Installation Instructions

Cloud adaptor

Model No. 

CZ-CFUSCC1 

Please Read Before Starting

This controller must be installed by the sales dealer or installer.
These instructions are all you need for most installation sites
and maintenance conditions. If you require help for a special
problem, contact our sales/service outlet or your certi

fi

 ed dealer

for additional instructions.

WARNING

This symbol refers to a hazard or unsafe 
practice which can result in severe personal 
injury or death.

CAUTION

This symbol refers to a hazard or unsafe 
practice which can result in personal injury 
or product or property damage.

 

We assume no responsibility for accidents or damages 
resulting from methods other than those described in the 
installation instructions or methods without using speci

fi

 ed 

parts. Malfunctions that occurred due to the unauthorised 
installation methods are not covered by the product warranty.

 

This controller shall be installed in accordance with National 
Wiring Regulations.

 

After the installation is complete, perform test operation to 
con

fi

 rm that no abnormality is present.

 

Read the installation instructions of devices to be connected as well.

 

When relocating or repairing this controller, provide the 
Installation Instructions to the servicing personnel.

 WARNING

ELECTRICAL SHOCK CAN CAUSE 
SEVERE PERSONAL INJURY OR DEATH.
ONLY A QUALIFIED, EXPERIENCED 
ELECTRICIAN SHOULD ATTEMPT TO 
WIRE THIS SYSTEM.

 

Highly dangerous electrical voltages are used 
in this system. Carefully refer to the wiring 
diagram and these instructions when wiring. 
Improper connections and inadequate 
grounding can cause 

accidental injury or 

death.

 

This controller is strongly recommended to be 
installed with Earth Leakage Circuit Breaker 
(ELCB) or Residual Current Device (RCD).
Otherwise, it may cause electrical shock 
and 

fi

 re in case of equipment breakdown or 

insulation breakdown.
Earth Leakage Circuit Breaker (ELCB) must be 
incorporated in the 

fi

 xed wiring in accordance 

with the wiring regulations. The Earth Leakage 

Circuit Breaker (ELCB) must be an approved 
10 A, having a contact separation by 3 mm in 
all poles.

 

Provide a power outlet to be used exclusively 
for this controller.

 

Turn off the circuit breaker of the controllers 
before installation.

 

Do not supply power to the controller until all 
wiring is completed or reconnected and checked.

 

Fix the power supply wiring securely with the 
clamper so that the power supply terminal 
board is free of tension (external force) when 
pulled. Loose connection of the terminal 
board may occur 

fi

 re.

 

To prevent possible hazards from insulation 
failure, the controller must be grounded.

 

Select an installation location which is rigid and 
strong enough to support or hold the controller, 
and select a location for easy maintenance. 

 

This product must not be modi

fi

 ed or 

disassembled under any circumstances.
Modi

fi

 ed or disassembled controller may 

cause 

fi

 re, electric shock or injury.

 

Do not clean inside the controller by users. 
Engage authorized dealer or specialist for cleaning.

 

Do not operate with wet hands.

 CAUTION

 

Ground yourself to discharge static electricity 
before performing any wiring.

 

Do not use the controller at the following locations. 

• Areas where leakage of 

fl

 ammable gas may 

be expected

• Places where large amounts of oil mist exist
• Locations where external air may enter the room 

directly (This may cause “condensation”.)

• Locations where high-frequency emissions 

are generated

• Locations where voltage 

fl

 uctuation frequently occurs

 

Do not wash with water.

Safety Precautions

CZ-CFUSCC1̲工説̲E.indd   1

CZ-CFUSCC1̲工説̲E.indd   1

2016/02/17   15:49:42

2016/02/17   15:49:42

Summary of Contents for CZ-CFUSCC1

Page 1: ...or death This controller is strongly recommended to be installed with Earth Leakage Circuit Breaker ELCB or Residual Current Device RCD Otherwise it may cause electrical shock and fire in case of equipment breakdown or insulation breakdown Earth Leakage Circuit Breaker ELCB must be incorporated in the fixed wiring in accordance with the wiring regulations The Earth Leakage Circuit Breaker ELCB mus...

Page 2: ...od consult the network administrator Installation Precautions Installation Location Avoid the following locations for installation Under direct sunlight Location near heat source Location where the controller will be splashed with water or affected by dampness or humidity Uneven surface Location that is subject to excessive vibration or physical impacts Fixing screws may come off and the controlle...

Page 3: ...H05RN F or H07RN F which conform to CENELEC HAR rating specifications or use the wiring based on IEC standard 60245 IEC57 60245 IEC66 Total Wire Length 30 m or less Inter Unit Control Wiring Type of wiring Use a flexible shield wiring of 0 5 to 2 mm2 Total Wire Length 1000 m or less Number of connectable units and devices Up to total of 100 units and devices can be connected Indoor unit Up to 64 u...

Page 4: ...oltage DC5 V 10 Contact allowable current Max 10 mA Pulse input 1 Pi1 8 Pulse input 2 Pi2 9 Pulse input 3 Pi3 10 Common COM 7 COM Pulse width 30 msec or more 100 msec or more Pulse interval 1 sec or more Connecting Wiring When connecting external equipment refer to the Connecting to external equipment section below U1 U2 0 1 2 3 4 5 6 20 U1 U2 TB1 TB2 Power supply wiring Power supply terminal boar...

Page 5: ...tion section back cover page 5 Start up the PC and set if the network settings as follows IP address 192 168 1 100 Subnet mask 255 255 255 0 Default gateway 192 168 1 254 6 Enter the following URL in the Web browser and access the cloud adaptor https 192 168 1 1 Recommended Web browser specifications Internet Explorer IE 11 The login screen appears If the login screen does not appear Check if the ...

Page 6: ... and the number of detected units correspond with each other If some of the indoor units are not displayed unexpected indoor units are displayed Check if wiring is properly done or the address setting for air conditioners is correct After correction redo from step 2 4 Enter the central address To assign manually Select the central address text box of the indoor unit on the A C Unit List screen and...

Page 7: ...ctions 1 2 When DHCP is used in the network environment Add a check mark for DHCP Enabled When other than the above Remove the check mark for DHCP Enabled and enter IP address Subnet mask and Default gateway of the cloud adaptor 2 3 When the DNS server information can be automatically obtained in the current environment Add a check mark for Obtain DNS server address automatically When other than t...

Page 8: ...Orange Red Green Lighting Blinking slow once per about 2 seconds Blinking fast once per about 1 second Off LED Status and Solution The cloud adaptor is in the maintenance mode page 7 After maintenance change it to the operation mode Communication failure Both Link 1 and 2 Check if the inter unit control wiring between the air conditioners and the cloud adaptor is correct Both Link 1 and 2 Communic...

Reviews: