Page 1: ...PROTECTION AUTOMATION AND CONTROL FOR POWER INDUSTRY DOCUMENT ID PP 06 22516 LAST VERSION 1 0 2022 02 21 BUDAPEST Installation Manual EUROPROT APPLICATION GUIDE ...

Page 2: ...2 Installation Manual www protecta hu VERSION INFORMATION VERSION INFORMATION VERSION DATE MODIFICATION COMPILED BY 1 0 2022 02 21 First edition Hanti ...

Page 3: ...ing location 5 3 4 Mounting the device 6 3 5 Safety aspects 6 3 5 1 Earth connections 6 3 5 1 1 Protective earth 6 3 5 1 2 Stranded wires 6 3 5 1 3 Cable screen connection 7 3 5 1 4 CT and VT circuits 7 3 5 2 Connections of the device 7 3 5 3 Optical ports 7 3 5 4 Removing and changing modules 8 4 Wiring 8 4 1 Tools for connecting 8 4 2 Connectors 9 5 Deinstallation and Repair 9 5 1 Deinstallation...

Page 4: ...ovided here will strongly support commissioning maintenance and deinstallation work as well This document s targeted user groups are skilled electrical professionals executing installation works and commissioning with EuroProt devices Given that the EuroProt product family has a modular design the instructions provided here can cover all configurations Therefore this manual shall be used in conjun...

Page 5: ...g The tools and screws necessary for mounting depend on the method of the mounting see the Mounting methods section of the EuroProt Hardware description document Assuming the panel or cubicle is ready for installation of the device screwdrivers matching the screws used plyers wrenches etc are necessary For safety aspects mechanical protective gloves shall be used to avoid injuries 3 2 Environmenta...

Page 6: ...cross section solid or stranded wire A 6 3 mm 1 4 inch female flat connector according to IEC 61210 shall be used crimped to the earthing wire During the installation make sure that the shortest possible length for PE Protective Earth cable routing is applied The earth connection of the device is situated at all kinds of Power supply modules In the case of more Power supply modules all of them sha...

Page 7: ... to the station earth system 3 5 2 Connections of the device Before connecting the wires make sure that all voltage levels correspond to the device ratings It is particularly important by the power supply trip and binary input CT and VT module Use only the connectors provided to the device or identical ones The CT connectors shall be fixed with screws provided During the operation of the device th...

Page 8: ...ing the connectors of the CT modules the CT circuits shall be short circuited and disconnected The protective earth connection can be disconnected last if it is necessary e g when removing a Power supply module The devices contain components that are sensitive to electrostatic discharges ESD wrist strap shall be worn during any operations with modules Some of the modules can operate at high intern...

Page 9: ...ing the device make sure that all incoming power supply and control voltages are switched off The earth connection of the device shall be disconnected last 5 2 Repair Thanks to its modular design many hardware problems can be fixed by replacing single modules By executing this procedure note that the printed board s surface may get hot during normal operation In addition attention shall be paid to...

Page 10: ...odules Metallic parts fastening elements Aluminum steel Separation and recycling Mounted PC boards Plastic various electronic elements Separation and recycling Connectors Plastic various metals Separation and recycling Transformers coils Iron copper plastic paper Separation and recycling Relays Iron copper plastic other metals Separation and recycling Package Box Cardboard Recycling Attachments Ma...