background image

 

Summary of Contents for Centurion RT PSLCERT1000

Page 1: ......

Page 2: ...e frequency variation switching transients and harmonic distortions The Centurion RT s Lithium Iron Phosphate LiFePO4 or more simply LiFe true online double conversion topology will continuously protect your equipment by internally isolating your equipment from the utility power ensuring that all your equipment always receives clean uninterrupted and stable power Very Important WARRANTY REGISTRATI...

Page 3: ...ould be observed CAUTION REFER TO OPERATOR S MANUAL Refer to your operator s manual for additional information such as important operating and maintenance procedures SAFETY EARTHING TERMINAL Indicates the primary safety ground This symbol indicates that you should not discard the UPS or the UPS batteries in the trash The UPS may contain Lithium Iron Phosphate LiFePO4 or more simply LiFe batteries ...

Page 4: ...panel view 7 2 2 Operating principle 8 2 3 Installing the UPS 8 2 4 Setting up the UPS 9 3 Operations 12 3 1 Button operation 12 3 2 LCD Panel 13 3 3 Audible Alarm 14 3 4 LCD display wordings index 14 3 5 UPS Parameter Settings 15 3 6 Operating Mode Description 18 3 7 Faults Reference Code 19 3 8 Warning indicator 20 4 Troubleshooting 21 5 Storage and Maintenance 22 5 1 Operation 22 5 2 Storage 22...

Page 5: ... install the UPS system near water or in moist environments Do not install the UPS system where it would be exposed to direct sunlight or near heaters Do not block ventilation holes in the UPS housing 1 3 Installation Do not connect appliances or devices which would overload the UPS system e g laser printers to the UPS output sockets To ensure against physical hazards place cables safely such that...

Page 6: ...ins power then disconnect the batteries and verify that no hazardous voltages are present at the terminals of the large storage capacitors BUS capacitors Only persons who are adequately familiar with high capacity batteries and with the understanding of the required precautionary measures outlined below are permitted to replace batteries and supervise operations Unauthorized persons must be kept w...

Page 7: ...nel shall be stated in the installation service handbook c If batteries are to be installed by Service Personnel instructions for interconnections including terminal torque shall be provided Do not attempt to dispose of batteries by burning as they may explode Do not open or destroy batteries Escaping electrolyte can cause injury to the skin and eyes It may be toxic Replacement fuses must be of th...

Page 8: ...els support internal LiFePO4 batteries Please refer to the following model table Model No Type PSLCERT1000 Standard LiFePO4 Model with internal LiFePO4 batteries PSLCERT2000 PSLCERT3000 2 1 Rear panel view PSLCERT1000 PSLCERT2000 PSLCERT3000 1 Programmable outlets connect to non critical loads 2 Output receptacles connect to mission critical loads 3 AC input 4 USB communication port 5 RS 232 commu...

Page 9: ...ss and UPS output 2 3 Installing the UPS The UPS is usually shipped from the factory with the battery wires connected Note LCD and alarm will indicate if battery wires are not connected at the start of the power up sequence If not connected please follow the steps below to re connect the battery wires Step 1 Step 2 Step 3 Remove front panel Re connect DC battery wires and connect the AC input Put ...

Page 10: ...void dust and high temperature 2 Maintain an ambient temperature range of 0ºC to 45ºC for UPS optimal operation For every 5ºC above 45ºC the UPS will de rate 12 of nominal capacity at full load The highest permissible working temperature for UPS operation is 50ºC 3 There is a service ceiling limit with a maximum altitude of 1000m for the UPS to operate at full load If the UPS is to be used at high...

Page 11: ...ation port USB port RS 232 port Intelligent slot To allow for unattended UPS shutdown start up and status monitoring connect the communication cable on one end to the USB or RS 232 port of the UPS and the other to the USB or RS232 communication port of your PC With the monitoring software installed you can schedule UPS shutdown start up and monitor UPS status through the PC The UPS is equipped wit...

Page 12: ...tion install the UPS monitoring software to fully configure UPS shutdown Follow the steps below to download and install NetGuard monitoring software 1 Go to the website www powershield com au 2 Click Downloads software icon and choose your required OS to download the NetGuard software in the https powershield com au downloads downloads page 3 Follow the on screen instructions to install the NetGua...

Page 13: ...Confirm selection key Press this button to confirm selection in UPS setting mode Select Button Switch LCD message Press this button to change the LCD message for input voltage input frequency input current battery voltage battery current battery capacity ambient temperature output voltage output frequency load current and load percent Setting mode Press and hold this button for 3 seconds to enter ...

Page 14: ...uency input ampere battery voltage battery ampere battery capacity and ambient temperature k kilo W watt V voltage A ampere percent centigrade degree Hz frequency AC alternating current DC direct current Indicate the output voltage output frequency output ampere load current and load percentage k kilo W watt V voltage A ampere percent Hz frequency AC alternating current Load information Indicates ...

Page 15: ...ing every second Overload 2 short beeps every 2 seconds Fault Continuously sounding Bypass Mode Sounding every 10 seconds 3 4 LCD display wordings index Abbreviation Display content Meaning ENA Enable DIS Disable ESC Escape HLS High loss LLS Low loss AO Active open AC Active close EAT Estimated autonomy time RAT Running autonomy time SD Shutdown OK OK ON ON BL Battery Low OL Over Load OI Over inpu...

Page 16: ...200Vac 208 presents output voltage is 208Vac 220 presents output voltage is 220Vac 230 presents output voltage is 230Vac 240 presents output voltage is 240Vac Default 02 Frequency Converter enable disable Interface Setting Parameter 2 Enable or disable converter mode You may choose the following two options CF ENA converter mode enable CF DIS converter mode disable Default 03 Output frequency sett...

Page 17: ...220 230 240 VAC models the setting range in parameter 3 is from 7V to 24V of the nominal voltage Default 12V 06 Bypass enable disable when UPS is off Interface Setting Parameter 2 Enable or disable Bypass function You may choose the following two options ENA Bypass enable DIS Bypass disable Default 07 Bypass voltage range setting Interface Setting Parameter 2 Set the acceptable high voltage point ...

Page 18: ...e frequency low loss point from 55Hz to 59Hz Default 57 0Hz 09 Programmable outlets enable disable Interface Setting Parameter 2 Enable or disable programmable outlets ENA Programmable outlets enable DIS Programmable outlets disable Default 10 Programmable outlets setting Interface Setting Parameter 2 Set up backup time limits for programmable outlets 0 999 setting the backup time limits in minute...

Page 19: ...me Default setting Aut LCD display backlight will turn off after 60 seconds if no buttons are pressed 00 Exit setting Interface Setting Exit the setting mode 3 6 Operating Mode Description Operating mode Description LCD display Online mode When the input voltage is within acceptable range UPS will provide pure and stable AC power to output The UPS will also charge the battery at online mode ECO mo...

Page 20: ...overload UPS will enter bypass mode or bypass mode can be set by front panel Alarm is sounding every 10 seconds Standby mode UPS is powered off and no output supply power but still can charge batteries Fault mode When a fault has occurred the ERROR icon and the fault code will be displayed 3 7 Faults Reference Code Fault event Fault code Icon Fault event Fault code Icon Bus start fail 01 x Battery...

Page 21: ... EPO enable 2 short beeps every 2 seconds Over temperature Continuously sounding Charger failure Continuously sounding Battery fault Continuously sounding At this time UPS is off to remind users something wrong with battery Out of bypass voltage range 2 short beeps every 2 seconds Bypass frequency unstable 2 short beeps every 2 seconds Battery replacement 2 short beeps every 2 seconds EEPROM error...

Page 22: ...ected Check if all batteries are connected well Fault code is shown as 27 on LCD display and alarm is continuously sounding Battery voltage is too high or the charger is fault Contact your dealer Fault code is shown as 28 on LCD display and alarm is continuously sounding Battery voltage is too low or the charger is fault Contact your dealer The icons and and the warning code flash on LCD display A...

Page 23: ... 2A on LCD display and alarm is continuously sounding The short circuit occurs on the charger output Check if battery wiring of connected external pack is in short circuit status Fault code is shown as 45 on LCD display At the same time alarm is continuously sounding The charger does not have output and battery voltage is less than 10V PC Contact your dealer 5 Storage and Maintenance 5 1 Operation...

Page 24: ...23 www powershield com au 6 Specifications ...

Page 25: ...on charge will apply as above 11 For hardwired products larger than 3KVA the warranty covers onsite repair for metro areas in capital cities only For equipment installed in remote locations Power Shield may at its sole discretion request that the product be returned to a Power Shield service centre at the customer s cost 12 Power Shield UPS products are not failsafe devices Although well designed ...

Reviews: