background image

 

V01-050417 

 

TIR Two 

 

TIR  Two  (Temperature  Inputs  Relays)  is  a  digital  signals  and  impulse 
centralizer. In only 4 DIN modules, the unit has 2 relay outputs, 2 voltage 
free digital inputs and 2 NTC/PTC inputs for temperature sensors. 

The  device  works  with  LoRa

TM

  protocol  for  long  range  radio 

communications, 

with maximum communication’s range of 1 km indoor and 

up to 20 outdoor with direct line of sight. 

All setup in radio communications is done using the dip-switch located in 
the lower part of the device. Once the configuration is completed, 

TIR Two 

devices  connect  automatically  with 

Gateway  LR 

for  a  fast  and  easy 

installation. 

 

TECHNICAL CHARACTERISTICS 

 

Power circuit 
Input voltage 

110 … 264 Vac 

Frequency 

47 … 63 Hz 

Maximum consumption 

2,5 …. 4,5 VA 

Environmental conditions 
Temperature range 

-10 …. +60ºC 

Humidity range 

5 …. 95% 

Mechanical characteristics 
Enclosure material 

Plastic UL94 – V0 Self-extinguishable  

Protection grade 

IP20 

Unit dimensions (Width x Height x Length) 

18 x 70 x 109 mm 

Weight 

70 g 

Mounting 

DIN Rail (1 module) 

Maximum working altitude 

2000 m 

Radio communication 
Protocol 

LoRa

TM 

Frequency 

868 / 915 MHz configurable  

External antenna connector 

Yes 

External antenna connector type 

SMA female 

Autosync sensor-gateway 

Yes 

Temperature metering 
Probe type 

NTC/PTC 

Number of probes included 

Digital inputs characteristics 
Type 

Free voltage 

Maximum activation current 

5 mA 

Outputs characteristics 
Type 

Relay 

Nominal voltage 

250 Vac 

Electrical endurance 

3 x 10

4

 operations (5 A A.C.) 

Nominal current 
   With resistive charge 

   With inductive charge (CA) 
   With inductive charge (CC) 

 
250 Vac / 5 A A.C. 

250 Vac / 2 A A.C. 
24 Vdc / 5 A D.C. 

Characteristics and electrical security 
Security 

CAT III 300 V under EN 61010 

Electric shock protection 

Double insulation class II 

Standards 
Standards 

UNE EN 61010-1:2010, UNE-EN 61000-6-2, UNE-EN 61000-6-4

 

 