0.875"
AFTER PROPER TERMINATION OF FERRULE,
MARK LINE ON CONDUCTOR INSULATION
FROM END OF CRIMPED FERRULE
STRIP
SENSOR LEAD
INSULATION
FERRULE F80-12-M
FIGURE 2: CONNECTOR FEATURES
T10 TORX TERMINAL SCREWS are accessible
from the two ports and are used to ADJUST
TERMINALS inside the CONNECTOR. TERMINALS
are used to SECURE a PAIR of COLOR-CODED,
FULLY-INSERTED and PROPERLY-CRIMPED TAP
WIRES (AVT Sensor Leads) within TERMINALS
INSERTION PORTS for FULLY-INSERTED
and PROPERLY-CRIMPED TAP WIRES
(AVT Sendor Leads) into TERMINALS
INSIDE THE CONNECTOR
MAIN FASTENER
Page 1 of 3
For Technical Support: www.panduit.com/resources/install_maintain.asp
FIGURE 1: PREPARATION OF FERRULES
ONTO SENSOR LEADS
Step-by-Step Installation Procedure:
Always de-energize panel and verify absence of voltage before installation.
See FIGURE 1: Prepare (strip) AVT device sensor leads
1.
See FIGURE 1: Crimp ferrules F80-12-M onto sensor seads
2.
See FIGURE 1: Make locating mark on sensor leads
3.
See FIGURE 2: Review connector features
4.
See FIGURE 2: Loosen factory-tightened MAIN FASTENER at least 6 full turns before proceeding to next step.
5.
CONNECTION KIT
CATALOG
PART NUMBER
"RUN" WIRE RANGE
(CODE WIRE)
"TAP" WIRE AWG
(Terminated with Ferrule)
CONNECTOR
FERRULE
Min.
Max.
CATALOG
P/N
QUANTITY CATALOG
P/N
QUANTITY
VS-CKP14-6
14 AWG SOL
14 AWG STR
6 AWG SOL
6 AWG STR
14 AWG STR Class K
(Terminated with Ferrule)
VSC6
3
F80-12-M
12
VS-CKP4-000
4 AWG SOL
4 AWG STR
3/0 AWG STR
VSC3/0
3
F80-12-M
12
VeriSafe Insulation-Piercing Connector: VSC Series
VeriSafe Insulation-Piercing Connection Kit: VS-CKP Series
for
VeriSafe AVT Sensor Lead Tapping on Copper Conductors
IMPORTANT
:
READ THIS ENTIRE INSTRUCTION SHEET BEFORE ATTEMPTING TO INSTALL THE CONNECTOR
.
READ THE ENTIRE VERISAFE AVT ABSENCE OF VOLTAGE TESTER INSTRUCTION MANUAL (B21052
, OR EQUIVALENT
)
PROVIDED WITH THE AVT DEVICE OR DOWNLOAD CURRENT MANUAL FROM .
C
Panduit Corp. 2018
INSTALLATION INSTRUCTIONS
T-PMPI-322-PC
(revision 02)
TM
TM
TM
Safety Information:
PANDUIT VSC Series Insulation-Piercing Connectors are intended for use in simplifying installation and connection of
PANDUIT VeriSafe AVT Absence of Voltage Testers to phase (run) conductors, per electrical code requirements, within
the rated environmental and operational limitations according to regulatory / safety standard certifcations or listings.
Always DE-ENERGIZE panel and VERIFY for absence of voltage in panel before attempting to install connector.
•
Installer must ALSO follow all safety, installation, commissioning and operating steps from the AVT Device Manual.
•
Connector is intended for one-time installation and use only! Do not reuse nor re-install connector.
•
www.panduit.com
Connection Kit Contents:
Connection Kits contain connectors and ferrules to install the AVT Device per below;
TM
TM
TM