background image

PMI v507, PMI v512

Operating Manual 1003981-EN-01

}

Operator terminals

Summary of Contents for 265507

Page 1: ...PMI v507 PMI v512 Operating Manual 1003981 EN 01 Operator terminals ...

Page 2: ...cumentation will be gratefully received Source code from third party manufacturers or open source software has been used for some components The relevant licence information is available on the Internet on the Pilz homepage Pilz PIT PMI PNOZ Primo PSEN PSS PVIS SafetyBUS p SafetyEYE SafetyNET p the spirit of safety are registered and protected trademarks of Pilz GmbH Co KG in some countries SD mea...

Page 3: ...10 3 3 1 Installation site 10 3 3 2 Measures to protect against interference 11 3 3 3 Supply voltage 11 3 3 4 Operation 11 3 3 5 Maintenance 12 Section 4 Function description 13 4 1 Features 13 4 2 Side view 13 Section 5 Installation 15 5 1 Safety 15 5 1 1 Installation site and unit surroundings 15 5 2 Dimensions 16 5 3 Installing the unit 17 5 4 Installation 17 Section 6 Wiring 19 6 1 General wir...

Page 4: ... 7 2 3 Keyboard soft keyboard 24 7 2 4 Network and dial up 24 7 2 5 Regional settings 24 7 2 6 Storage Manager 25 7 2 7 System 25 7 2 8 Network servers 25 Section 8 Care and Maintenance 26 8 1 Cleaning the touchscreen 26 Section 9 Technical details 27 Section 10 Order reference 29 10 1 Product 29 ...

Page 5: ...DANGER This warning must be heeded It warns of a hazardous situation that poses an immediate threat of serious injury and death and indicates preventive measures that can be taken WARNING This warning must be heeded It warns of a hazardous situation that could lead to serious injury and death and indicates preventive measures that can be taken CAUTION This refers to a hazard that can lead to a les...

Page 6: ...Introduction Operating Manual PMI v507 PMI v512 1003981 EN 01 6 INFORMATION This gives advice on applications and provides information on special fea tures ...

Page 7: ...erate and monitor technical processes 2 1 1 Unit features Capacitive touchscreen Character set Unicode Memory 256 MB DDR SDRAM 512 MB Flash 1 serial interface 1 Ethernet interface 1 USB slave interface 2 USB host interfaces Battery buffered real time clock Pre installed software PASvisu Server PASvisu Viewer PMI PSS 4000 Firmware OPC Server ...

Page 8: ...screen see Technical details 27 2 3 Scope of supply PMI v507 Operator terminal 6 retaining clamps Connector plug for power supply Projection stand PMI v512 Operator terminal 8 retaining clamps Mounting frame for achieving protection class IP66 Connector plug for power supply Projection stand ...

Page 9: ...emed improper use in particular Any component technical or electrical modification to the product Use of the product outside the areas described in this manual Use of the product outside the technical details see Technical details 27 NOTICE EMC compliant electrical installation The product is designed for use in an industrial environment The product may cause interference if installed in other env...

Page 10: ...ds applicable to the specific application 3 2 2 Warranty and liability All claims to warranty and liability will be rendered invalid if The product was used contrary to the purpose for which it is intended Damage can be attributed to not having followed the guidelines in the manual Operating personnel are not suitably qualified Any type of modification has been made e g exchanging components on th...

Page 11: ... to the central earth point in star form A cable cross sec tion of at least 1 5 mm should be used for the connection Connections should be kept as short as possible 3 3 3 Supply voltage The supply voltage must be 24 V DC CAUTION Safe electrical isolation must be ensured for the external power supply gen erating the 24 V voltage supply Failure to do so could result in electric shock Power supplies ...

Page 12: ...MI v512 1003981 EN 01 12 3 3 5 Maintenance Do not use thinners or organic solvents to clean the unit and touchscreen surface Further information on care and maintenance of the touchscreen can be found in the chapter Care and Maintenance ...

Page 13: ...ouch screen An Ethernet interface is available for the transfer of data e g diagnostic data and for communication with other subscribers The device is fitted with a real time clock that is battery buffered so allowing it to run for 90 days without an external power supply The battery is automatically charged during normal operation by the power supply for the device 4 2 Side view 1 2 3 4 5 6 7 8 9...

Page 14: ...Function description Operating Manual PMI v507 PMI v512 1003981 EN 01 14 8 USB Host 2 9 Functional earth ...

Page 15: ...ould refer to any guidelines laid down by the plant manufacturer or operator 5 1 1 Installation site and unit surroundings Keep as large a distance as possible between the system and any electromagnetic fields particularly when frequency converters are nearby To avoid the build up of heat a distance of 10 cm 3 94 should be kept free all round the unit Protect the system from direct sunlight and du...

Page 16: ...1 mm 216 8 504 153 6 024 332 13 071 222 8 740 b2 mm h2 mm t2 mm 199 7 835 136 5 354 33 5 1 319 315 12 402 205 8 071 31 5 1 240 b3 mm h3 mm t3 mm 144 4 5 685 83 3 268 25 9 1 020 146 6 5 772 101 3 976 25 9 1 020 t1 mm 6 0 236 6 0 236 b4 mm h4 mm 200 1 7 874 0 039 137 1 5 394 0 039 316 1 12 441 0 039 206 1 8 11 0 039 h t Dimensions without connections Allow extra for hardware connections ...

Page 17: ...5 mm To avoid a build up of heat a distance of a 10 cm 3 94 should be maintained all round the system Ensure the information given for the ambient and operating temperatures in the tech nical details is observed Protection type IP65 PMI v507 IP66 PMI v512 is only guaranteed when the fixing screws are tightened as follows min 0 3 Nm max 0 5 Nm the gasket is not damaged the wall thickness is at leas...

Page 18: ...Installation Operating Manual PMI v507 PMI v512 1003981 EN 01 18 Fig Installing the PMI v512 ...

Page 19: ... Connect the power cable shield with low impedance to earth Use only shielded data lines For high frequency reasons we recommend that the shielding on the data line cable RS 232 cable is earthed on both sides If you are using longer cables and there is the possibility of transient currents we recommend one of the following methods Use equipotential bonding conductors Use electrical isolation Conne...

Page 20: ... 1 Supply voltage The connection for the 24 V DC supply is located on the side of the housing 1 2 3 Fig Layout of supply voltage connector 1 Functional earth 2 0 V 3 24 V DC UL requirement Use a 24 VDC power supply isolating source Connect a max 5 A fuse between the power supply and PMI ...

Page 21: ...or control cabinet 2 Earth bus bar 3 Supply voltage 4 Functional earthing terminal electronic 5 Functional earthing bolts housing 6 Data line shield 7 Split ferrite 0 V and are connected internally INFORMATION To reduce interference position a split ferrite on the 24 V and GND line at a distance of approx 100 mm from the PMI Loop the cable once around the ferrite core ...

Page 22: ...ing Manual PMI v507 PMI v512 1003981 EN 01 22 6 2 3 Interfaces Pin assignment of RS232 interface COM1 GND n c TxD RxD n c n c CTS RTS n c n c Not connected Fig Pin assignment of RS232 interface Sub D connector 9 pin ...

Page 23: ... being ready for operation 7 1 Activating the setup Press the SETUP button within 2 seconds to access the system settings Fig Activating setup 7 2 Control Panel All system settings can be made from the Control Panel of Windows Embedded Compact 7 Special features and device specific settings are described in the following 7 2 1 Date time Setting the date time time zone and winter summer time ...

Page 24: ...lighting 7 2 3 Keyboard soft keyboard Setting the keyboard layout German or English and setting the soft keyboard small large or no keyboard 7 2 4 Network and dial up Modify existing connections e g IP address or set new connections PPP over Ethernet 7 2 5 Regional settings Regional settings number format currency time date ...

Page 25: ... v512 1003981 EN 01 25 7 2 6 Storage Manager Format partition memory 7 2 7 System Display modify system properties relationship between program memory file management 7 2 8 Network servers Start and stop various services Telnet SMB FTP SNTP Web Server ...

Page 26: ...reen at regular intervals Use a damp cloth to do this NOTICE Make sure the unit is switched off before cleaning it This prevents you from accidentally triggering functions when you touch the touchscreen Cleaning agents Only use water and washing up liquid or window cleaner to dampen the cloth Never use aggressive solvents or abrasive cleaning agents ...

Page 27: ...ory RAM 256 MB 256 MB Program memory Flash 512 MB 512 MB Real time clock yes yes Removable data medium 265507 265512 Type SD card SD card USB interface 265507 265512 Number of USB Hosts 2 2 Number of USB Slaves 1 1 Ethernet interface 265507 265512 Number 1 1 Serial interface 265507 265512 Number of RS232 interfaces 1 1 Audio interfaces 265507 265512 Number 1 1 Environmental data 265507 265512 Ambi...

Page 28: ...1g 1g Shock stress In accordance with the standard EN 60068 2 27 EN 60068 2 27 Acceleration 15g 15g Duration 11 ms 11 ms Protection type In accordance with the standard EN 60529 EN 60529 Housing IP20 IP20 Front IP65 IP66 Mechanical data 265507 265512 Dimensions Height 153 mm 222 mm Width 216 mm 332 mm Depth 65 4 mm 63 4 mm Weight 1 390 g 2 450 g Where standards are undated the 2010 12 latest editi...

Page 29: ... 1003981 EN 01 29 10 Order reference 10 1 Product Product type Features Order No PMI v507 Operator terminal 800 x 480 pixel resolution ca pacitive touchscreen 265 507 PMI v512 Operator terminal 1280 x 800 pixel resolution capacitive touchscreen 265 512 ...

Page 30: ...T p the spirit of safety are registered and protected trademarks of Pilz GmbH Co KG in some countries We would point out that product features may vary from the details stated in this document depending on the status at the time of publication and the scope of the equipment We accept no responsibility for the validity accuracy and entirety of the text and graphics presented in this information Ple...