Handling-Short Instruction for
EtherSens-devices / MONI V1.0
The EtherSens devices and
MONI
are data loggers according to their specification. Either for digital or analog
input- and output-signals, energy data or just as a pure messenger.
Commissioning of the device :
- EtherSens Bridge, EtherSens Control,
MONI
:
Connect the voltage 24V DC ± 20% to the labeled terminal conn 24V and GND
- EtherSens Energy, EtherSens Energy II,
MONI
:
Connect the voltage 230V AC to the labeled terminal connectors L1 and N.
The device starts up now, you will see the status of the device on the two-color illuminated LED display :
Green:
ON
device ready
OFF
device executes a restart or is powered off
Red:
ON
device is booting
flashing at device boot
device is updating the firmware
flashing 0,5 Hz
device is logging data
fast flashing
output of error codes (see below)
List of error codes:
1x flash:
Initialization error of a sensor.
2x flashes:
Space on the SD card smaller than 1 Kilobyte
or SD card removed without logging off.
3x flashes:
Error at last mail transfer (SMTP).
4x flashes:
Error at last time adjusting (NTP).
5x flashes:
No network connection available (only when there isn’t a connection to the
Access-Point and no LAN link state available).
When you want to reset your device (factory settings) you can press the reset button for 3s to 10s while the
device is booting. The button must be pressed with the help of a paperclip and can be found on the bottom / back
of the device.