EMK-XP

ElEctroMElt PowEr connEction and End SEal Kit inStallation inStructionS

Description

The ElectroMelt EMK-XP Power Connection and End Seal Kit is for 

use with ElectroMelt EM2-XR heating cable for snow-melting and 

anti-icing applications. Materials for one power connection and 

one end seal are included. This kit is suitable for connecting the 

heating cable to 14 through 4 AWG (Cu only) power wires. Power 

wiring must meet NEC or CEC requirements and have a minimum 

temperature rating of 167°F (75°C).
These installation instructions should be used in conjunction with 

the ElectroMelt System Design Guide (H53393) and ElectroMelt 

System Installation and Operation Manual (H58086).
For technical support call Pentair Thermal Management at 

(800) 545-6258.

tools requireD

•  Needle-nose pliers 

•  Utility knife

•  Heat gun or propane torch 

•  Wire strippers

•  Ideal Crimp Tool Model 30-425  •  Diagonal cutters

ADDitionAl MAteriAls requireD

•  EMK-XJB (Not shown) or equivalent UL Listed or CSA Certified 

weatherproof junction box suitable for the location. A minimum 

of 400 cubic inches are needed for 1 power connection and 1 end 

termination per junction box.

This component is an electrical device that must be installed correctly to ensure proper 

operation and to prevent shock or fire. Read these important warnings and carefully follow 

all the installation instructions.
•  To minimize the danger of fire from sustained electrical arcing if the heating cable 

is damaged or improperly installed, and to comply with the requirements of Pentair 

Thermal Management, agency certifications, and national electrical codes, ground-

fault equipment protection must be used. Arcing may not be stopped by conventional 

circuit breakers.

•  Approvals and performance are based on the use of Pentair Thermal Management-

specified parts only. Do not substitute parts or use vinyl electrical tape.

•  The black heating cable core is conductive and can short. It must be properly insulated 

and kept dry.

•  Damaged bus wires can overheat or short. Do not break bus wire strands when scoring 

the jacket or core.

•  Do not bury any of the components. Both the power connection and end seal must be 

installed in a dry junction box.

•  Heat-damaged components can short. Use a heat gun or torch with a soft, yellow, low-

heat flame. Keep the flame moving to avoid overheating, blistering, or charring the 

heat-shrinkable tubes. Avoid heating other components. Replace any damaged part. 

•  Bus wires will short if they contact each other. Keep bus wires separated.
•  Connection kits and heating cable ends must be kept dry before and during 

installation.

•  Damaged heating cable can cause electrical arcing or fire. Use only plastic cable ties 

to secure the heating cable to the reinforcement. Do not use metal attachments such 

as tie wire.

•  Do not attempt to repair or energize damaged heating cable. Remove damaged 

sections at once and replace them with a new length using the appropriate Raychem 

splice kit. Replace damaged connection kits.

•  Megohmmeters operate at high voltage. This voltage is hazardous and possibly lethal. 

Read and follow all instructions included with the instrument you are using.

HealtH Hazard

: Over heating heat-shrinkable tubes will produce 

fumes that may cause irritation. Use adequate ventilation and avoid 

charring or burning. Consult MSDS RAY4566 for further information.
CHEMTREC 24-hour emergency telephone:  

(800) 424-9300
Non-emergency health and safety information:  

(800) 545-6258

.

WARNING:

CAUTION:

Kit contents

item qty  Description

power connection

Black heat-shrinkable tube – 1 1/2 x 6 in (38 x 152 mm)

Heat-shrinkable cap

Clear yellow heat-shrinkable tubes – 1/2 x 2 3/4 in (13 x 70 mm) 

Clear yellow heat-shrinkable tube – 1/2 x 2 in (13 x 51 mm) 

“Electric Deicing and Snow Melting” labels

Black heat-shrinkable tubes – 1/8 x 3/4 in (3 x 19 mm) 

Small non-insulated crimp connectors

Large non-insulated crimp connectors

Cable tie

Mastic sheet – 3 x 12 in (76 x 305 mm)

end seal

Black heat-shrinkable tube – 1 1/2 in x 6 in (38 mm x 152 mm) 

Mastic sheet – 3 in x 12 in (76 mm x 305 mm)

Black heat-shrinkable tube – 1 in x 3 in (25 mm x 76 mm) 

Clear yellow heat-shrinkable tube – 1/2 in x 1 1/2 in (13 mm x 38 mm)

ApprovAls

LISTED

877Z

DE-ICING AND

SNOW MELTING EQUIPMENT

-W

A

B

C

D

E

F

G

H

I

J

K

L

tHerMAl builDing solutions

Raychem-IM-H57284-EMKXP-EN-1612

Summary of Contents for Raychem EMK-XP

Page 1: ...etorcore Donotburyanyofthecomponents Boththepowerconnectionandendsealmustbe installedinadryjunctionbox Heat damagedcomponentscanshort Useaheatgunortorchwithasoft yellow low heatflame Keeptheflamemovingtoavoidoverheating blistering orcharringthe heat shrinkabletubes Avoidheatingothercomponents Replaceanydamagedpart Buswireswillshortiftheycontacteachother Keepbuswiresseparated Connectionkitsandheati...

Page 2: ...ck around heating cable to remove Note See Step 1 for proper heating techniques Instructions for using a heat gun or torch Read important warnings on page 1 and follow safety precautions provided with heat gun or torch When using a torch use a soft yellow low heat flame Apply just enough heat to do the job Keep torch or heat gun moving continuously to distribute the heat evenly to avoid overheatin...

Page 3: ...m F over bus wires Shrink tubes completely Lightly score inner jacket around and down as shown Bend heating cable to break jacket at score Peel off jacket Score between bus wires at inner jacket Bend core to break free at inner jacket Peel core and any remaining material from bus wires Remove 1 1 2 in 38 mm insulation from power supply lines Remove 1 in 25 mm insulation from equipment grounding co...

Page 4: ...he correct crimp tool Ideal 30 425 when making the connections To make the proper crimp connection position the heating cable bus wire directly below the larger supply wire Position the supply wire and bus wire in the crimp connectors and crimp tool exactly as shown Crimp each connector twice see detail Use only one crimp connector to attach equipment grounding conductor to heating cable braid see...

Page 5: ...immediately pinch end while tube is still hot hold for 5 seconds to ensure seal Allow tubes to cool Cut two 3 in x 1 3 4 in 76 mm x 44 mm pieces from one mastic sheet Item J Cut a 3 in x 5 in 76 mm x 127 mm piece from one mastic sheet Item J Wrap each power wire with a 3 in x 1 3 4 in 76 mm x 44 mm piece of mastic Fold the covered power wires flat against the heating cable Use the 3 in x 5 in 76 m...

Page 6: ...at the cap until it shrinks completely Cut second mastic sheet Item J into two pieces 3 in x 6 in 76 mm x 152 mm Secure all wires 2 in 51 mm from end of outer jacket using cable tie Item I Position braid connection next to cap Wrap braid connection and 1 2 in 13 mm of outer jacket with 3 in x 6 in 76 mm x 152 mm mastic sheet Item J Note See Step 1 for proper heating techniques IMPORTANT If cap sta...

Page 7: ...n 13 mm 6 in 152 mm tube Heat this end first 24 Position the 6 in 152 mm long heat shrinkable tube Item A over the mastic sheet 1 2 in 13 mm from end of mastic sheet Begin heating tube at end near cable tie Heat until tube is recovered completely and adhesive or mastic flows from ends Continue to heat center section to melt mastic inside but do not blister or burn tube Allow the connection to cool...

Page 8: ...l adhesive or mastic flows out ends Remove heat source and immediately pinch end with needle nose pliers for 20 seconds to ensure a complete moisture seal Allow tube to cool completely Refer to Material Safety Data Sheet RAY4566 Position short tube Item L over end of heating cable as shown Heat tube until it shrinks and adhesive flows out ends While still hot gently pinch end and hold for 5 second...

Page 9: ...at center section to melt mastic inside but do not blister or burn tube Remove heat source and immediately pinch end with needle nose pliers for 20 seconds to ensure a complete moisture seal Allow end seal to cool completely Position end seal so it does not come in contact with power connection Route heating cable so that power connection and end seal are in same junction box Use an EMK XJB juncti...

Page 10: ...NORTH AMERICA Tel 1 800 545 6258 Fax 1 800 527 5703 Tel 1 650 216 1526 Fax 1 650 474 7711 thermal info pentair com Pentair and ElecroMelt are owned by Pentair or its global affiliates All other trademarks are the property of their respective owners Pentair reserves the right to change specifications without prior notice ...

Reviews: