Operating Instructions RFI 1000 / RFI 1000-2
Please read the operating instructions before starting the device
The device is able to memorize 99 RFI keys (either in form of a card or a tag) as opening keys and one
key as programming key at a maximum. If, in addition, a manual terminal is applied 999 RFI keys can
be memorized as opening keys and one as programming key. Any number between 0 and 999 may be
assigned to each key to store it thereunder. Such number may be selected by means of two turn
switches on the printed-circuit board or by a manual terminal, this is the
„RFI MASTER“
(0-999).
Turn switch „A“ sets the digits and turn switch „B“ the decimals.
Each key may as well be deleted individually. Moreover, all stored keys may be deleted completely.
Only one number can be assigned to each key.
Keys to which an odd number was assigned (1,3,5 etc.) activate relay 1 and keys an even number (2,4,6
etc.) was assigned to activate relay 2 (only on model RFI 1000-2). A key to which figure „O“ is
assigned may be used as programming key.
The device consists of two parts these are reading device and evaluation unit.
The installation of the device is quite simple. A separate transformer is not necessary. An A.C.-door
opener (12 V) usual in the trade may be connected directly. Operating voltage, 230V A.C. and reading
device being connected, the whole device is ready for use. As connecting line between reading device
and evaluation unit, a commercial ringing wire
(2-wire cable)
is sufficient.
The length of the cable may be up to 100 m. Polarity does not have any importance.
Using a manual terminal the entering and deleting of keys is quite easy. In this case, the whole
operation is done via the manual terminal which is held on to the reading device. Up to three reading
devices may work together with one evaluation unit.
Power supply 230V AC
2 potential free relay exits with one break contact each, 1 make contact 230V 5A
12V A.C. exit to connect an electric door opener
999 keys at a maximum may be entered
decoder RFI 1000 does not have a second relay exit and no 12V A.C. exit
decoder-protective system: IP40 or IP65 optional
reading-device protective system: IP65
Normal working order
The turn switches should not be in „0“ position. A RFI key is brought into the reading area of the
reading device (distance : 1 to 5 cm, according to each type). Please make sure the RFI key is held as
parallel to the surface of the reading device as possible. If the RFI key is accepted to be valid,
the red
luminous diode on the reading device
beams and the red and the green luminous diode on the
evaluation unit and on relay 1 attract resp. the red and the yellow luminous diode and relay 2 attract as
long as the RFI key remains within the reading area.
As soon as the RFI key leaves the reading area the luminous diodes go out and the relay tapers off after
a delay time.
The length of
delay
time
may be adjusted. If a card is not accepted and regarded to be
invalid, the red luminous diode on the reading device and the red luminous diode on the evaluation
unit flash in short intervals. None of the relays does attract. If the luminous diodes remain dark, there is
no RFI key recognized.