To  reduce  the  risk of  fire or  electric shock,  do  not  expose 
this device to rain or moisture. Do not energise unless the 
front  cover  is  in  place.    This  device  must  be  earthed. 
Installation,  programming  and  maintenance  must  be 
carried out by qualified personnel. 

 

0.24A Single Phase Supply

 

 

 

15V DC Regulated Output

 

 

 

Output is Short Circuit Proof

 

 

 

Enclosure is DIN Rail Mount with Circuit Breaker Profile

 

 

 

Simple Installation - 

DIN Rail mount facilitates installation. 

All connection terminals are accessible without disassembly 

Warning 

– 

This is a class A product.  In a domestic environment 

this product may cause radio interference in which case the user 
may be required to take adequate measures. 

Read  Instructions

 

–  We  recommend  that  you  read  this 

Instruction Manual prior to commencement of installation.   

Power

 

Sources

 

–  This device  should  only  be  operated from the 

type of supply specified on the front cover.  This device 

must

 be 

earthed. 

Output

 

– The load on this device should not exceed the specified 

capacity  of  1.5A.  This  device  should  be  fed  via  a  HRC  fuse  or 
MCB. 

Mounting  Location

 

–  Install  in  a  dry,  well-ventilated  location.  

Controllers  may  emit  some  mechanical  noise.    Take  this  into 
account when deciding the mounting location. 

Data Cable

 

– Use screened, stranded RS485 data cable with 

three twisted pairs. Segregate from mains cables by 300mm 
minimum.  Connect devices in a ‘daisy chain’.  A data cable that is 
connected to an energised device is live.  Do not cut or terminate 
live data cables. 

1.  Mount the device on a DIN rail inside an approved enclosure. 

 

2.  Connect a single phase 0.25A feed to the control circuit supply terminals.  This device must be earthed. 

 

3.  Connect the two power conductors of data cables to the device. There are two common methods of doing this: 

a) 

Method 1

: Use a 2 core cable to connect between the DDNP1501 and the data cable connector on a device that is 

connected to the network. Parallel connect the GND and +12V terminals on the DDNP1501 to the GND and +12V 

terminals on the network device. 

b) 

Method 2

:  Loop the network cable to the DDNP1501 and connect the Green pair to GND terminal and Orange pair to 

+12V terminal. Ensure that the other conductors are looped through using a suitable terminal block. 

……… 

DDNP1501 

15v DC network power supply 
Installation Manual 