background image

Summary of Contents for 4300 TL

Page 1: ...V e r s i o n0 5 2 0 1 0 Ma t N o 7 3 45 5 9 A B E N I n s t a l l a t i o na n dO p e r a t i n gMa n u a l I n v e r t e r...

Page 2: ...ou for purchasing a PLATINUM Inverter 4300 TL 4800 TL 5300 TL 6300 TL 7200 TL In this instruction we have compiled all information that is important for installation and operation If you still have an...

Page 3: ...5 Mounting 9 5 1 Scope of delivery 9 5 2 Unpacking 9 5 3 Mounting the inverter 10 5 4 Connection of the inverter 15 6 Start Up 26 6 1 Initial startup of inverter 27 6 2 Phase Balancer 35 6 3 Replacin...

Page 4: ...manual PLATINUM Inverter 4300 TL 4800 TL 5300 TL 6300 TL 7200 TL Version 05 2010 Mat No 734 559 AB 12 Troubleshooting 71 12 1 Table of events 71 13 Standards and Approvals 73 14 Technical Data 74 15 E...

Page 5: ...of dangers indicated by the following signal words Caution warns of material damage Warning warns of bodily harm Danger warns of a danger to life Layout of the warning notices 1 2 Other symbols Instr...

Page 6: ...nverter 4300 TL 4800 TL 5300 TL 6300 TL 7200 TL Symbols 6 Installation and operating manual PLATINUM Inverter 4300 TL 4800 TL 5300 TL 6300 TL 7200 TL Version 05 2010 Mat No 734 559 AB 1 3 Symbols on t...

Page 7: ...cal position Ensure that all protection devices are fully operational Verify that ventilation openings are not blocked or covered Protect inverters from direct sunlight Prior to installation and maint...

Page 8: ...L PLATINUM 7200 TL Possible types with DC disconnector without DC disconnector 4 2 Options Upgrades for an inverter or an inverter system Inverter networking via EIA 485 bus Much easier and more compr...

Page 9: ...ruction Note A detailed installation and operating manual is available in the download area of our website www diehlako de 5 2 Unpacking Fig 1 Unpacking the inverter Unpack the inverter as follows 1 P...

Page 10: ...erter Have inverters installed by qualified specialists only The qualified specialist personnel requires a license from the relevant energy suppliers Danger Danger to life due to inverter dropping fro...

Page 11: ...n 05 2010 Mat No 734 559 AB PLATINUM Inverter 4300 TL 4800 TL 5300 TL 6300 TL 7200 TL Mounting Protector Fig 2 Removing protector 1 Protector Hold protector 1 on bottom side and pull away from inverte...

Page 12: ...4300 TL 4800 TL 5300 TL 6300 TL 7200 TL Mounting 12 Installation and operating manual PLATINUM Inverter 4300 TL 4800 TL 5300 TL 6300 TL 7200 TL Version 05 2010 Mat No 734 559 AB Fig 3 Protector positi...

Page 13: ...fixture 2 from the back of the inverter t Two locking screws secure the inverter in the mounting fixture t The locking screw 6 is marked by a paper strip with a lock symbol t Do not remove the paper s...

Page 14: ...mounting fixture 2 Use the outer cooling fins as guides in mounting fixture 2 Hold the inverter at molded grips 7 and push up until mounting bolts 5 drop into slotted pieces 4 on both sides Let down t...

Page 15: ...voltage Prior to connecting the inverter verify that voltage is applied to the generator side DC terminal Prior to connecting the inverter verify that the DC voltage polarity is correct Wear insulati...

Page 16: ...re that wire cross sections and fuses conform to VDE 100 Part 430 Ensure that any network cables between two inverters are not longer than 30 m For DC cables use a wire cross section of at least 2 5 m...

Page 17: ...L 7200 TL Version 05 2010 Mat No 734 559 AB PLATINUM Inverter 4300 TL 4800 TL 5300 TL 6300 TL 7200 TL Mounting Terminal side Fig 6 Terminal side inverter 1 Switch knob DC disconnector optional 2 DC te...

Page 18: ...he nominal AC power exceeds the admissible value In this case it is necessary to divide the nominal AC power to at least two inverters with less power and to at least two phases Caution Destruction of...

Page 19: ...5300 TL 6300 TL 7200 TL Mounting Fig 7 Cover of AC voltage connection 1 Screws 2 Cover of AC voltage connection area 3 Tray for screws Establish AC voltage connection as follows Open cover of AC volt...

Page 20: ...onnect the cables Use lines matching the type dependent AC Fuse lines accordingly Stick screwdrive in release opening 6 and press release Push cable into cable input 7 as far as it will go Ensure that...

Page 21: ...e with a DC plug connector If more than one strand is connected ensure that the number and type of solar modules and the PV power are identical for every strand Put protective caps on unused plug conn...

Page 22: ...allocated 5 Input max 12 V option 6 Supply voltage for ext consumer 12 V max 300 mW 7 Supply voltage for ext consumer 0 V 8 Shielding EIA485 RS485 9 Line A of EIA485 bus line 10 Line B of EIA485 bus l...

Page 23: ...85 bus line Establish connection to network as follows Establish connection between inverters or inverters and monitoring devices on serial interface EIA485 using a cable with RJ45 plugs or cable on t...

Page 24: ...st inverter in PLATINUM network Plug termination plug into slot for network connection 1 Alarm contact Connect any external indicator device to the potential free relay contact t When an error is dete...

Page 25: ...Mat No 734 559 AB PLATINUM Inverter 4300 TL 4800 TL 5300 TL 6300 TL 7200 TL Mounting Mounting protector Fig 13 Mounting protector 1 upper fixture 2 Protector 3 lower fixture Put upper part of protect...

Page 26: ...A 485 interface the startup can be carried out at any one of the installed inverters master programming This inverter transmits the configuration settings to all other inverters in the network Every i...

Page 27: ...fuse For inverters with DC disconnector Set switch knob to 1 The inverter is supplied with power Configuration through the following dialogs Initial startup Caution Lack of function due to missing se...

Page 28: ...us for other inverters all inverters connected to the network are blocked EIA485 bus As long as the network scan Scanning Network is still in process the display shows the following screen When the ne...

Page 29: ...reen Inverter numbering appears Note If one or several inverters have been replaced or not all inverters are numbered correctly this can be corrected see 6 3 Replacing devices Inverter numbering It is...

Page 30: ...een is not displayed if only one inverter is configured After OK was selected Allocate numbers to inverters in the required sequence t The inverter adopts the next available number t The display shows...

Page 31: ...34 559 AB PLATINUM Inverter 4300 TL 4800 TL 5300 TL 6300 TL 7200 TL Start Up Note The following screen is not displayed if only one inverter is started up Entry only at one inverter All inverters conn...

Page 32: ...t automatically in dependence on the selected country Note The setting can be changed within 4 hours after the setting and the start of the feeding into the mains supply Without feeding the period is...

Page 33: ...nd a network is established the inverter will show the number of configured inverters and the type of configuration Note If an inverter is replaced only the country code of the replaced inverter can b...

Page 34: ...ved data or cause gaps in data recording To accept time setting Select SELECT Press OK key The inverter automatically shares the new time setting with all network participants To reset time Select BAC...

Page 35: ...ble to set the admissible maximum power unbalanced load and the reaction time according to the specifications of the power plant operator see 8 1 Service Men 6 3 Replacing devices If one or more PLATI...

Page 36: ...nverters show the following screen On every replaced inverter Select desired device number Press OK key Inverter does another network scan The inverter automatically transmits the device numbers to al...

Page 37: ...manual PLATINUM Inverter 4300 TL 4800 TL 5300 TL 6300 TL 7200 TL Version 05 2010 Mat No 734 559 AB PLATINUM Inverter 4300 TL 4800 TL 5300 TL 6300 TL 7200 TL Start Up Reassign numbers Renumbering see 6...

Page 38: ...of the inverter indicates whether a DC disconnector is available The DC disconnector enables switching on and off the solar generator To engage the solar generator Set DC disconnector to 1 To switch o...

Page 39: ...TL 6300 TL 7200 TL Operation 7 2 Display and operation Note If there is no input for approx 2 minutes inverter switches to standard display during feed Fig 15 Display and operation 1 Time 2 LED red 3...

Page 40: ...blinking indicate that the inverter is performing a network scan Scroll arrows The menu contains other menu items Navigate using keys T and S or W and X Title Title of the selected menu Date Date dis...

Page 41: ...ation Device number Displays the inverter number Day Displays the day of the week 7 3 Standard screen Arrow to the right of the table designation of physical value displayed in graphic Number in the t...

Page 42: ...n Display The operation display shows a list of physical values and a corresponding evaluation graph Type and value of the displayed physical value depend on the selected period The illustration below...

Page 43: ...ed power for the indicated period EUR rebate for the indicated period Adjustable in menu Settings kg quantity of saved carbon dioxide CO2 Number in the top left corner of the graphic maximum value of...

Page 44: ...as columns in the periods WEEK MONTH and YEAR Rebate in country specific currency t Values 999 000 are displayed as a factor t Example 1 234 567 is displayed as 1 234E6 CO2 emission reduction in kg o...

Page 45: ...of physical value Day in hours 0 24 Week one column per day Mo Su Month one column per day Year one column per month Jan Dec Note Type and value of the displayed physical value depend on the selected...

Page 46: ...ttings the following settings are possible Time settings Language Alarm volume Alarm contact function LCD Rebate System Energy meter Time settings In the menu Time settings the following settings are...

Page 47: ...time can result in overwriting saved data or cause gaps in data recording To accept time setting Select SELECT Press OK key The inverter automatically shares the new time setting with all network par...

Page 48: ...accept time setting Select CANCEL Press OK key Date format Daylight saving time MANUALLY Manual setting of daylight saving time required AUTOMATIC Inverter sets daylight saving time automatically depe...

Page 49: ...the following screen will appear the next time the date or time is set To set daylight saving time Select YES Press OK key Inverter adds 1 hour to set time To not set daylight saving time Select NO Pr...

Page 50: ...g to all network participants Alarmkontakt OFF The alarm contact NO contact is constantly open if a safety relevant or blocking error occurs Alarmkontakt ist deaktiviert INTERVAL The alarm contact NO...

Page 51: ...closed until the error is remedied TEST Close alarm contact temporarily while selecting a menu item LCD Feed payback Key Function ST Increase or reduce contrast or brightness WX Navigate between inpu...

Page 52: ...meter The energy meter enables the metering of energy and operating hours since the start of the inverter or since a reset of the energy meter Key Function ST Increment or decrement present digit WX N...

Page 53: ...erating data System data Inverter type Inverter version Event information Note The menu Information merely displays the value It is not possible to change the values Operating data GENERAL Shows feed...

Page 54: ...ata NAME Shows the name of the PV system NUMBER OF PARTICIPANTS Indicates number of network participants e g inverter and monitoring devices such as PLATINUM PV Monitor PLATINUM ViewMaster and PLATINU...

Page 55: ...Operation Inverter type TYPE Indicates inverter type S N Indicates inverter serial number Note When contacting the PLATINUM service have the serial number ready After changing the inverter network par...

Page 56: ...0 TL Version 05 2010 Mat No 734 559 AB Inverter version FIRMWARE Shows the inverter software version HARDWARE Shows the inverter hardware version EIA485 Shows the data bus software version BL Shows ve...

Page 57: ...ys are meant for the user Any detected errors are displayed with a slight delay In case of an error the inverter displays the error type and error code Error causes and measures see 12 Troubleshooting...

Page 58: ...r closes the alarm contact Setting see screen Settings t function Alarm contact Exclusively service personnel can remedy the blocking error and switch the inverter back on To stop the acoustic alarm P...

Page 59: ...blocking errors are of a transient nature e g mains voltage surge The inverter remains switched off until the error cause no longer persists When the error has been remedied the inverter automaticall...

Page 60: ...d functions display event list display parameters set max unbalanced load Phase balancer reconfiguration display startup date display feed meter Note To display other parameters or to change the param...

Page 61: ...7200 TL Service Event list Columns 1 column Event no 2 column Event date 3 column Event time 4 column Event code Note The inverter shows the last 100 detected events Explanations about the events see...

Page 62: ...ency may differ temporarily or permanently from the factory settings It is possible to adapt the PLATINUM inverter to these values Contact the PLATINUM service for more information The screens Paramet...

Page 63: ...rating mode OFF Switch off Phase Balancer function No limit of unbalanced load POWER CONTROL Switch on Phase Balancer function The inverter monitors and limits the difference between AC powers ERROR O...

Page 64: ...um power unbalanced load Range of values 200 W to 9 999 W Factory setting 5 000 W Reaction time Range of values 10 s to 9 999 s Factory setting 300 s Key Function ST Increment or decrement present dig...

Page 65: ...twork after the reaction time has been confirmed During the transfer the inverter shows the following screen After a successful transfer the inverter shows the following screen Note If an inverter s f...

Page 66: ...only a display Values cannot be changed Meter The menu is only a display Values cannot be changed Inverter numbering To change the inverter numbering after startup Select Reconfiguration in the Servi...

Page 67: ...DC and AC high voltage Wear insulating protective clothing and face protection Have any cleaning or maintenance works carried out exclusively by trained personnel The qualified specialist personnel re...

Page 68: ...insulating protective clothing and face protection Have inverters uninstalled by qualified specialists only The qualified specialist personnel requires a license from the relevant energy suppliers Sw...

Page 69: ...f input voltage DC side Disconnect remaining connectors as required Dismount the inverter as follows Loosen and remove the locking screws paper strip Lift the inverter up and out of the mounting fixtu...

Page 70: ...TL 5300 TL 6300 TL 7200 TL Version 05 2010 Mat No 734 559 AB Packaging Pack inverter as follows Fig 16 Packing of inverter 1 Rest the inverter on the inner packaging 2 Put the inverter with the inner...

Page 71: ...aging and consumed parts according to the rules and regulations applicable in the country where the device was installed Do not dispose of the PLATINUM inverter in the household waste No Operating sta...

Page 72: ...1 Amplitude limit for feed phase exceeded or fallen below Have voltage amplitude of feed phase checked 202 to 204 exclusively for 3 phase ENS Amplitude limit of phase voltages exceeded or fallen below...

Page 73: ...rter from mains Restart inverter If measure is not successful Call Service 234 to 289 Diagnosis support during service Provide the service with the error code if required 290 Subsequent error in case...

Page 74: ...put characteristics Max AC power 4 120 W 4 600 W 5 000 W 6 000 W 6 900 W Nominal AC power rating 3 750 W 4 200 W 4 600 W 5 500 W 6 300 W Nominal AC current 16 3 A 18 3 A 20 0 A 23 9 A 27 4 A Max AC cu...

Page 75: ...ation at nominal power output 45 C Storage temperature 20 C to 80 C Max air humidity 95 Protection Type except digital interface IP 66 according to DIN EN 60529 Dimensions H 720 mm x W 320 mm x D 250...

Page 76: ...6 65 EG and the EMC directive 2004 108 EG The designated devices conform to the following norms DIN EN 50178 1998 04 DIN EN 61 000 3 2 2006 10 DIN EN 61 000 3 12 2005 09 DIN EN 61 000 3 3 1994 A2 2005...

Page 77: ...re the actual users of a Warranted Product Warranted User Traders of any kind and trade level do not gain from this manufacturer s warranty any rights and claims against Diehl AKO 3 Establishment of t...

Page 78: ...r free of charge repairs or free of charge replacement of the Warranted Products with a product that offers at least the same or the same type of functionality and performance Such repairs or replacem...

Page 79: ...e 8 Portability of the guarantee This agreement on guarantee and the rights that result from it can only be transferred from a licencee to a third party with a previous written approval When the guara...

Page 80: ...7200 TL Version 05 2010 Mat No 734 559 AB This manufacturer s warranty is subject only to the laws of the Federal Republic of Germany excluding the stipulations of Private International Law and the U...

Page 81: ......

Page 82: ...rstra e 75 88239 Wangen im Allg u Deutschland Tel 49 7522 73 700 Fax 49 7522 73 710 platinum diehl controls com www diehl com photovoltaics PLATINUM Service Tel 49 7522 73 777 Fax 49 7522 73 737 servi...

Reviews: