3-Way or More Applications (Multi-Location)

 

OccuSwitch Manual-ON Occupancy Sensor Remote 

California Title 24 2008 Compliant

Cat. No. LRS2211R - 120VAC, 60Hz

For use with Cat. No. LRS22110 Sensors

INSTALLATION INSTRUCTIONS

WARNINGS AND CAUTIONS:

• 

TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER AT CIRCUIT BREAKER OR FUSE AND TEST THAT THE POWER IS OFF BEFORE WIRING!

•  

To be installed and/or used in accordance with electrical codes and regulations.

•  

To avoid overheating and possible damage to this device and other equipment, 

DO NOT install to control a receptacle.

•  

Use only one LRS22110 sensor in a multi-location circuit with up to LRS2211R matching remotes with LEDs.

WARNINGS AND CAUTIONS:

•  

If you are not sure about any part of these instructions, consult an electrician.

•  

The Manual-On Occupancy Sensor Remote is intended to replace additional 3-Way and 4-Way switches when used with the LRS22110 

Occupancy Sensors.

•  

Do not touch the surface of the lens. Clean outer surface gently with damp cloth only. 

DO NOT use soaps or cleaning liquids. 

•  Use this device 

WITH COPPER OR COPPER CLAD WIRE ONLY.

DI-401-IPV0R-02A

4-Way Wiring of Sensor Remote with LRS22110 

Sensor:

 Step 4b

 TOOLS NEEDED TO INSTALL YOUR DEVICE

INSTALLING YOUR  REMOTE

NOTE: Use check boxes        when Steps are completed.

Slotted/Phillips Screwdriver 

Electrical Tape 

Pliers 

Pencil  

 

Cutters  

Ruler

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

 Step 1

WARNING:

 

TO AVOID FIRE, SHOCK, OR DEATH; 

TURN OFF POWER at circuit breaker or fuse and test 

that power is off before wiring!

 Step 2

Identifying your wiring application 

(most common) -

 NOTE: If the wiring in the wall box 

does not resemble any of these configurations, consult an 

electrician.

3

5

1
2

6

4

4-Way

1.  First Traveler – note color 

2.  Second Traveler – tagged 

3.  Neutral 

4.  Ground 

5.  Third Traveler – note color 

6.  Fourth Traveler – tagged 

NOTE: For matching remote 

w/LEDs installation, the 

First 

Traveler becomes Line Hot.

2

4

1

5

3

3-Way

1.  Line or Load (See important 

  instruction below) 

2.  Neutral 

3.  Ground 

4.  First Traveler – note color 

5.  Second Traveler – note color 

NOTE: For matching remote 

w/LEDs installation, the 

First 

Traveler becomes Line Hot.

3-Way Wiring of Sensor Remote with 

LRS22110 Sensor:

 Step 4a

IMPORTANT:

For 3-Way applications, note that one of the screw terminals from 

the old switch being removed will usually be a different color (Black) or 

labeled Common. Tag that wire with electrical tape and identify as the 

common (Line or Load) in both the sensor wall box and remote wall box.

For 4-Way applications, note that the old switch being removed will 

have 4 screws plus a ground screw. Tag the two same color insulated 

wires with electrical tape. 

BK

RD

3-Way

WH

BK

RD

3-Way

WH

Terminal

Screw marked

White (WH)

Terminal

Screw marked

White (WH)

Terminal

Screw marked

Red (RD)

3

1

3

4

LRS22110 Sensor

LRS2211R Remote

Additional

Neutral Wire

Terminal

Screw

marked

3-Way

Terminal

Screw

marked

Black (BK)

Ground

Terminal

Screw

(Green)

Terminal

Screw

marked

3-Way

Terminal

Screw

marked

Black (BK)

Ground

Terminal

Screw

(Green)

5

1

5

Hot (Black)

Neutral (White)

LRS22110 Sensor

LRS2211R Remote

3-Way

RD

WH 

BK 

3-Way

WH

BK

Black

White

Line 

120VAC, 60Hz

Green

Ground

Green

Ground

LOAD

NOTE: The Occupancy Sensor must be installed in a wall box that has a Load 

connection. The sensor remote 

must be installed in a wall box with a Line Hot 

connection and a Neutral connection. A Neutral wire to the sensor remote needs 

to be added as shown. If you are unsure about any part of these instructions, 

consult an electrician. 

NOTE: Maximum wire length from sensor to all installed 

remotes cannot exceed 300 ft (90 m).

WIRING SENSOR REMOTE (3-Way wall box with Line Hot 

connection):

Connect wires per WIRING DIAGRAM as follows:

NOTE: Use backwire connection when connecting two wires to one screw terminal.

•  Green or bare copper wire in wall box to Green terminal screw on Sensor 

Remote.

•  Line Hot (common) wall box wire identified (tagged) when removing old 

switch and First Traveler wall box wire to Sensor Remote terminal screws 

marked "BK".

•  Second Traveler wall box wire from other 3-Way wall box to Sensor Remote 

terminal screw marked "3-Way". This traveler from the remotes must go to the 

terminal screw marked "3-Way" on the sensor.

•  Neutral wall box wire to remote terminal screw marked "WH".

WIRING SENSOR (3-Way wall box with Load connection):

Connect wires per WIRING DIAGRAM as follows:

NOTE: Use backwire connection when connecting two wires to one screw terminal.

•  Green or bare copper wire in wall box to Green terminal screw on sensor.

•  Load wall box wire identified (tagged) when removing old switch to terminal 

screw marked "RD" on sensor.

•  First Traveler Line Hot to terminal screw marked "BK" on sensor.

•  Remove Red insulating label from terminal screw marked "3-Way" on sensor.

•  Second Traveler wall box wire 

(note color as above) to terminal screw 

marked "3-Way" on sensor. This traveler must go to the terminal screw on 

the Sensor Remote marked "3-Way" or to the terminal screw on the Vizia 

matching switch remote marked "YL/RD".

•  Neutral wall box wire to terminal screw marked "WH" on sensor.

BK

RD

3-Way

WH

BK

RD

3-Way

WH

LRS2211R Remote

(3-Way Wall box from Step 2)

LRS2211R Remote

(4-Way Box from Step 2)

LRS22110 Sensor

(3-Way Wall Box from Step 2)

Terminal

Screw marked

White (WH)

Terminal 

Screw marked 

White (WH) 

Terminal

Screw marked

White (WH)

3

1

Additional

Neutral Wire

Additional

Neutral Wire

BK

YL/RD

WH

RD

3

6

2

1

Terminal

Screw

marked

Yellow/Red

(YL/RD)

Terminal

Screw

marked

Black (BK)

5

5

Terminal

Screw marked

Red (RD)

1

5

4

Terminal

Screw

marked

3-Way

Terminal

Screw

marked

Black (BK)

Ground

Terminal

Screw

(Green)

Terminal

Screw

marked

3-Way

Terminal

Screw

marked

Black (BK)

Ground

Terminal

Screw

(Green)

Ground

Terminal

Screw

(Green)

4

2

Hot (Black)

Neutral (White)

LRS22110 Sensor

LRS2211R Remote  

VP0SR-1L Remote

YL/RD 

3-Way

RD

WH 

WH

BK 

3-Way

WH

BK

BK

Line 

120VAC, 60Hz

Black

White

Green

Ground

Green

Ground

LOAD

Green

Ground

NOTE: The Occupancy Sensor must be installed in a wall box that has a Load 

connection. The sensor remote 

must be installed in a wall box with a Line Hot 

connection and a Neutral connection. A Neutral wire to the sensor remote needs to 

be added as shown. If you are unsure about any part of these instructions, consult 

an electrician. 

NOTE: Maximum wire length from sensor to all installed remotes 

cannot exceed 300 ft (90 m).

WIRING SENSOR REMOTE (3-Way wall box with Line Hot 

connection):

Connect wires per WIRING DIAGRAM as follows:

NOTE: Use backwire connection when connecting two wires to one screw terminal.

•  Green or bare copper wire in wall box to Green terminal screw on Sensor 

Remote.

•  Line Hot (common) wall box wire identified (tagged) when removing old switch 

and First Traveler wall box wire to Sensor Remote terminal screw marked "BK".

•  Second Traveler wall box wire from 4-way wall box to Sensor Remote terminal 

screw marked "3-Way" 

(note wire colors). This traveler from the remotes must 

go to the terminal screw marked "3-Way" on the sensor.

•  Neutral wall box wire to remote terminal screw marked "WH".

WIRING SENSOR REMOTE (4-Way wall box):

Connect wires per WIRING DIAGRAM as follows:

NOTE: Use backwire connection when connecting two wires to one screw terminal.

•  Green or bare copper wire in wall box to Green terminal screw on Sensor 

Remote.

•  First Traveler and Third Traveler wall box wires to Sensor Remote terminal screw 

marked "BK".

•  Second Traveler (tagged) and Fourth Traveler (tagged) wall box wires to Sensor 

Remote terminal screw marked "3-Way" terminal screw marked "YL/RD" 

(note 

wire colors). This traveler from the remotes must go to the terminal screw 

marked "3-Way" on the sensor.

•  Neutral wall box wire to remote terminal screw marked "WH".

WIRING SENSOR (3-Way wall box with Load connection):

Connect wires per WIRING DIAGRAM as follows:

NOTE: Use backwire connection when connecting two wires to one screw terminal.

•  Green or bare copper wire in wall box to Green terminal screw on sensor.

•  Load wall box wire identified (tagged) when removing old switch to terminal 

screw marked "RD" on sensor.

•  First Traveler Line Hot to terminal screw marked "BK" on sensor.

•  Remove Red insulating label from terminal screw marked "3-Way" on sensor.

•  Second Traveler wall box wire 

(note color as above) to terminal screw marked 

"3-Way" on sensor. This traveler must go to the terminal screw on the Sensor 

Remote marked "3-Way".

•  Neutral wall box wire to terminal screw marked "WH" on sensor.

 CHANGING THE COLOR OF YOUR DEVICE

Your device may include color options. To change color of the face 

proceed as follows:

RESET

RESET

TESTTEST

1    2
0    3

Push down 

tabs per 

diagram, 

one at a time 

and rotate 

forward to 

release

Attach new 

face by 

inserting 

bottom hinge 

tabs, then 

pivot and 

snap the 

color kit to 

attach

•  

Make sure that the ends of the wires from the wall box are 

straight (cut if necessary).

•  Remove insulation from each wire in the wall box as shown.

Strip Gage 

(measure bare wire 

here or use gage on 

back of the remote)

5/8”

(1.6 cm)

Cut

(if necessary)

 Step 3

Preparing and connecting wires:

This remote can be wired using side wire terminal 

screws or through backwire openings. Choose 

appropriate wire stripping specifications accordingly.

Side Wire

Side wire terminals 

accept #14-12 AWG 

solid copper wire only.

Back Wire 

Back wire openings 

use #14-12 AWG 

solid 

copper wire only.

BK

RD

YL 3-Way

WEB 

VERSION