SPECIFICATION FOR DOMESTIC WATER HEATERS

Power Combustion, Gas-Fired Water Heaters with Nickel-Plated Storage Tanks

Furnish and install the following 

MAXIM

 gas water heater(s) as manufactured by PVI INDUSTRIES, INC of Fort Worth,

Texas.

Model

Btu/h

GPH Recovery

Storage

Qty

Number

Input

40° to _____°F 

Tank Size

___

____________

__________

________

_______ 

gallons

___

____________

__________

________

_______ 

gallons

___

____________

__________

________

_______ 

gallons

Gas and Electrical Consumption

The water heater will operate at 83% thermal efficiency.

Each water heater will have a burner motor with the following maximum electrical ratings:

Heater Model Number

Heater Btu/h Input

Motor Horsepower 

Voltage

Amps

______________

___________

_____

_____

____

______________

___________

_____

_____

____

______________

___________

_____

_____

____

To conserve energy, the water heater will not utilize a continuously operating, integral circulation pump between the

storage and heating section.

Pressure Vessel and Heating Surfaces

The water heater will be a vertical fire tube design that is constructed and stamped in accordance with Section IV,

Part HLW of the ASME code.  Both the storage and heating sections of the water heater will be National Board
Registered for a working pressure of 150 psi and will be pressure tested at 1-1/2 times working pressure.  For maximum
thermal strength, the fireside of the heating surfaces will be of boiler-grade steel. For corrosion protection, the waterside
of the heating tubes will be sealed in copper.  The heating tubes will be rolled, beaded, and seal welded into the tube
sheets. The combustion side of the tube sheet will be insulated by a layer of ceramic fiber that will protect the tube sheet
from both thermal stresses and failure that can result from the accumulation of scale and precipitants.