background image

OUMAN OY

www.ouman.fi

2.

3.

X = 130 mm, 180 mm, 290 mm

TMW

Water sensor

The water sensors (TMW) installed on the water pipes  are suitable for heat-

ing and domestic hot water control. The water sensors come with immersion 

sensor of different lenghts as follows (Ø 4 mm):

The sensor should be positioned at a point where the water is well mixed. 

With heating control install the supply water sensor approx. 1 m from the 

mixing point and with hot water temperature control  install the supply water 

sensor less than 0,5 m from the mixing point

Installation and connection

Install the water sensor on the bend of the water-supply pipe so that the 

immersion sensor faces opposite the direciton of flow.

1.  Screw the sensor on a welded pipe fitting or T-piece using proper sealing 

methods. The case can be turned clockwise at the end of the rst pocket 

until the cable’s bushing seal goes down.

2.  Open the screw-off lid and connect the sensor to the controlling device as 

a two-wire connection using weak current cable. The polarity of the cable 

is irrelevant. 

3.  Tighten the bushing seal so that it acts as a seal and repels water.

Type code 

Meas. element 

Meas. accuracy

TMW-(50, 100, 210) / NTC10  

NTC 10 

+ 0,2 °C (0-70 °C)

TMW-(50, 100, 210) / Pt1000 

Pt 1000 

+ 1 °C (0-70 °C)

TMW-(50, 100, 210) / Ni1000  

Ni 1000 LG 

+ 1 °C (0-70 °C)

Technical information

Materials

- Case 

Cover PC, base PBT, seal PA

- Immersion pipe and nipple 

RST AISI 304 EN 1.4301 

Range of use 

-50 °C...+130 °C (water, cooling liquids)

Protection class 

IP 54

Seal 

 

  M16 x 1,5

Pressure class 

PN 16

Time constant 

< 3 s

Thread 

R ½”, cross-knurling

Wrench size 

22 mm