UNIVERSAL TEMPERATURE CONVERTER

4 way isolated - RS485 MODBUS- Datalogger

QA-TEMP

Power

Fail

Rx

Tx

Dout

USB

OTG

QA-TEMP

QEED

Advanced

UNIVERSAL  TEMPERATURE  CONVERTER

,

USB

configurable

,

DIN  rail  mounting,  4-way  galvanically  isolated,

universal  power  supply  AC/DC,

Programmable  alarm  contact

,

RS485 Modbus

.

DATALOGGING  via  USB

with  pen  drive  stick  memory  and

download storage data on excel importable files.

RTC Real Time

Clock

integrated.

RTD,TC and POTENTIOMETER CONVERTER.

Temperature
Sensor

 INPUT

TEMPERATURE:
RTD:

Pt100, Pt500, Pt1000, Ni100. 2, 3 or 4 wire measure, automatic detection of

cable interruption.

TC Types:

 J, K, R, S, T, B, E, N; automatic detection of cable interruption.

POTENTIOMETER:

from 1000 Ohm to 10 KOhm.

RESISTANCE:

resistance measurement 400ohm or 4000 ohm to 2, 3, 4 wires.

 OUTPUT

CURRENT:

0...20mA programmable, max load resistance 600 ohm.

VOLTAGE:

0...10V programmable, min load resistance 2 kohm.

CONTACT  ALARM:

5A  230Vac  SPDT  relay  fully  programmable  by  FACILE  QA-

TEMP.

RS485 MODBUS:

Bus connection on the base of module by adapter (option) or

on terminals. Dip-switch for setting address and baudrate.

1

09

2015

Analog output

Contact Alarm

RS485 Modbus

DATALOGGER

POWER SUPPLY

  RETRASMISSION OUTPUT

PROTECTION INDEX

10..40 Vdc, 20-28 Vac, 50-60 Hz

On isolated analog output,

ABSORPTION

Maximum 2 VA

IP20

16 bit

50-60 Hz

< 100 ppm/°C

-15...+65°C

-40°C... +85°C

0,1% F.S.

Voltage  and  Current  (impressed)  programmable;  Active

or Passive supply output

13 Vdc 30mA max

ACCURACY

RESOLUTION

 REJECTION

THERMAL STABILITY AT 25°C

WORKING TEMPERATURE

STORAGE TEMPERATURE

ISOLATION

Input, analog and digital output,

serial  output  RS485  and  USB  port,  Power  supply,  are

4-way galvanically isolated at 1,5kV

OnTheGo port by Pen Drive stick memory. The software
FACILE QA-TEMP (free of charge) allow you to configure
Log,  all  conversion  parameters,  set  contact  alarm,  set
Modbus address. RTC Real Time Clock integrated

By free software FACILE QA-TEMP to configure all of the
conversion parameters like span, zero, alarm contact and
log  via  USB  port  or  via  RS485.  Dip-switch  for  setting
modbus address and baudrate

CONFIGURATION

EN61000-6-4/2006 + A1 2011;
EN64000-6-2/2005; EN61010-1/2010

17,5 x 100 x 112 mm (terminals excluded)

Up to 2000 m s.l.m.

HUMIDITY

10...90% non condensing

ALTITUDE

MOUNTING

Removable terminals 5,08mm

CONNECTIONS

CE STANDARDS

DIMENSIONS

Non-volating memory. Log on USB

DATA LOGGER

DIN rail mounting with removable

terminals,  RS485  bus  and  Supply  connection  ready  on
the  base  of  module  (connector  not  included,  on
request).

ENGLISH

Summary of Contents for QA-TEMP

Page 1: ...2015 Analog output Contact Alarm RS485 Modbus DATALOGGER POWER SUPPLY RETRASMISSION OUTPUT PROTECTION INDEX 10 40 Vdc 20 28 Vac 50 60 Hz Onisolatedanalogoutput ABSORPTION Maximum 2 VA IP20 16 bit 50...

Page 2: ...and 6 The Thermo couple whatever it is it requires the connection between termi nals 3 and 4 To connect a potentiometer use terminals 3 4 and 6 To make resistance measurements at 2 3 and 4 wires to fo...

Page 3: ...ISTANCE at 400ohm or 4kohm at 2 3 4 wires Ni100 PT100 PT500 PT1000 at 2 3 4 wires TC type J K R S T B E N The QA TEMP sampling data every 100 msec you can choose to mediate the input value up to a max...

Page 4: ...t starting as OPEN CONTACT that is if there is an alarm already set or active If you want to change the initial status of the digital output select CONTACT CLOSED from the dropdown in the upper right...

Page 5: ...entiometer or resistor ANALOG OUTPUT the value uA or in mV output of the module This value follows the setting made via FACILE INPUT TYPE refered to the Modbus Register 101 that indicate the type of t...

Page 6: ...reference to the logical address for ex 40010 corresponds to physical address n 9 as per Modbus RTU standard Modbus functions supported 3 Read multiple registers 6 Write single 16 Write multiple Any c...

Page 7: ...Log name Log name 15 letters max UNIT16 R W 0 40129 Log name Log name 15 letters max UNIT16 R W 0 40130 Log name Log name 15 letters max UNIT16 R W 0 40131 RTC Year RTC Year UNIT16 R W 2000 2099 4100...

Page 8: ...is document correspond to the products and technologies described This information may be amended or supplemented by technical and commercial requirements Disposal of Electrical Electronic Equipment A...

Reviews: