POLON 4000 

INTERACTIVE FIRE DETECTION AND ALARM SYSTEM

 

 
 
 
 

ADC-4001M 

ADAPTER 

 

 

Installation and maintenance manual 

 
 

IK-E323-001E 

 

 

Edition IA 

 

 

 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for ADC-4001M

Page 1: ...1 IK E283 001E POLON 4000 INTERACTIVE FIRE DETECTION AND ALARM SYSTEM ADC 4001M ADAPTER Installation and maintenance manual IK E323 001E Edition IA ...

Page 2: ...Spółka z ograniczoną odpowiedzialnością Sp k Glinki 155 Street PL 85 861 Bydgoszcz 05 1438 CPD 0069 EN 54 18 ADC 4001M adapter Addressable alarm signal input element detachable Technical data IK E323 001 manual Read the manual carefully before the detector assembling and commissioning Any nonconformity with the instructions contained in the manual may be harmful or may cause violation of the law i...

Page 3: ... evokes a fire alarm at the control panel The adapter is equipped with a short circuit isolator The ADC 4001M adapter is intended for wall or ceiling mounting using the G 40 base 2 TECHNICAL SPECIFICATIONS Operation voltage from detection loop 16 5 V 24 6 V Current drawn from detection loop from 0 5 mA to 16 mA depending on operation mode Maximum branch line resistance 2 x 25 Ω Operation temperatu...

Page 4: ... stage detectors installed in its branch line All line elements installed in the branch line possess a common address determined by the adapter A fire signal induced by a detector installed in the branch line is transmitted via the adapter to the control panel whereas it is signalled in the adapter with a red flashing diode light A branch line fault short circuit or breakage is also transmitted to...

Page 5: ...de intended exclusively for DOP 40 beam smoke detector connection without an end of line resistor the detector jumper set in ADC 1 position Mode 6 mode provided especially for interoperation with 40 model range detectors of low voltage power supply It enables installation of up to 5 40 model range detectors manufactured after June 15th 2002 date stated in a warranty certificate Detailed informatio...

Page 6: ...ntrinsically safe smoke detector or up to 10 pcs intrinsically safe manual call points equipped with a 1 kΩ alarm resistor system limitation NOTE A branch line short circuit behind an intrinsically safe separator is signalled as a fire alarm A line short circuit between a separator and an adapter is signalled as a fault The separator should be installed in a safe zone directly behind an endangered...

Page 7: ...hould be squeezed with fingers then the connector should be placed between the guides in the base rectangular hollow 8 SERVICING AND MAINTENANCE The ADC 4001M adapter unfailing operation depends on ensuring proper operation conditions appropriate assembly execution and systematic periodical inspection The periodical checks should be carried out at least yearly by a person who knows the device oper...

Page 8: ...8 IK E283 001E Fig 2 ADC 4001M adapter exemplary connection into addressable detection line with exemplary adapter branch line connection IK E323 001E 05 2009 01 2012 ...