Installing The Heating Mats
I
MPORTANT NOTE: THESE MATS ARE NOT TO BE INSTALLED IN WALLS OR CEILINGS FOR ANY
REASON AND MUST BE WIRED BY A QUALIFIED, LICENSED ELECTRICIAN.
NEVER:
Cross the blue heating cable over itself.
Cut the blue heating cable for any reason.
Run heating cable directly to the junction box.
Subject the blue heating cable to harmful surfaces.
ALWAYS:
Follow local and national electrical codes.
Test the mat for the proper readings before, during and
after the installation.
Make certain the splice is completely buried in the pour.
Fill out the warranty card and return it to Orbit.
Product Description:
IT IS VERY IMPORTANT
TO NEVER CUT THE HEATING CABLE
(Minimum distance between adjacent runs of
cable and minimum bending radius are 2 inches).
The Nexans Millimat is constructed of a blue twin conductor cable attached to a white
poly mesh mat. The cable is spaced at a fixed 3.15” On Center Spacing with tape and comes with 8 feet of cold
lead on one end . The Millimats are designed to provide 12 watts per square foot.
as this will damage the mat and void the warranty. Details of mat
dimensions, load, voltage, etc. are given on the UL Tag.
Quality & Comfort from the Ground Up
1507 B WEST PARK AVE. PERKASIE, PA 18944
PHONE: 215-453-9228
FAX: 215-257-7399
ORBIT MANUFACTURING COMPANY
Electrical Code and Safety:
(In addition, the installation shall be in accordance with the
regulations of all authorities having jurisdiction.) Caution:
All heating mat installations shall be installed according to the National Electric
Code (NEC) Article 424 for space heating.
This equipment shall only be installed by
qualified personnel, who are familiar with the construction, operation, and installation.
Plan the installation by identifying the area you would like to heat minus the permanent fixtures. The distance
between the mat and non-heated areas shall be no closer than 1 inch. Select the correct Millimat(s) with
respect to the heated area and the 1 inch margin as specified. The heating cable cannot cross or touch itself
and cannot be placed in or under a wall, therefore
the area of the Millimat(s) must be slightly smaller
than the heated area. When cutting and adjusting
the mesh,ensure that the cables are kept at the
same distance from each other as the cables on the
mat itself. The heating cable shall not touch or
overlap itself. The splice MUST be buried in the
masonry. This is the point at which the heating
cable is attached to thecold lead. Only the cold
lead can be out of the Masonry or concrete and run
into the conduit.
GENERAL INSTALLATION GUIDELINES
Millimat Splice
Nexans Electric Floor Heating Mat Installation Instructions
1/2 Conduit for Floor Sensor
Floor Sensor
Non combustible
Sub-Floor
Thin Set
Heating Mat
Tile, Stone, Marble, Laminates
*
Backer Board
*Slab
Millimat
application methods for
thin set installations
Leveling Agent
******DO NOT CUT THE HEATING CABLE******