background image

 

 

 

 

POLON

 

4000

 

INTERACTIVE

 

FIRE

 

DETECTION

 

AND

 

ALARM

 

SYSTEM

 

 

DOT

4046

 

MULTI

SENSOR

  

SMOKE

 

AND

 

HEAT

 

DETECTOR

 

 

 

Installation

 

and

 

Maintenance

 

Manual

 

IK

E301

001GB

 

 

IIIB

 

Edition

 

Summary of Contents for DOT?4046

Page 1: ...POLON 4000 INTERACTIVE FIRE DETECTION AND ALARM SYSTEM DOT 4046 MULTI SENSOR SMOKE AND HEAT DETECTOR Installation and Maintenance Manual IK E301 001GB IIIB Edition ...

Page 2: ...fa pl web site 1438 Polon Alfa Spółka z ograniczoną odpowiedzialnością Sp k 155 Glinki Street PL 85 861 Bydgoszcz POLAND 05 1438 CPD 0015 EN 54 7 DOT 4046 Multi sensor Smoke and Heat Detector utilising scattered light effect and heat sensor addressable detachable Application fire safety Technical data IK E301 001GB manual Read the manual carefully before the detector assembling and commissioning A...

Page 3: ... modes from 25 C to 65 C Allowable relative humidity up to 95 at 40 C Dimensions without base Ø 115 mm x 43 mm Number of basic operation modes 4 Mass without base 0 2 kg Standard colour white Address coding method programmable at the control panel Test fire detection suitability TF1 TF2 TF3 TF4 TF5 TF6 TF8 see design guidelines 3 SAFETY CONDITIONS 3 1 Repairs and maintenance Any maintenance works ...

Page 4: ...ire alarm control panel and the DOT 4046 detectors is provided through a two wire addressable detection line A unique fully digital communications protocol enables passing any information from the control panel to the detector and inversely e g evaluation of surrounding conditions smokiness temperature tendency of its change as well as current temperature analogue value and smokiness density The d...

Page 5: ... only a smoke detector DOR operates 6 mode in which only a heat detector TUP in class A1R operates 7 mode in which only a heat detector TUP in class BR operates 7 OPERATION AND SERVICING CONDITIONS During the detectors operation it is obligatory to avoid creation of dew or rime on the detector surface as well as to protect against excessive contamination with dust For the period of repair works th...

Page 6: ...smantling is shown on Fig 1 In order to dismantle the detector it is necessary to a pressing the net long tongue turn the cover right in the basket until it is taken out b remove and bend aside the thermistor basis from the labyrinth c unfasten two screws that fix the labyrinth and take the labyrinth out d perform the necessary cleaning A delicate brush as well as vacuum cleaner are recommended fo...

Page 7: ... see the POLON 4000 system control panels Installation and Maintenance Manuals The detectors are installed in the 40 model range bases The detection line connection is presented in the G 40 base Installation and Maintenance Manual An additional optical alarm signal of a detector or a group of detectors can be obtained by connecting the WZ 31 alarm indicator Alarm system cables are routed in accord...

Page 8: ...8 IK E301 001GB Fig 2 Clamps of base interoperating with DOT 4046 plug IK E301 001GB 05 2011 01 2012 ...