•  This manual provides important safety-related information. Thoroughly read and understand 

this manual before installing and using the product. 

•  Keep this manual in a convenient location so that you can refer to it whenever necessary.

Uninterruptible Power Supply (UPS)

Instruction Manual

BU50SW/BU75SW/BU100SW/BU150SW

-

バッテリ

 交換

バッテリ

 増設

ブザー停止/テスト

電源出力

バイパス

運転

BU150SW

Summary of Contents for Powli BU100SW

Page 1: ...horoughly read and understand this manual before installing and using the product Keep this manual in a convenient location so that you can refer to it whenever necessary Uninterruptible Power Supply...

Page 2: ...omenon in which extraordinary high voltage occurs instantaneously Under normal conditions it converts the commercial power to a direct current once recon verts it to a stable AC sine wave and outputs...

Page 3: ...s symbol indicates earth ground This symbol indicates turning on UPS This symbol indicates turning off UPS 3 INTERNAL BATTERY Internal battery voltage is 24V DC for BU50SW BU75SW BU100SW 36V DC for BU...

Page 4: ...orm installation and connection Page 5 Check the operation and displays Pages 13 Charge the battery Page 15 Measure the backup time Page 15 Read Using the UPS monitoring software and contact signal Pa...

Page 5: ...function 24 4 4 Changing the setting of the functions 24 5 Measuring the backup time 29 5 1 How to measure backup time 29 5 2 Estimated backup time 29 6 Maintenance and Inspection 31 6 1 Checking the...

Page 6: ...the same level of importance Warning Important information for safe operation is described Be sure to read it before installation and start of use Misuse may cause injury or property damage Carry the...

Page 7: ...cause a failure or malfunction of the unit Do not exceed the ranges specified for environmental conditions during use storage Do not install or store the unit in the places listed below Do not store i...

Page 8: ...the unit Doing so will cause the internal temperature to rise which may cause the unit to fail and the battery to deteriorate Leave at least 5 cm of space between the vent and the wall Do not connect...

Page 9: ...disconnect the AC input plug from a wall outlet commercial power Using the unit under such conditions may cause a fire If you notice such a condition stop using the unit and contact us at _____ for i...

Page 10: ...tery replacement Perform replacement on a stable and flat place Handle the battery carefully so that you do not drop it Not doing so could cause injury or burns due to liquid acid leakage Use a specif...

Page 11: ...it current The following precautions should be observed when working on batteries 1 Remove watches rings or other metal objects from the hands 2 Use tools with insulated handles 3 Wear rubber gloves a...

Page 12: ...do not short the output lines to the ground The unit may fail Do not connect the AC input plug of the unit to its Power Supply Output Receptacle during the Battery Mode The unit may fail Do not conne...

Page 13: ...ry can be charged once the AC input plug of the unit is connected to a wall outlet commercial power Quitting Battery Mode If a power failure lasts for an extended period of time the battery discharges...

Page 14: ...U100SW BU150SW Quick Install Guide 1 1 1 1 CD ROM 1 1 1 1 Connection cable RS 232C 1 1 1 1 Open the package box and take out the UPS and accessories The weight of the product is 13 kg BU50SW BU75SW 15...

Page 15: ...ed view of the display panel Side view Air inlet Rear side Front side BU150SW Display panel A Status indicator digital display B Power switch C Beep stop test switch D Battery addition lamp BU100SW an...

Page 16: ...S232C OUTPUT AC100 120V 50 60Hz 1 500VA 350W INPUT AC100V 120V 50 60Hz 8A AC 10A A D E F G B H I C BU50SW BU75SW BU100SW BU150SW A RS232C connector B Contact signal card C Additional battery connector...

Page 17: ...beep UPS output power enabled supplied by operating on line mode battery mode Bypass output ON Additional battery unit connected to the UPS For BU100SW BU150SW only Batteries at end of useful life nec...

Page 18: ...50SW Otherwise the power cord may be heated When equipment with the maximum output capacity is connected a maximum current of 8A BU50SW 10A BU75SW 12A BU100SW or 16A BU150SW flows Provide secure groun...

Page 19: ..._ All of the included accessories are designed to be used exclusively with the unit Do not use the accessories with other devices Doing so may compromise the safety of devices This UPS utilizes voltag...

Page 20: ...ault For PLUGGABLE EQUIPMENT the socket outlet shall be installer near the equipment and shall be easily accessible Notes When moving the unit from a cold place to a warm place leave it for several ho...

Page 21: ...upply to another power supply source such as generating equipment will cause no problem Do not install or store the unit in a place exposed to direct sunlight The rise of temperature may cause the bui...

Page 22: ...of the serial number of this device The serial number is required when contacting us about the device The serial number is written in the label on the unit Incorrect Positions BU150SW BU150SW Correct...

Page 23: ...m or other peripheral Wall outlet commercial power Plug of connected device Connect it directly Connect the plug directly Example of connection 1 Example of connection 2 RS232C OUTPUT AC100 120V 50 60...

Page 24: ...050W Using a 15A plug It is possible to use a wall outlet commercial power with a basic 15A NEMA 5 15 plug It is possible to connect to a 2 pin outlet using the included 3P 2P adapter In this case mak...

Page 25: ...ing the operation on page 13 also before charging the battery RS232C M J h p t OUTPUT AC100 120V 50 60Hz 1 o d 500VA 350W n INPUT AC100V 120V 50 60Hz 8A AC d 10A 2P receptacle 3P receptacle Connect to...

Page 26: ...mmercial power 2 Bring all the connected devices into operation Including devices connected to the AC outlet of your PC Operate the devices in a way in which abrupt power stop does not damage the conn...

Page 27: ...when an additional battery unit is connected go back to 4 on page 13 If the problem persists after checking the 2 points above con tact us ____ Setting switch 1 can be used to turn the beeper ON OFF...

Page 28: ...described below in 2 6 Measuring the initial value of backup time proceed to 3 Operation Page 16 When you measure the backup time initial value of the unit in your environment this value can be used...

Page 29: ...y cause a fire If you notice such a condition stop using the unit and contact us at _____ for inspection and re pairs Use the unit under the conditions in which you can immediately disconnect the AC i...

Page 30: ...propriate procedures for example saving data while the unit is still supplying power Rebooting If the battery discharges completely during a power failure the unit stops After recovery from the power...

Page 31: ...10 seconds If the battery voltage is low the self diagnostic test is not performed It is auto matically executed after the battery is charged 1 When the self diagnostic test finishes successfully swi...

Page 32: ...op soon Same as above Battery is dead so output stopped This is displayed only for a few seconds Charge the battery indicates blinking Operation during recovery from a power failure If a power failure...

Page 33: ...ON 90 or more 60 or more 60 ON 60 or more 30 to 60 30 ON 30 or more 0 to 30 All OFF 30 or less Connection capacity during normal operation Battery capacity dur ing Battery Mode 1 Displays and beeps in...

Page 34: ...ll devices connected to the unit reduce the number of connected devices and turn the power switch back ON again Check that the AC input of connected devices is not short circuited Moved to bypass oper...

Page 35: ...according to the stat us No Status indicator Power supply output lamp Beep Charging Description Solution Bypass operation lamp Battery replacement lamp Displays the details of the error that occurred...

Page 36: ...and other devices to the UPS and then turn ON the power switch of the UPS 2 The Battery Mode starts for testing purpose automatically Status indicator No beep sounds After about 10 seconds when the te...

Page 37: ...F or if the battery is not fully charged 1 When the auto battery test starts the Battery Mode automatically starts Status indicator No beep sounds After the auto battery test is complete the normal op...

Page 38: ...st is disabled Use this setting to disable Battery Mode for for the regularly performed auto battery test 1 2 5 3 4 8 6 7 ON DIP Auto restart setting setting switch 2 Factory setting OFF OFF Automatic...

Page 39: ...ting OFF BU150SW only OFF Set to OFF when using a 15A AC input plug The UPS can connect to as much as the rated out put capacity 1100VA 950W for a 15A plug ON Set to ON when using a 20A AC input plug...

Page 40: ...be set Output is performed at the set voltage with no relation to the input voltage How to make settings There are 2 items to select 1 Cold start ON OFF setting 2 Output voltage setting 1 When the bee...

Page 41: ...l sta tus T h e reis A Cinp ut w h e n a th esta tus ind ica tor is O N Pow e r sw itch O F F Sta tus N o 2 A B D C C C C D D D D D D D O N O F F 1 0 0 V 1 1 0 V 1 1 5 V 1 2 0 V C oldsta rt O N O F Fs...

Page 42: ...p time varies depending on the capacity of connected devices After calculating the total capacity of connected devices refer to the graph of the backup time to obtain an estimation of the initial valu...

Page 43: ...740 440 260 140 90 65 51 35 21 20 1050W BU100SW BUM100S Minutes Backup time 120 110 100 90 80 70 60 50 40 30 20 10 0 Power consumption of connected devices W 0 100 200 300 400 500 600 700 800 900 1000...

Page 44: ...page 29 replace the battery When you compare the initial value of the backup time you measured and the current backup time make the capacity of devices connected to the UPS same as when you measured t...

Page 45: ...1 5 years after purchase Check once a month When 3 or more years have passed since purchase When 1 5 or more years have passed since purchase Caution for battery replacement Perform replacement on a s...

Page 46: ...Remove watches rings or other metal objects from the hands 2 Use tools with insulated handles 3 Wear rubber gloves and boots 4 Do not lay tools or metal parts on top of batteries 5 Disconnect chargin...

Page 47: ...his to remove Remove the 2 screws 4 Hold the pullout label at the bottom of the battery pack and remove the battery pack Do not hold the connector or cable of the battery pack Use the red tape on the...

Page 48: ...rt the lug at the bottom of the cover into the hole in the main body and push it towards the main body Use a screwdriver to securely tighten clockwise the 2 screws you removed Do not pinch the cable w...

Page 49: ...attery when operation was stopped Connect the AC input plug to a wall outlet commercial power and turn ON the power switch of the UPS When operation starts the self diagnostic test is automatically pe...

Page 50: ...ng Battery Mode Do not replace the fan while in Battery Mode The unit will stop Do not insert your hand or metal objects into the fan recess Doing so may cause electric shock or short circuit Do not p...

Page 51: ...For information on the connection procedure See also 2 3 Connecting the equipment Page 10 2 While pressing down on the tip of the fan connector pull it toward you to disconnect it The beep stops and...

Page 52: ...el OS Communication method UPS monitoring software Required options sold separately Reference BU50SW BU75SW BU100SW BU150SW Windows Vista Serial RS232C PowerAct Pro Note 1 See 7 1 Windows server2003 x...

Page 53: ...ring software allows you to automatically save files and perform shutdown processing of your PC when a power failure occurs Also you can perform desired operation by setting the automatic start stop o...

Page 54: ...start after OS closing processing using the UPS monitoring software When a power failure occurs certain PCs 1 automatically restart immediately after the OS is shut down by auto shutdown In this case...

Page 55: ...ontact signal connector on UPS 2 Perform UPS service setup You need to make Windows settings in order to perform auto shutdown There is no need to install soft ware When using the Windows Server 2003...

Page 56: ...d to In the example screen below the UPS is connected to COM1 Click the Next N button How to set up UPS service shut down Windows when low battery level is detected 1 Double click the Power supply opt...

Page 57: ...is detected Windows shutdown does not start and the normal monitoring state is restored Recycling and Discarding the Battery In the Windows Vista Windows Server 2003 XP 2000 UPS service there is no f...

Page 58: ...e to wait before starting Windows shutdown after a power failure occurs Setting range 2 to 720 minutes Click the OK button 3 Click the OK button in the Power supply options window Setup is complete Cl...

Page 59: ...al L and Remote uninterruptible power source shutdown signal R to insert check marks Set each signal interface voltage setting as shown below Power failure signal P Negative Low battery signal L Negat...

Page 60: ...tery Replacement Signal output WB Goes ON when the battery needs to be replaced due to deterioration BL COM ON when the battery is low TR COM ON when a power failure occurs WB COM ON when battery dete...

Page 61: ...n be used to start and stop the UPS by using either an externally connected con tact or the ON OFF status of the open collector circuit To use this function turn on the Power Switch of the UPS Connect...

Page 62: ...ailure signal is output can be delayed be tween 0 and 3 minutes The power failure signal is not output if the power supply error is resolved within the set delay time BU BL signal reverse output setti...

Page 63: ...signal output BU 4 NC COMMON COM 5 COMMON COM Battery Low Signal output BL 6 Remote ON OFF input Backup stop signal input BS 7 Remote ON OFF input Remote ON OFF input 8 Backup signal output BU Trouble...

Page 64: ...minals 5 VDC Current when closed max 10 mA Example of BU signal output circuit and the connected circuit Example of BS signal input circuit and the connected circuit COM UPS side BU 12V1K TLP627 To po...

Page 65: ...ct signal card settings Cable Connection cable BUC28 sold separately 1 UPS connection procedure 1 Turn OFF the unit s power switch and remove the contact signal card from the rear of the unit See also...

Page 66: ...the SNMP Web card in its place Store the removed contact sig nal card in a safe place SNMP Web card model number SC20G sold separately 1 Remove the 2 screws and carefully pull out the contact signal...

Page 67: ...ate with each other to perform shutdown Log function The UPS power status battery status etc can be stored in the built in flash memory Compatible with SYSLOG Auto shutdown function Shutdown is automa...

Page 68: ...y unit Use the removed screws to attach the cable clamps 2 Connect the battery connection cable to the battery connectors on the rear side of the unit and the bat tery unit To simplify the operation d...

Page 69: ...vices connected to the UPS Connect them to a wall outlet commercial power for 3 pin plugs or connect their Grounding Terminal to the Grounding Terminal of a wall outlet This problem may occur when pow...

Page 70: ...failure switching time Uninterrupted Commercial direct shipment switching time 4 msec max Backup time 3 Minimum 8 minutes Minimum 5 minutes Minimum 5 minutes Minimum 4 minutes Battery Type Compact se...

Page 71: ...58 Reference B Dimensions Power cable approx 1 8 m BU150SW Power cable approx 1 8 m BU50SW BU75SW BU100SW unit mm Tolerance 1mm unit mm Tolerance 1mm...

Page 72: ...Power supply output 100V AC D Related products Description Model Replacement battery pack for BU50SW BU75SW BP70XS Replacement battery pack for BU100SW BP100XS Replacement battery pack for BU150SW BP1...

Page 73: ...displayed 5 Shutdown when OS is inactive Shutdown can be performed when the computer is in an inactive state The operating status is retained at shutdown in inactive state so operation details are no...

Page 74: ...No part or whole of this manual may be reproduced without permission The contents of this manual are subject to change without notice OMRON Corporation K1L D 05095G...