background image

powerware

®

Prestige Series

6000 VA

Installation and Operator’s Manual for IBM Applications

Summary of Contents for Prestige 6000

Page 1: ...powerware Prestige Series 6000 VA Installation and Operator s Manual for IBM Applications ...

Page 2: ...h the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense ICES 003 This Class A Interference Causing Equipment meets all requirements of the Canadian Interference Causing Equipment Regulations ICES 003...

Page 3: ... you are connecting the UPS to an AS 400 the QUPSDLYTIM system value for the UPS Monitoring feature should be set See UPS Monitoring on page 50 for instructions 2 3 PowerPass Distribution Model Number Desired Output Voltage Voltage Selector Position 208 ___ 120 208V 208 100 200V 200 240 110 220V 220 240 ___ 115 230V 230 120 240V 240 ...

Page 4: ...Quick Install 6 7 8 9 ...

Page 5: ...Quick Install 10 For the AS 400 interface plug the AS 400 communications cable into the serial port on the UPS rear panel Plug the other end of the cable into the J14 connector on your AS 400 11 ...

Page 6: ...Quick Install This page intentionally left blank ...

Page 7: ...PowerPass Distribution Module Installation 32 UPS with PPDM Startup 39 REPO Installation 41 Troubleshooting Tips 43 4 UPS Operation 45 UPS Front Panel 45 Operating Modes 46 Normal Mode 46 Bypass Mode 47 Battery Mode 47 Diagnostics 48 Battery Test on Demand 48 Battery Start 48 UPS Shutdown 49 Changing the Output Voltage 49 UPS Monitoring 50 Using the PPDM 51 Disconnecting the UPS 51 Reconnecting th...

Page 8: ...ecifications 65 Physical Specifications 66 Technical Specifications 66 PPDM Outlets and Input and Output Cords 67 Electrical Specifications for the Prestige 6000 with PPDM 67 Part Numbers 68 Base Equipment 68 Standard Accessories 68 Optional Accessories 68 Manuals 69 7 Troubleshooting 71 Resetting the UPS 73 Silencing the Alarm 73 8 Service and Support 75 AS 400 9910 UPS Service and Support 75 S 3...

Page 9: ...ions equipment while protecting it from the frequent irregularities that are inherent in commercially available power Voltage spikes power surges brownouts and power failures have the potential to corrupt critical data destroy unsaved work sessions and in some instances damage expensive hardware With the Prestige 6000 you can safely eliminate the effects of electrical line disturbances and guard t...

Page 10: ... determine the total load requirements 1 Obtain the load ratings from either the nameplate or operator s manual of the equipment to be protected by the UPS The ratings are listed in either watts W amperes or amperes max A or volt amperes 2 If the rating is in watts multiply by 1 4 to obtain the VA requirement this is the typical relationship between watts and volt ampere ratings in most computing ...

Page 11: ...S X 1 4 1260 VA 3 x 2 AMPS x 240V 1440 VA 50 VA 1260 VA 1440 VA 50 VA 2750 VA Total Load Requirements 300 WATTS EACH 2 AMPS EACH 50 VA Figure 2 Volt Amperes Calculation Example If the total load requirements of the equipment exceeds the capacity of the UPS you must either reduce the number of pieces of equipment or use a UPS with a larger load capacity When deciding on which pieces of equipment to...

Page 12: ...10 EP8 Figure 3 Determining Approximate Battery Time 1 See Load Requirements on page 2 for assistance in determining the total load requirements for your UPS Round this number up to the next Load VA entry in the Prestige 6000 with PPDM table on page 5 and enter the number in Figure 3 2 In Figure 3 enter the number of battery cabinets that you have installed Find the intersection point of the appro...

Page 13: ...tige 6000 with PPDM Load VA Load W Approximate Battery Time in Minutes Load VA at 0 67 PF Load W 2 Cabinets 3 Cabinets 4 Cabinets 5 Cabinets 6 Cabinets 1500 1000 42 67 93 123 160 3000 2000 18 33 44 57 74 4500 3000 10 18 27 34 44 6000 4000 8 14 19 26 31 Typical Power Factor PF NOTE For AS 400 usage see Base Equipment on page 68 ...

Page 14: ...dicates that a risk of electric shock is present and the associated warning should be observed CAUTION REFER TO OPERATOR S MANUAL Refer to your operator s manual for additional information INPUT BREAKER Indicates the input breaker which shuts off utility power to the PPU BATTERY BREAKER Indicates the battery breaker which shuts off battery power power transmission through the battery cord BATTERY ...

Page 15: ...e voltage even when the UPS is not connected to an AC supply Never dispose of batteries in a fire Batteries may explode when exposed to flame Never open or mutilate batteries Released electrolyte is harmful to the skin and eyes and may be extremely toxic To reduce the risk of fire or electric shock install this UPS in a temperature and humidity controlled indoor environment free of conductive cont...

Page 16: ...VARSEL Batterier kan udgøre en fare for elektrisk stød eller forbrændinger forårsaget af høj kortslutningsspænding De korrekte forholdsregler bør overholdes Korrekt bortskaffelse af batterier er påkrævet Overhold gældende lokale regler for bortskaffelsesprocedurer Denne UPS indeholder egen energiforsyning batterier Udgangsnetstikkene kan lede strøm selv når UPS en ikke er tilsat en AC energikilde ...

Page 17: ...stemer med direkte forbundne udgange skal afbryderkontakter tilAC kredsløbet med passende mærkeeffekt kommeandetsteds fra Belangrijke Veiligheidsinstructies BELANGRIJKE VEILIGHEIDSINSTRUCTIES BEWAAR DEZE INSTRUCTIES DEZE HANDLEIDING BEVAT BELANGRIJKE VEILIGHEIDSINSTRUCTIES GEVAAR Deze UPS bevat LEVENSGEVAARLIJKE ELEKTRISCHE SPANNING Alle reparaties en onderhoud dienen UITSLUITEND DOOR ERKEND SERVI...

Page 18: ...hebben De hoofdvoedingcontactdoos moet zich op minder dan 2 meter van de apparatuur bevinden en makkelijk bereikbaar zijn voor de gebruiker De aan uit schakelaar op de UPS biedt geen elektrische isolatie voor de inwendige onderdelen De stekker uit de voedingcontactdoos halen wanneer het apparaat voor lange tijd niet wordt gebruikt Neem er nota van dat de uitgangaansluit punten op de UPS altijd ond...

Page 19: ... Paljastunut elektrolyytti on vahingollinen iholle ja silmille ja voi olla erittäin myrkyllistä Vähentääksesi tulipalon ja sähköiskun vaaraa asenna tämä UPS sisätiloihin joissa lämpötila ja kosteus on säädettävissä ja joissa ei ole virtaa johtavia epäpuhtauksia Ympäristön lämpötila ei saa ylittää 40 C Älä käytä lähellä vettä ja vältä kosteita tiloja 95 maksimi Älä poista tai irrota sisääntulojohto...

Page 20: ... Prendre les précautions nécessaires Une mise au rebut réglementaire des batteries est obligatoire Consulter les règlements en vigueur dans votre localité Cet onduleur renferme sa propre source d énergie batteries Les prises de sortie peuvent être sous tension même lorsque l onduleur n est pas branché sur le secteur Ne jamais jeter les batteries au feu L exposition aux flammes risque de les faire ...

Page 21: ... surintensités des circuits de sortie de courant alternatif est à se procurer auprès d un autre fournisseur Pour les systèmes de bypass dotés de sortie à bornier les interrupteurs adaptés au circuit de courant alternatif sont à se procurer auprès d un autre fournisseur Sicherheitswarnungen WICHTIGE SICHERHEITSANWEISUNGENANLEITUNGEN AUFBEWAHREN DIESES HANDBUCH ENTHÄLT WICHTIGE SICHERHEITSANWEISUNGE...

Page 22: ... den daran angeschlossenen Geräten entfernt wird Die Netzsteckdose die zur Hauptversorgung verwendet wird darf sich nicht weiter als 2 Meter vom Gerät weg befinden und muß für den Bediener erreichbar sein Der Ein Aus Schalter der USV bietet keine elektrische Isolation der internen Teile Wenn das Gerät längere Zeit nicht benutzt wird sollte es von der Netzsteckdose abgezogen werden Beachten daß die...

Page 23: ...åéò äéÜèåóÞò ôïõò Ôï óõãêåêñéìÝíï UPS ðåñéÝ åé ôç äéêÞ ôïõ ðçãÞ åíÝñãåéáò óõóóùñåõôÝò ÏéñåõìáôïäüôåòåîüäïõìðïñåßíáÝ ïõí åíåñãüôÜóç áêüìç êáé üôáí ôï UPS äåí åßíáé óõíäåäåìÝíï óå ðçãÞ åíáëëáóóüìåíïõ ñåýìáôïò AC ÐïôÝ ìçí ðåôÜôå ôïõò óõóóùñåõôÝò óôç öùôéÜ ãéáôß ìðïñåß íá åêñáãïýí ÐïôÝ ìçí áíïßãåôå Þ êáôáóôñÝöåôå ôïõò óõóóùñåõôÝò Ï çëåêôñïëýôçòðïõèááðåëåõèåñùèåßìðïñåßíáðñïêáëÝóåéâëÜâçóôï äÝñìá êáé ôá ...

Page 24: ...äéùìÝíåò åîüäïõò ç ðñïóôáóßá áðü ôçí õðåñÝíôáóç ãéá ôï êýêëùìá ôá êõêëþìáôá åîüäïõ AC ðñÝðåé íá ðáñÝ åôáé áðü ôñßôïõò Óôá óõóôÞìáôá ÐáñÜêáìøçò ìå êáëùäéùìÝíåò åîüäïõò ïé äéáêüðôåò áðïóýíäåóçò ðïõ åßíáé êáôÜëëçëïé ãéá ôï êýêëùìá êõêëþìáôá åîüäïõ AC ðñÝðåé íá ðáñÝ ïíôáé áðü ôñßôïõò Avvisi di sicurezza IMPORTANTI ISTRUZIONI DI SICUREZZA CONSERVARE QUESTE ISTRUZIONI QUESTO MANUALE CONTIENE IMPORTANTI ...

Page 25: ... il collegamento a terra di sicurezza del gruppo statico di continuità e dell apparecchiatura ad esso collegata la presa di alimentazione principale non deve trovarsi a oltre 2 metri dall apparecchiatura e deve essere accessibile all operatore L interruttore on off del gruppo statico di continuità non isola elettricamente i componenti interni Scollegare l unità dalla presa di alimentazione quando ...

Page 26: ...riske støt bør denne UPS en installeres i et innendørs miljø med kontrollert temperatur og luftfuktighet som er fritt for ledende forurensende stoffer Romtemperaturen må ikke overskride 40 C Den må ikke brukes i nærheten av vann eller ved meget høy luftfuktighet 95 maks Strømforsyningskabelen må ikke fjernes eller trekkes ut når UPS en er på slik at ikke sikkerhetsjordingen fjernes fra UPS en og d...

Page 27: ...ão se encontra conectada a uma fonte de alimentação de corrente alternada Nunca jogue as baterias no fogo porque há risco de explosão Nunca abra ou danifique as baterias O eletrólito liberado é prejudicial à pele e aos olhos e pode ser extremamente tóxico Para reduzir o risco de incêndios ou choques elétricos instale a UPS em ambiente interno com temperatura e umidade controladas e livres de conta...

Page 28: ...О МЕРАМ БЕЗОПАСНОСТИ О П А С Н О В данном ИБП имеются СМЕРТЕЛЬНО ОПАСНЫЕ НАПРЯЖЕНИЯ Все работы по ремонту и обслуживанию должны выполняться ТОЛЬКО УПОЛНОМОЧЕННЫМ ОБСЛУЖИВАЮЩИМ ПЕРСОНАЛОМ Внутри ИБП нет узлов ОБСЛУЖИВАЕМЫХ ПОЛЬЗОВАТЕЛЕМ О С Т О Р О Ж Н О Аккумуляторы могут вызвать опасность поражения электрическим током или ожога от тока короткого замыкания Соблюдайте соответствующие меры предостор...

Page 29: ...вания и быть доступной для оператора Выключатель ИБП не отключает внутренние узлы от входного электропитания При отключении оборудования на продолжительные интервалы времени отсоедините входной сетевой шнур от настенной розетки Пожалуйста обратите внимание на то что выходные розетки ИБП находятся под электрическим напряжением если была нажата кнопка включения выхода ИБП даже если входной сетевой ш...

Page 30: ...da pueden transmitir corriente eléctrica aun cuando el SIE no esté conectado a un suministro de corriente alterna c a Nunca deseche las baterías en el fuego Las baterías pueden explotar si se las expone a la llama Nunca abra ni dañe las baterías El electrolito que se libera es perjudicial para la piel y los ojos y puede ser extremadamente tóxico Para reducir el riesgo de incendio o de choque eléct...

Page 31: ...cuadamente para el los circuito s de la salida de c a deberán ser adquiridos a un tercero Säkerhetsföreskrifter VIKTIGA SÄKERHETSFÖRESKRIFTER SPARA DESSA FÖRESKRIFTER DENNA BRUKSANVISNING INNEHÅLLER VIKTIGA SÄKERHETSFÖRESKRIFTER FARA Denna UPS enhet innehåller LIVSFARLIG SPÄNNING ENDAST AUKTORISERAD SERVICEPERSONAL får utföra reparationer eller service Det finns inga delar som ANVÄNDAREN KAN UTFÖR...

Page 32: ...er från utrustningen och måste vara inom räckhåll för användaren UPS enhetens strömbrytare isolerar inte elektriskt de interna delarna Vid längre avstängning bör nätsladden dras ur vägguttaget Observera att UPS enhetens uttag är strömförande när laddningsström brytaren Output On button trycks ned oberoende av om spänningskällan är tillkopplad eller inte Minska brandrisken genom att ansluta UPS enh...

Page 33: ...Safety Warnings 25 Powerware Prestige Series Installation and Operator s Manual for IBM Applications 6000 VA Uncontrolled Copy ...

Page 34: ...Safety Warnings 26 Powerware Prestige Series Installation and Operator s Manual for IBM Applications 6000 VA Uncontrolled Copy ...

Page 35: ...Safety Warnings 27 Powerware Prestige Series Installation and Operator s Manual for IBM Applications 6000 VA Uncontrolled Copy ...

Page 36: ...Safety Warnings 28 Powerware Prestige Series Installation and Operator s Manual for IBM Applications 6000 VA Uncontrolled Copy ...

Page 37: ...Safety Warnings 29 Powerware Prestige Series Installation and Operator s Manual for IBM Applications 6000 VA Uncontrolled Copy ...

Page 38: ...Safety Warnings 30 Powerware Prestige Series Installation and Operator s Manual for IBM Applications 6000 VA Uncontrolled Copy This page intentionally left blank ...

Page 39: ...y your distributor if damage is present For assistance with the IBM 9910 UPS see Chapter 8 Service and Support on page 75 UPS and Battery Cabinet Storage If you plan to store the UPS or battery cabinets prior to use store them in a cool dry environment Storage temperature should not exceed 35 C 95 F in order to preserve battery life For longer term storage energize the power processing unit and ba...

Page 40: ... the PPU and battery cabinets with the PPDM 1 Place the UPS near the equipment to be protected The UPS should be well ventilated and away from direct sunlight or other heat source Stack the PPU battery cabinets and PPDM as shown in Figure 4 If more than two batteries are to be used place the batteries next to the other batteries See the FCC Statement in the front of this manual for more informatio...

Page 41: ...EC 320 C19 Receptacles 5 15R Circuit Protectors Power Cords To PPU Circuit Protectors 6 15R Receptacles Neutral Ground Screw Figure 5 L6 30R IEC 320 C19 PPDM Rear Panel Connections 3 For L6 30R IEC 320 C19 PPDM Models Only The factory default for the PPDM output neutral is grounded In some countries the output neutral should not be grounded If your application requires an ungrounded output neutral...

Page 42: ...over Ground Cover Grounded Position Default Ungrounded Position For certain applications only Neutral Ground Screw Figure 6 Output Neutral Ground Screw Utility Input To PowerPass Cord Attached Bypass Switch IEC 320 C19 Receptacle IEC 320 C13 Receptacles Power Cords To PPU IEC 309 Receptacle Circuit Protectors Figure 7 IEC 309 PPDM Rear Panel Connections ...

Page 43: ... Input L6 30R To PowerPass Cord Provided Input Breaker Bypass Switch 5 15R Receptacles L6 30R Receptacles 5 15R Circuit Protectors Power Cords To PPU Circuit Protectors for Locking Receptacles Figure 8 L6 30R 5 15R PPDM Rear Panel Connections 4 Verify the circuit breaker on all battery cabinets is in the OFF O position see Figure 9 ...

Page 44: ...ications 6000 VA Uncontrolled Copy PPU Battery Cabinets Battery Circuit Breaker Battery Connector Breaker Tie Battery Connector Guard Voltage Selector Switch Serial Port Input Plug Input Breaker Output Receptacle REPO Receptacle Battery Connector Figure 9 UPS with Battery Cabinets Rear View ...

Page 45: ...5R 240 240 Set to 200V for 100 200V PPDM output Set to 220V for 110 220V PPDM output Set to 230V for 115 230V PPDM output Set to 240V for 120 240V PPDM output The UPS output voltage should be set according to local mains voltage Using a screwdriver turn the switch to the corresponding position of the output voltage required see Figure 10 The output voltage is factory set to 220V CAUTION Do not tur...

Page 46: ...with the PPDM for 230V usage When using the PPDM it is recommended that the equipment not be plugged into the PPU Do not protect laser printers with the UPS PPDM because of the exceptionally high cyclic power requirements of the heating elements 8 Plug the battery cord into the battery connector on the PPU All battery connectors are polarized to prevent incorrect connection 9 If additional battery...

Page 47: ... PPDM Startup procedure UPS with PPDM Startup To start up the UPS 1 If you are connecting the UPS to an AS 400 the QUPSDLYTIM system value for the UPS Monitoring feature should be set See UPS Monitoring on page 50 for instructions 2 Verify the PPDM input breaker is in the OFF O position does not apply to the IEC 309 PPDM 3 Confirm the correct UPS output voltage is selected see Step 5 on page 37 4 ...

Page 48: ...performs diagnostic tests and enters Normal mode with the equipment load offline The indicator remains lit The startup should take about 15 seconds 12 Press and hold the Output On button until you hear the UPS beep approximately one second The indicator remains lit and the Self Test indicator turns on The front panel displays the percentage of full load being applied to the UPS The UPS is now in N...

Page 49: ...high voltage REPO wires To ensure the UPS stops supplying power to the load during any mode of operation the input power must be disconnected from the UPS when the emergency power off function is activated The optional three wire REPO cord see Figure 11 can be ordered from the manufacturer The green wire is a safety ground for the REPO conduit The REPO function activates when the black and white w...

Page 50: ... Cord If you are using the optional REPO cord junction box place the conduit through the access hole on the junction box Connect the exposed conduit wires to the corresponding compression terminals see the following table Tighten the compression terminals with a screwdriver see Figure 12 Mounting Holes Plug Receptacle PPU Connector Three Foot Cord Terminal Block Access Hole for Conduit Figure 12 O...

Page 51: ...ting Tips If you should encounter any problems during startup see the troubleshooting chart on page 71 The battery cabinets are shipped with the batteries charged However batteries may lose some of the charge during shipping and storage You can use the UPS immediately after unpacking but it may not provide the full rated backup time during a power failure Upon initial startup the UPS may need to o...

Page 52: ...Installation 44 Powerware Prestige Series Installation and Operator s Manual for IBM Applications 6000 VA Uncontrolled Copy This page intentionally left blank ...

Page 53: ...ional mode Normal Bypass or Battery Displays any alarm conditions present during operation the indicators flash Displays the loading percentage during Normal mode and the battery capacity during Battery mode You can also use the front panel to configure UPS communication options See Front Panel Communications Access on page 56 Overload Indicator Site Fault Indicator Overtemp Indicator Battery Faul...

Page 54: ...on Receptacle or Terminal Block Output EMI RFI Filters Surge Suppression EMI RFI Filters Battery Charger Battery Battery Inverter Bypass Line Battery Cabinets Emergency Power Off Receptacle or Terminal Block Utility Power Rectifier Figure 14 UPS Block Diagram Normal Mode During Normal mode the indicator illuminates and the front panel displays the percentage of UPS load capacity being used by the ...

Page 55: ...panel displays the approximate percentage of battery capacity remaining You can calculate the approximate minutes of battery time by multiplying the Total Battery Time Minutes see Figure 3 on page 4 times the percentage indicated by the Battery Operation indicators see Figure 17 When the utility power returns the UPS switches to Normal mode operation while the battery recharges BATTERY ONLINE 75 C...

Page 56: ...it is operating in Normal mode ensuring proper operation These tests include Self Test Utility Verification Test Battery Discharge Test Over Temperature Test The UPS also runs a series of over 20 internal tests when power is first applied If a diagnostic test fails see Chapter 7 Troubleshooting on page 71 Battery Test on Demand You can perform a battery test on the UPS while it is operating in Nor...

Page 57: ...M see Using the PPDM on page 51 To perform a UPS shutdown 1 Press and hold the Output Off button until the long beep ceases approximately three seconds The indicator remains lit indicating Normal mode load offline 2 Switch the input breaker on the power processing unit to the OFF O position The UPS enters Battery mode for several seconds The indicator turns off and the UPS shuts down 3 Unplug or r...

Page 58: ...tion in one of the following IBM documents AS 400 Advanced Series Backup and Recovery Advanced SC41 4305 for AS 400 Models 3xx and 5xx AS 400e series Backup and Recovery SC41 5304 for AS 400 6xx and Sxx V4R1 Backup and Recovery information AS 400 Models 3xx 5xx 6xx and Sxx is also available on the Customer Documentation AS 400 Softcopy Library CD SK3T 0118 and on the Internet at http publib boulde...

Page 59: ...DM UPS Load Figure 18 UPS and PPDM Block Diagram Disconnecting the UPS Use the following procedure to transfer the critical load to Maintenance Bypass AC Line operation and remove the PPU 1 Turn the Bypass switch on the PPDM to the BYPASS position see Figure 19 The PPDM is now powering your equipment from utility power 2 Press and hold the Output Off button until the long beep ceases approximately...

Page 60: ...y connector on the PPU rear panel 7 Remove the PPU 5 15R Circuit Protectors Power Cords To PPU PPU PPDM Power Processor Input Plug Output Receptacle Power Processor Input Breaker Voltage Selector Switch REPO Receptacle Battery Connector Serial Port L6 30R Receptacles Circuit Protectors for Locking Receptacles Utility Input Receptacle Cord Provided PPDM Input Breaker Bypass Switch 5 15R Receptacles...

Page 61: ...EC 320 C19 208 120 208 208 L6 30R 5 15R 208 120 208 IEC 309 IEC 320 C13 240 240 Set to 220V for 220V PPDM output Set to 230V for 230V PPDM output Set to 240V for 240V PPDM output L6 30R 5 15R 240 240 Set to 200V for 100 200V PPDM output Set to 220V for 110 220V PPDM output Set to 230V for 115 230V PPDM output Set to 240V for 120 240V PPDM output The UPS output voltage should be set according to lo...

Page 62: ... position After a short delay approximately three seconds the UPS front panel indicators turn on and cycle through several times The and indicators remain lit for several seconds UPS in Bypass mode 6 Press and hold the Output On button until you hear the UPS beep approximately one second The indicator remains lit and the Self Test indicator turns on 7 Turn the Bypass switch on the PPDM to the NORM...

Page 63: ...acts default Printer Mode 19200 Baud with Novell Contacts LAN Configuration Novell Style Network Interface 3Com Style Network Interface AS 400 Style Network Interface Custom User Configurable Interface Initial Communications Settings The UPS is factory configured for one of several communication interfaces usually determined by the customer To determine the initial UPS communications configuration...

Page 64: ... SITE FAULT OVERTEMP BATTERY SELF TEST OVERLOAD SITE FAULT OVERTEMP BATTERY SELF TEST OVERLOAD SITE FAULT OVERTEMP BATTERY SELF TEST FRONT PANEL COMMUNICATION OPTIONS Printer Mode 2400 Baud Novell Contacts Select this mode for the OnliNet9 or LanSafe software OVERLOAD SITE FAULT OVERTEMP BATTERY SELF TEST OVERLOAD SITE FAULT OVERTEMP BATTERY SELF TEST Novell Style LAN Contacts Any baud rate other ...

Page 65: ...e alarm beeps All indicators begin flashing 3 Press and hold the Output Off button a second time until the alarm beeps again A single indicator corresponding with the current setting remains flashing 4 Press the Output Off button to scroll through the communication options top to bottom Each time you press the button the UPS beeps and the next indicator flashes NOTE If you do not save a selection ...

Page 66: ...PS usually 2400 baud 8 bits No parity 1 stop bit Refer to your terminal or operating system documentation for details on configuring the terminal communication settings 3 At the terminal prompt press Control C until the UPS Serial Communications Menu appears 836 6 5 20081 7 216 0 18 6 7 23 5 7 21 02 17 5 6 7 21 217 18286 803 3 4 6 32 803 60 57 803 6 7 50 1 97 7 50 1 35 17 5 803 1 21 85 7 21 6 7 8 ...

Page 67: ...s mode 2 Polled Dump Status information is transmitted only when requested by a poll character Control E 3 Smart Dump Status information is transmitted when polled as in the previous mode However the transmission also occurs automatically whenever UPS status changes For example if there is a power outage UPS status information changes and is therefore automatically transmitted A ASCII Terminal The...

Page 68: ...on for details on the required signal states for configuring LAN communications QYHUWHU VKXWGRZQ FRQWURO LV HQDEOHG DFWLYH 9 6 7 86720 1 21 85 7 21 17 5 6 7 21 4 72 48 7 7 6 0 18 QYHUWHU VKXWGRZQ FRQWURO LV HQDEOHG DFWLYH 2 9 QYHUWHU VKXWGRZQ FRQWURO LV GLVDEOHG QVWUXFWLRQV KRRVH WKH GHVLUHG LQYHUWHU VKXWGRZQ IXQFWLRQ DUQLQJ W LV UHFRPPHQGHG WKDW WKLV IHDWXUH VKRXOG QRW EH XVHG ZLWK QRUPDO 56 FRPP...

Page 69: ... changes you make to the UPS communications configuration must correspond to the communications equipment you are using In particular new baud rate selections for the UPS must match your communications equipment Power Management Software Power management software allows you to monitor UPS operations automatically To use OnliNet or LanSafe software the UPS must be configured for any one of the Data...

Page 70: ...on The use of any additional pins for any of the following interfaces can cause interference with system communications Even though your network uses the specified signal lines the pins assigned to these signals at the network end of the cable may vary with those of the UPS serial port The connector body and style may vary as well NOTE Standard pin for pin cables may not work correctly Consult you...

Page 71: ...RS232 TxD 2 N A Data from UPS RS232 RxD 3 N A Signal Ground 7 Novell D f l Battery On ON AC 14 16 Open Default Low Battery TWO MIN 23 24 Closed Signal Ground 7 15 25 Novell C Battery On ON AC 14 16 Closed Custom Low Battery TWO MIN 23 24 Closed Signal Ground 7 15 25 3Com D f l Shutdown Remote SHUT DOWN 2 Positive Voltage Default Low Battery LOW BATT 9 Positive Voltage Battery On PWR FAIL 10 Positi...

Page 72: ...Communication 64 Powerware Prestige Series Installation and Operator s Manual for IBM Applications 6000 VA Uncontrolled Copy This page intentionally left blank ...

Page 73: ...cifications Output VA Output Voltage Output Watts Input Current Output Current Normal BTUs hr On Battery BTUs hr 5000 200 3350 19 6A 25 0A 1600 2200 5200 208 3500 19 7A 25 0A 1600 2300 5500 220 3700 19 7A 25 0A 1700 2400 5750 230 3850 19 6A 25 0A 1800 2500 6000 240 4000 19 5A 25 0A 1900 2600 Model 6000 UPS with PPDM Nominal Operating Specifications Output VA PPU Output Voltage PPU Output Watts Nor...

Page 74: ...Range 170 to 276 Vac Input Power Factor 0 95 Typical Frequency Range 50 60 Hz 3 Hz Surge Protection IEC 801 4 Output Waveform Sine wave Output Voltage 200 208 220 230 240 Vac 3 Common Mode Noise Rejection 60 dB 100 kHz Transverse Mode Noise Rejection 80 dB 100 kHz Input Cord Detachable 2 meter cord Outlets One L6 30R Batteries 10 per cabinet 12 Vdc 5 Ah maintenance free rechargeable lead acid Batt...

Page 75: ...quirements when the PPDM is used with the UPS The distribution of your load on the available outputs of the PPDM may affect the maximum load obtainable Prestige 6000 PPDM Ratings with a Model 6000 UPS PPDM Model Input Utility Voltage and Selected UPS Output Voltage Input Current Output Voltage and Maximum Current Maximum Output Apparent Power 208 120 208 L6 30R IEC 320 C19 PPDM 208 Vac 24A 120 208...

Page 76: ...tribution Module 120 240 IEC 309 17G1795 9910 6557 Prestige 6000 PowerPass Distribution Module 120 208 L630R IEC 320 C19 21H8441 9910 6555 Prestige 6000 PowerPass Distribution Module 120 208 L6 30R 5 15R 21H8442 9910 6556 Prestige 6000 PowerPass Distribution Module 120 240 L6 30R 5 15R IBM Part Number Powerware Part Number Description 17G2374 124102011 001 15 ft AS 400 Communications Cable N A 152...

Page 77: ...ator s Manual for IBM Applications 6000 VA Uncontrolled Copy Manuals IBM Order Number Description SC21 8380 Powerware Prestige Series Installation and Operator s Manual for IBM Applications 6000 VA Manuals may be ordered from the IBM Mechanicsburg Distribution Center ...

Page 78: ...Specifications 70 Powerware Prestige Series Installation and Operator s Manual for IBM Applications 6000 VA Uncontrolled Copy This page intentionally left blank ...

Page 79: ...ond then release UPS beeps occasionally Normal operation None UPS is protecting your equipment indicator remains lit th h li Utility line is out of specification Test wall socket repair as required lit even though line voltage is present UPS input breaker is tripped Reduce load then reset breaker UPS does not provide the expected backup time Battery circuit breakers are in the OFF O position Switc...

Page 80: ...RLOAD The UPS switched to Bypass mode because the overload increased above 105 The alarm beeps Reduce load If the Overload indicator remains lit reset the UPS by pressing the Output On button until the alarm beeps You may need to obtain a larger capacity UPS The utility line voltage and frequency are out of specification The inverter remains online deriving power from the utility until it is no lo...

Page 81: ... beeps Contact your service representative if condition persists NORMAL REPLACE Weak battery Verify that the battery is connected and the battery circuit breaker is in the ON position If battery is properly connected allow the battery to charge for 24 hours Retest Have batteries replaced if condition persists Resetting the UPS To reset the UPS while an alarm condition is present press the Output O...

Page 82: ...Troubleshooting 74 Powerware Prestige Series Installation and Operator s Manual for IBM Applications 6000 VA Uncontrolled Copy This page intentionally left blank ...

Page 83: ...y country Under NO CONDITIONS are IBM Customer Engineers authorized to remove the covers The warranty on the replacement unit should you require one is for the remaining period of warranty of the original unit See page 84 for a detailed description of the warranty Installation Instructions Installation instructions are in pictorial form on the Quick Install pages in the front of this manual and al...

Page 84: ...onths after manufacture whichever comes first The warranty is invalid if the battery is subject to misuse abuse or physical damage Warranty Model Part Number Coverage Area 5 Year 3 Year EP8 21H1572 AP Canada LA US X EP8 21H1572 EMEA X Obtaining Service The troubleshooting chart on page 71 covers most of the difficulties you may encounter during normal operations For further assistance with IBM 991...

Page 85: ...ort FSS 2 Customer indicates that the UPS is defective 3 The FSS will confirm that the unit is listed in the customer profile and notify Powerware 4 Powerware will promptly call the customer and ask for the serial number Powerware will also attempt to determine the nature of the problem The problem may be related to improper operation as opposed to a defect 5 If the unit requires replacement Power...

Page 86: ...calls 1 800 426 7378 2 Dispatch takes the information from the customer and notifies the IBM Customer Service Representative CSR 3 Problem determination is performed by the CSR 4 If a replacement unit is required the unit is ordered out of stock and sent to the customer 5 The CSR does the swap and returns the defective unit to the IBM parts center Latin America Customer Process for Service 1 Custo...

Page 87: ... is element exchange If the UPS becomes inoperative the module that is inoperative will be replaced For 6 kVA UPSs this would either be the battery the PowerPass Distribution Module the Power Processing Unit the Transformer Module or interconnection cable between the UPS and the optional battery cabinets Under NO CONDITIONS are IBM Customer Engineers authorized to remove the covers from any of the...

Page 88: ...llow for connection to customer power and the S 390 equipment The following figures represent approximate dimensions of cable access cuts for 3 standard raised floor tile sizes 177 mm l 177 mm 7 in l7 in 127 mm 5 in 610 mm 24 in or 600 mm 23 6 in Tile 75 mm 3 in 465 mm Tile 18 25 in 177 mm l 177 mm 7 in l7 in The UPS can be positioned on the right side of the S 390 since S 390 growth adds frames t...

Page 89: ... Top Cover Battery Cabinet Battery Cabinet Power Processing Unit PowerPass Distribution Module Castor Plate Battery Warranty The warranty period is five years from the date of installation or 66 months from the date of manufacture whichever occurs first If in Powerware Corporation s opinion the unit fails to meet published specifications and the defect is within the terms of the limited warranty a...

Page 90: ...ons There are many configurations of UPS and S 390 models and options The following are basic examples of the Powerware Corporation UPSs and IBM S 390 processors The type and part number of the line cord sense and power cable will vary depending upon customer power connection S 390 model and features See Part Numbers on page 83 for detail Power Cable Sense Cable One 9910 and one S 390 S 390 Line C...

Page 91: ... the IBM part numbers assigned to the Powerware Corporation modules 46H9377 Power Processing Unit 46H9378 PowerPass Distribution Module 46H9379 Battery Cabinet 46H9380 REPO Cable 46H9381 Transformer 46H9382 Castor Plate 46F4593 9672 to 9910 Power Line Cord with RS connector 19G2943 9672 to 9910 Power Line Cord with pigtail 07H6890 Power Cable 9910 to S 390 9672 74 R2 R3 C2 C3 07H6901 Power Cable 9...

Page 92: ...RESSLY IN LIEU OF ANY OTHER WARRANTY AND THERE ARE NO OTHER EXPRESSED OR IMPLIED GUARANTEES OR WARRANTIES INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OF FITNESS FOR PURPOSE Powerware Corporation s liability on any claim of any kind relating to the unit batteries or otherwise for any loss or damage arising out of or in connection with or resulting from this Agreement or from the performance o...

Page 93: ...can National Standards Institute ANSI power line transients electrical spikes electrical surges brownout blackout UPS products must be properly maintained according to the manufacturers recommendations set forth in the operator s manual and the UPS installation must adhere to electrical safety requirements set forth by the National Electrical Code NEC or applicable local code s The UPS must be pro...

Page 94: ...Service and Support 86 Powerware Prestige Series Installation and Operator s Manual for IBM Applications 6000 VA Uncontrolled Copy This page intentionally left blank ...

Page 95: ... Mode 59 B battery circuit breaker 36 configuration 2 extension time 4 input connector 36 installation 32 output connector 36 rear panel 36 storage 31 Battery Fault alarm 72 indicator 45 Battery Mode 47 Battery Online indicator 45 Battery Start 48 Battery Test on Demand 48 baud rates 58 61 Bypass Mode 47 Bypass switch 33 34 35 C changing the output voltage 49 communication interface port 62 modes ...

Page 96: ...dicators front panel 45 input cord 39 66 Inverter Shutdown Control 60 L LAN Configuration Main Menu option 58 menu 60 load definition 2 requirements 2 LOW_BATT 60 M Main Menu 58 Maintenance Bypass feature See also PowerPass Distribution Module PPDM activating 51 deactivating 53 Menu Custom LAN Configuration 60 LAN Configuration 60 Main 58 Serial Communications 58 Set Baud Rate 61 Mode ASCII Termin...

Page 97: ...Line operation 51 block diagram 51 changing output voltage 37 53 installation 32 Maintenance Bypass feature 32 operation 51 power output receptacles 33 34 35 rear panel 33 34 35 startup 39 utility input connector 33 34 35 PPU external battery connector 36 input breaker 36 power input connector 36 power output receptacles 36 rear panel 36 REPO connectors 36 serial port 36 Printer Mode front panel c...

Page 98: ...ature 31 Switch Bypass 33 34 35 Output Voltage Selector 37 system requirements 2 T Terminal Modes 59 Tests Battery on demand 48 diagnostic 48 troubleshooting chart 71 tips 43 U uninterruptible power system 1 UPS alarm silencing 73 alarms 72 block diagram 46 changing output voltage 49 communication 55 Communications Mode Reference Chart 63 front panel 45 operation 45 operation with PPDM 51 resettin...

Page 99: ...91 Powerware Prestige Series Installation and Operator s Manual for IBM Applications 6000 VA Uncontrolled Copy ...

Page 100: ...92 Powerware Prestige Series Installation and Operator s Manual for IBM Applications 6000 VA Uncontrolled Copy 164200291 E ...

Reviews: