33.
Specifications
Features
DS10KB-RM
Front Panel
DS10KB-RM
Rear Panel
* DS10KB-RM
* Online double conversion design
* Pure sine wave output with less than 3% THD
* Fully digitized microprocessor control
* Power factor correction
* Selectable UPS output voltage
* High efficiency mode
* Cold start function (DC power on)
* Emergency power off function (EPO)
DS10KB-RM
* Short circuit and overload protection
* Fax/Modem/LAN data line surge protection
* Advanced battery management (ABM)
* Automatic battery charging in UPS OFF mode
* Automatic diagnostics and battery check-up
* Extended battery pack available
* Multilanguage LCD display
* RS232 and USB Communication ports,
UPS monitoring software
Line Interactive
UPS Series
On Line UPS
Series
A
VR Series
Inverter Series
Surge Series
Standby UPS
Series
Networking
Series
Green Power
Series
windows
2000 / XP
2003 / Vista
Sine Wave
DS10KB-RM
Topology
On-battery Output Waveform
Number of Phase
INPUT
Maximum Capacity
Nominal Input Voltage
Input Voltage Regulation
Nominal Input Frequency
Input PFC
Input Short Protection
OUTPUT
Nominal Output Voltage
Output Voltage Regulation
Output T.H.D
High Efficiency Mode (AC to AC)
Crest Factor
Start on Battery
Auto Restart
PROTECTION
Data Line Surge Protection
BATTERY
User Replaceable Batteries
Typical Backup Time (Full / Half load)
Recharge Time to 90%
Connected Battery Pack
ADVANCED WARNINGS / DIAGNOSTICS
Front Panel LEDs
Audible Alarms
COMMUNICATION INTERFACE
Communication Port
SNMP Manageable
ENVIRONMENTAL
Operation Temperature
Storage Temperature
Relative Humidity
Audible Noise
PHYSICAL
Dimensions (Physical / Packing) (in)
(LxWxH) (mm)
Weight (Net / Gross) (lbs)
(kg)
Battery Pack (Net / Gross) (kg)
Battery Pack Dimensions (in)
(mm)
CONFORMANCE
EMI / RFI Compatibility
Safety Certifications
Model Name
True On-Line, Double Conversion
Pure Sine Wave
Single Phase (2W+G)
10000VA/7000W
208/220/230/240Vac
176-276Vac
50Hz / 60Hz Auto Sensing
>
0.97@Full load
Circuit Breaker
208/220/230/240Vac (selectable)
Rated V/-2%
<
3% T.H.D at Linear Load
>
92%
3 : 1
Yes
Yes
RJ11 / RJ45
240V / 12V34W × 20 (in Battery pack)
12/24 min
<
4 Hours
BP10000-RM
AC mode / On line / On battery / Bypass / Fault / Overload and 15 UPS Parameters
Battery mode / UPS faults / Overload
RS232 and USB Port
Yes
0~40°C / 32~104°F
-20~60°C / -4~140°F
0~95% humidity, non-condensing
<40dBA (at 1 meter from surface of unit)
23.5×16.9×5.1 / 29.1×22×10.7
597×428×130 / 740×560×273
44.1 / 52.9
20 / 24
66 / 75.5
23.5×16.9×5.1 / 29.1×22×10.7
597×428×130 / 740×560×273
CE; GOST-R
C-Tick, A-Tick; GOST-R
RS232
EPO
Input
External
Battery
Connector
Communication
Port