INSTALLATION INSTRUCTIONS

 © Panduit Corp. 2010

FS012

Opticom Rack Mount Fiber Cassette Enclosure

Part Number: FCE4U

1 - ENCLOSURE 
4 - #12-24 X 1/2" SCREWS
4 - M6X1 SCREWS
2 - #10-32 X 3/8" SCREWS
4 - #10-32 HEX NUTS

CAUTION:

Fiber optic cable is sensitive to excessive pulling, bending and crushing forces. Consult the manufacturer’s cable specification sheet for the 
specific cable in use.

Follow TIA/EIA-568A, 569, 606, and 607 installation guidelines where applicable.

WARNING: UNMATED CONNECTORS MAY EMIT INVISIBLE LASER RADIATION. DO NOT LOOK DIRECTLY INTO THE END OF 
THE CONNECTOR. DO NOT INSPECT WITH MAGNIFYING DEVICES. MAINTAIN CAP ON UNMATED CONNECTORS.

Care should be taken when opening and closing fully loaded enclosure in order to protect fiber components.

Contents:

2 - GROMMETS
2 - STRAIN RELIEF BRACKETS
3 - TAK-TYS (6" pcs.)
4 - CABLE TIES (PLT2S-M0)
2 - SLACK SPOOLS

3 - ADHESIVE BEVEL ENTRY CLIPS
3 - ADHESIVE MOUNTS
1 - CAUTION LABEL
1 - LASER WARNING LABEL
2 - BEND RADIUS POSTS

Enclosure

Trunk or 
Interconnect 
Cable Entry 
Grommet

ASSEMBLY VIEW

FCE4U

Strain Relief Bracket

Bend Radius 
Post

Door Assembly
(shown in open 
position)

Figure 1

Enclosure 
Sliding Drawer

Lid (not removable)

Page 1 of 10

Blank
(removable)

Summary of Contents for FCE4U

Page 1: ...NG UNMATED CONNECTORS MAY EMIT INVISIBLE LASER RADIATION DO NOT LOOK DIRECTLY INTO THE END OF THE CONNECTOR DO NOT INSPECT WITH MAGNIFYING DEVICES MAINTAIN CAP ON UNMATED CONNECTORS Care should be tak...

Page 2: ...surrounding sheet metal DO NOT install grommet at this stage grommet will be installed after enclosure is mounted to rack Place enclosure mounting brackets at desired position on the rack Mount the en...

Page 3: ...re Install grommet following the proper cutting diagram See Figure 4A Cut the small circle for 1 diameter innerduct Cut the large circle for 1 1 2 diameter innerduct Cut the straight lines when not us...

Page 4: ...lted down cables omitted for clarity Opticom QuickNet Cassette Installation Route fiber through grommet to fiber cassettes as shown Leave enough slack so when the drawer is fully extended the cables a...

Page 5: ...For Technical Support www panduit com resources install_maintain asp INSTALLATION INSTRUCTIONS Panduit Corp 2010 FS012 Figure 6C Tray in home position cover omitted for clarity Page 5 of 10...

Page 6: ...punch hole into adhesive mounts Note spool orientation Position FAPs between upright flanges as shown Once mounted fully seat NyLatches to secure FAPs Fully extend tray to ensure proper amount of slac...

Page 7: ...tended the cables are not put under tension DO NOT use so much slack that the drawer cannot be returned to its home position See Figure 7C Use Tak Tys to secure fiber cords at cable entry location and...

Page 8: ...der note orientation The remaining FOSMs are stacked on top of each other and snap in place after termination of lower tray Position FAPs between upright flanges as shown Once mounted fully seat NyLat...

Page 9: ...lete loop of individual fibers around splice tray slack spools See instruction sheet for splice trays Leave enough jacketed slack so when the drawer is fully extended the cables are not put under tens...

Page 10: ...eld to allow room to route patch cords under the tabs to the cable manager Plug fiber connector into FAP adapter Route patch cords down to fiber manager base under fiber manager fingers and Bend Radiu...

Reviews: