeral values to the allocated words of the numeral memory table entries refer to 5 3 1 Allocation Words and Dis play of Memory Table Entries page 117 Symbol C series PL...

Page 139: ...d When numerical data is input at the NT11 this is automatically notified to the PT status notify area PT PLC allocated in the PLC memory as follows Notification of upgrade PT status numeral setting strobe flag turned ON 1 Upgraded numeral table entry number Stored in the content upgrade memory table entry When the PLC reads the content upgrade memory table entry at the leading edge of the numeral...

Page 140: ...allocate the PT status notify area PT PLC to the PLC memory 2 Using the support tool create a numeral setting screen and allocate the numeral memory table entry to the PLC memory 3 Create a PLC program for reading the content upgrade memory table en try in the PT status notify area when the numeral setting strobe flag in the PT status notify area comes ON 1 4 Read the allocated word for the numera...

Page 141: ... numeral setting strobe flag bit 11211 comes ON 1 the con tents of CIO IR 0111 the word where the content upgrade memory table entry is located are transferred to DM 0105 The number of the numeral memory table entry that contains the upgraded data is stored in DM 0105 in this case it is 003 or 004 If the numeral memory table entry is allocated to a PLC word the value in put to it can be read easil...

Page 142: ...splay setting is ON In situations like this control the NT11 by using the PT status control bits Screen display bit 15 The screen display bit determines whether the backlight is lit or unlit whether the screen is displayed or not It is used to prolong the service life of the backlight and prevent the formation of an afterimage When bit 15 is set to OFF 0 the backlight is switched off Once the scre...

Page 143: ...o 1 the contents of the specified words are read from the PLC and output to the printer once in the specified for mat To output the data to the printer again bit 4 must be switched OFF set to 0 and then switched back ON to 1 Reference Settings such as the printing format and word settings are made by using the support tool For details on the support tool setting procedures relating to the daily re...

Page 144: ...f the PT status control bits The example below shows how the PT status control bits are used to execute daily report printing Setting at the support tool Perform the following setting with the support tool PT status control area allocated word CIO IR 0118 PLC program Create the following PLC ladder program Program operation 1 When CIO IR 00110 comes ON the daily report printing bit bit 4 of the PT...

Page 145: ...n the NT11 is in the RUN mode this bit is ON 1 In other modes and when the system menu is displayed it is OFF 0 When it is OFF 0 the allocated bits and words cannot be read or written to Screen switching strobe bit 12 When the screen displayed by the NT11 is switched by an instruction from the PLC or by the standalone function the screen switching strobe comes ON 1 On notification to the PLC it go...

Page 146: ...h as operating statuses to the PT status notification bits in the PT status notify area PT PLC allocated in the PLC memory as follows Notification of operating mode PT operation status Notification of screen switching Screen switching strobe Notification of numerical value updates Numeral setting strobe flag Notification of password input mistakes Password input error flag Restrictions on allocati...

Page 147: ...he example below shows how the PT status notification bits are used to check the NT11 status Setting at the support tool Perform the following setting with the support tool PT status notify area allocated word CIO IR 0110 PT error storage area allocated word DM0001 PLC program Create the following PLC ladder program Program operation 1 When PT operating status CIO IR 11215 goes OFF 0 1 NT11 stoppe...

Page 148: ...hooting 136 6 2 Responding to Displayed Error Messages 138 6 2 1 Errors Occurring at Start of Operation and Their Remedies 138 6 2 2 Errors Occurring during Operation and Their Remedies 139 6 2 3 Errors Occurring on Screen Data Initialization and Transmission 139 6 2 4 Errors in the System Installer Mode and Their Remedies 140 6 2 5 Communication Errors and Their Remedies 140 6 3 Inspection and Cl...

Page 149: ...ng to the host Memory switch settings do not match Check the communication setting in the Memory Switch menu of the Maintenance mode and match the communication protocol settings for the host and NT11 3 7 Setting the Conditions of Communications with the PLC by Using the Memory Switches page 71 NT11 and host are not correctly con nected Check that the type length and installation of the connector ...

Page 150: ... the screen data in a batch to the NT11 The total of the element coefficients for the displayed screen is greater than 1024 The following System Menu operations are not possible Establishing the Transmit mode Displaying the memory switch setting screens Screen data memory check Displaying the initializa tion menu Screen Memory Protect has been set to Disabled because the PT power supply was turned...

Page 151: ... is set in Screen Data Set Direct Connecting Information in Screen Data using by the NT Support Tool Then set the PT to the TRANSMIT MODE and download Screen Data again Allocated words have not been set for the PT Status Control Area and PT Status Notify Area Allocate words for the PT Status Control Area and PT Status Notify Area with the NT Support Tool and then transmit the direct connection inf...

Page 152: ...essage Cause Remedy Flash Memory Error Flash Memory I O Error If this happens frequently Flash Memory may be broken Press Reset Switch to restart There is a hardware fault or the flash memory memory for storing screen data has reached the end of its service life If the same message is displayed even after clearing the screen data or transmitting screen data several times contact your OMRON service...

Page 153: ...as reached its life Select Download System Program and download the system program 3 5 Transferring the System Program page 66 If this does not solve the problem contact your OMRON service center Unable to erase System Program Hardware fault or flash memory memory for storing the system program has reached its life If the same message is displayed on repeating selection of Download System Program ...

Page 154: ...d data corruption during communication Carry out grounding work in accordance with the conditions by referring to 2 2 3 Wiring the Ground Wire page 21 The PLC is transmitting incorrect data Check the operation at the host side Time out Error The connecting cables are not con nected correctly Send Receive Check the communication cable connection and per form a conductivity test If there is a fault ...

Page 155: ...ar In environments that are extremely hot and humid or very dusty environments shorten the inspection interval Items Required for the Inspection Prepare the following items before starting the inspection Screwdrivers Phillips flat head Tester or digital voltmeter Industrial alcohol 100 cotton cloth Hygrometer required in some cases Thermometer required in some cases Synchroscope required in some c...

Page 156: ... accordance with the laws and regulations of the relevant country and local authority Ambient environmental conditions Ambient temperature temper ature in the operation panel 0 to 50 C Thermometer Ambient humidity humidity in the operation panel 35 to 85 Hygrometer Presence absence of dust Dust must not be settled Visual inspection Mounting conditions Looseness of mounting brack ets etc To be no l...

Page 157: ...144 Inspection and Cleaning Section 6 3 ...

Page 158: ...on resistance 10 to 57 Hz with 0 075 mm amplitude and 57 to 150 Hz with 9 8 m s2 acceler ation for 30 min in each of X Y and Z directions Shock resistance 147 m s2 3 times in each of X Y and Z directions Ambient operating temperature 0 to 50 C Ambient operating humidity 35 to 85 with no condensation Operating environment No corrosive gasses Storage temperature 20 to 70 C with no icing Enclosure ra...

Page 159: ...ife expectancy 1 million operations minimum Item Specification Display characters Normal characters 8 16 dots Alphanumerics and symbols Marks 8 16 dots User defined 64 max Number of characters displayed Normal size 20 horizontally 4 lines vertically max Enlargement function Double width Display elements Character string displays 8 positions per screen Numeral displays 8 positions per screen Graph ...

Page 160: ...ntenance functions Self test for memory switches etc Status setting confirmation for communications and other conditions Simple communications confirmation Product Specification Model Programmable Ter minal Host link direct con nection NT link method Ten key type frame color beige NT11 SF121 EV1 Ten key type frame color black NT11 SF121B EV1 Support Software CD ROM for Windows 95 98 Me XP NT 2000 ...

Page 161: ...e system using the STROBE signal and the ACK signal STOROBE DATA 0 DATA 1 DATA 2 DATA 3 DATA 4 DATA 5 DATA 6 DATA 7 ACK BUSY PAPER EMPTY SELECT 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 AUTO FDXT ERROR INIT SLCTIN GROUND GROUND GROUND GROUND GROUND GROUND GROUND GROUND DATA STROBE BUSY ACK t1 t2 t3 t1 t2 and t3 are each 0 5 µs or longer ...

Page 162: ...149 Appendix B Dimensions Body NT11 SF121 B EV1 38 2 7 5 218 203 113 98 ...

Page 163: ...150 Dimensions Appendix B ...

Page 164: ...porting and Storing the NT11 When transporting the NT11 use the packaging intended for it When storing the NT11 observe the following conditions Storage ambient temperature 20 to 70 C Storage ambient humidity 0 to 70 C 85 ...

Page 165: ...152 Transporting and Storing the NT11 Appendix C ...

Page 166: ...amage the shield ing underneath 3 Cut back the shielding wire with scissors 4 Use wire strippers to strip the insulation from each wire 5 Fold back the shielding wire 6 Wrap aluminum foil tape around the folded back shielding wire Cable with Shield Not Connected to FG 1 Cut the cable to the required length 2 Remove the external vinyl insulation from the cable with a razor blade Take care not to da...

Page 167: ...erminal 4 Push the heat shrink tube over the soldered joint and heat the tube to shrink it in place Hood Assembly Assemble the connector hood as shown below 40 1 57 RS 232C 5 25 0 98 RS 422A 1 2 3 4 5 Units mm inch Vinyl tape 0 19 Soldering iron Heat shrink tube F 1 5 mm dia l 10 mm 1 mm Heat shrink tube Aluminum foil tape End connected to FG End not connected to FG ...

Page 168: ...3 4 5 7 1 SD RD RS CS SG 5 V 2 3 4 5 9 6 Connector hood Name Model Remarks Connector XM2D 2501 25 pin made by OMRON for personal computer side XM2A 0901 9 pin made by OMRON for PT side Connector hood XM2S 2511 25 pin made by OMRON for personal computer side XM2S 0911 9 pin made by OMRON for PT side Connector set XM2S 0911 S003 9 pin made by OMRON for PT side Connector and Connector hood Cable AWG2...

Page 169: ...therwise the product may malfunction The 5 V output of the unit delivers 5 V 5 and 150 mA maximum Name Model Remarks Connector XM2D 0901 9 pin made by OMRON for personal computer XM2A 0901 9 pin made by OMRON for PT Connector hood See note XM2S 0911 9 pin mm pitch screw made by OMRON XM2S 0913 9 pin inch pitch screw made by OMRON Connector set XM2S 0911 S003 9 pin made by OMRON for PT side Connect...

Page 170: ...11 unless these memory table entries are used for screen displays 2 The maximum number of bits words that can be read is 120 words per screen If the number that can be read is exceeded the data are not upgraded The contents of the allocated bits and words registered in the PLC are all read at one time NT11 processing Details of processing NT11 power ON Initial processing Hardware check communicati...

Page 171: ...al character string memory table entries that are not being displayed change the changed contents are not written to the PLC NT11 processing Details of processing PT PLC PT PLC Writing to character string memory table High Low Writing to the PT status notify area Changing the contents of words allocated to the PLC when the value in a numeral memory table has changed Changing the contents of words ...

Page 172: ... Name SRM1 C02 V2 Features an RS 232C port SRM1 Model Specification Applicable PLC CS1W SCU21 RS 232C 2 ports Rack mounting Unit CS series CS1G H CS1G H H CJ1W SCU41 Features an RS 422A 485 port port 1 and an RS 232C port port 2 CJ series CJ1G Model Specification PLC Type CPM1 10CDR CPM1 20CDR CPM1 30CDR CPM1A 10CD CPM1A 20CD CPM1A 30CD CPM1A 40CD RS 232C adapter RS 422A adapter connected to the p...

Page 173: ... able 9 pin C series C200HG Z E C200HX CPU34 Z E C200HX CPU44 Z E C200HX CPU54 Z E C200HX CPU64 Z E C200HX CPU65 ZE C200HX CPU85 ZE Features a connector for RS 232C connections select able 9 pin C series C200HX Z E CS1G CPU42 E V1 CS1G CPU43 E V1 CS1G CPU44 E V1 CS1G CPU45 E V1 Features a connector for RS 232C connections 9 pin CS series CS1G CS1H CPU63 E V1 CS1H CPU64 E V1 CS1H CPU65 E V1 CS1H CP...

Page 174: ...U21 E C200HS CPU23 E C200HS CPU31 E C200HS CPU33 E Features a connector for RS 232C connections select able 9 pin C series C200HS C200HE CPU32 Z E C200HE CPU42 Z E Features a connector for RS 232C connections select able 9 pin C series C200HE Z E C200HG CPU33 Z E C200HG CPU43 Z E C200HG CPU53 Z E C200HG CPU63 Z E Features a connector for RS 232C connections select able 9 pin C series C200HG Z E C2...

Page 175: ...M2A CPM2C SRM1 compatible with host link and NT Link 1 1 CPM1 CIF11 Links the RS 422A port of a Link Adapter and the peripheral port of a CPM1 CPM2A CPM2C SRM1 compatible with host link Name Model Remark NT Support Tool NT ZJCAT1 EV4 Ver 4 7 or later Compatible with PC AT or compatible personal computers For Windows 95 98 NT Me 2000 or XP English version CD ROM Options NT11 CKF01 10 key sheets for...

Page 176: ...44 D 54 T 64 d 74 t 84 ä 94 ö 36 52 68 84 100 116 132 148 5 25 35 5 45 E 55 U 65 e 75 u 85 à 95 ò 37 53 69 85 101 117 133 149 6 26 36 6 46 F 56 V 66 f 76 v 86 å 96 û 38 54 70 86 102 118 134 150 7 27 37 7 47 G 57 W 67 g 77 w 87 ç 97 ù 39 55 71 87 103 119 135 151 8 28 38 8 48 H 58 X 68 h 78 x 88 ê 98 ÿ 40 56 72 88 104 120 136 152 9 29 39 9 49 I 59 Y 69 i 79 y 89 ë 99 Ö 41 57 73 89 105 121 137 153 A ...

Page 177: ... Ñ B5 C5 D5 E5 s F5 õ 165 181 197 213 229 245 6 A6 a B6 C6 D6 E6 m F6 166 182 198 214 230 246 7 A7 o B7 C7 D7 E7 t F7 167 183 199 215 231 247 8 A8 B8 C8 D8 E8 F F8 168 184 200 216 232 248 9 A9 B9 C9 D9 E9 Q F9 169 185 201 217 233 249 A AA BA CA DA EA W FA 170 186 202 218 234 250 B AB 1 2 BB CB DB EB d FB Ö 171 187 203 219 235 251 C AC 1 4 BC CC DC EC FC n 172 188 204 220 236 252 D AD BD CD DD ED f...

Page 178: ...ings 29 CPU Units connections 30 45 models host link 159 NT link 161 crimp terminals 40 D daily report printing 102 dimensions body 149 DIP switches initializing 65 NT link 53 precautions 18 Programmable Controllers 34 Serial Communications Boards 56 settings 18 startup 60 direct connection function 9 display 6 display history printing 102 104 display history screen function 101 display screen not...

Page 179: ...hods 19 precautions 2 19 K key input check 82 L LCD check 81 LED check 80 M maintenance 80 147 maintenance mode key operations 63 marks 6 memory switches 60 71 auto restart 75 history data 77 memory tables 115 allocations 117 character string 94 115 changing 120 copying 121 example 124 displaying 117 numeral 95 116 bar graphs 96 changing 120 menu screen function 99 messages 3 models accessories 16...

Page 180: ... 151 printer connections 57 printer port connector pin arrangement 148 signal timing 148 printing 147 daily report 102 display history 104 production line status 2 Programmable Controllers 23 connections NT link 55 switch settings 27 42 Programmable Terminals 147 models 159 Programming Tools manuals 13 PT settings 84 PT status control area 11 89 91 allocations 111 130 PT status control bits 129 ap...

Page 181: ...figurations 147 special features 147 startup 60 procedure 12 status control 129 storing 151 Support Software 147 switch settings Programmable Controllers 27 42 See also DIP switches system configuration 8 System Installer 8 errors 140 manual 13 system keys 7 precautions 7 System Menu 60 61 displaying 62 functions 62 initializing 64 system program erasing 68 transfer ROM 4 transferring 60 66 67 sys...

Page 182: ...atalog number on the front cover of the manual The following table outlines the changes made to the manual during each revision Page numbers refer to the previous version Revision code Date Revised content 01 January 2004 Original production Cat No V084 E1 01 Revision code ...

Page 183: ...170 Revision History ...

Page 184: ...eadquarters OMRON EUROPE B V Wegalaan 67 69 NL 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 OMRON ELECTRONICS LLC 1 East Commerce Drive Schaumburg IL 60173 U S A Tel 1 847 843 7900 Fax 1 847 843 8568 OMRON ASIA PACIFIC PTE LTD 83 Clemenceau Avenue 11 01 UE Square Singapore 239920 Tel 65 6835 3011 Fax 65 6835 2711 ...

Page 185: ...Authorized Distributor Cat No V084 E1 01 Note Specifications subject to change without notice Printed in Japan This manual is printed on 100 recycled paper ...

Page 186: ...NT11 Programmable Terminal Cat No V084 E1 01 USER S MANUAL ...

Reviews: