Quick start 2-Wire v3.0 

EMM.630(M)CT-MID (

1A of 5A CT

) and 

EMM.630MCT-RC (Rogowski coils) 

The EMM.630 (M)CT is an advanced 3 phase 
energy monitor with direct connection to the 

mains for measuring reference voltages and 

3 connection for linking the current 
transformers 1A  or 5A CT or Rogowski  coils 

(EMM.630 MCT-RC) with which consumers 
can be measured >100A. The configuration 

of the meter is done via the touch keys on 

the front panel and the LCD display. The bi-
directional measurement measures 

consumption on mono, 3x230V or N 

power supplies. Both active and reactive power are measured. The 
readout of the consumption values can be done via the display or on the 

linked web server. The module is packed in a 4 module wide DIN rail 
housing. In addition to an RS485 connection, this energy meter also has 2 

pulse outputs, of which 1 is configurable. 

1. Connect: 

Attention 1:

 To avoid voltage surge: first connect coil conductors to the 

meter, only then clip coil around current conductors !! Install the power coil 
only by a qualified electrician !!! Wear safety goggles during every operation 
with the coils !!! 

Attention 2:

 With the  

EMM.630 CT-MID

,  the type of coil can only be 

entered once, see point 2. Configuration on display  
 

Attention 3:

  After connecting the coils via display key "P"  

polarity check

if negative power(Watt) or negative PF then open and turn coil, unless 
there would be injection by solar panels! 

 

Attention 4:

  The measured reference voltage and the measured current 

must be at the same  stage: ALWAYS test

 with voltmeter

 : Voltage 

between conductor reference voltage and conductor flow pool must be 
ZERO, otherwise you have a wrong measurement!! Here you can possibly 

use the voltage drain terminals type UAD (see website) 

EMM.630 (M)CT: Mono-phase connection 

 

 

On display: 

set as mono phase: SYS 1P2 

Reference voltage:

 Neuter on Clamp 1; Phase on Clip 4 

Flow coil:

 Keep flow arrow on coil, arrow points to Users!  Black 

conductor(=GND) on Clip 19; White conductor on Clip 20 

Power voltage module: 

Neuter on Clamp 6,Phase on Clamp 5 

Note: by-loop-Clamp to next meter Clamp 7= Clamp 5; Clip 8= Clamp6 

Modbus connections:

 Clamp A (=13) and B (=14)  and GROUND (=12 GND) 

EMM.630 CT: 3x230V connection 

 

 

On display: 

set as 3phase/3guider: SYS 3P3 

Reference voltage: 

L1  on Clamp 4; L2 on Clamp 1; L3 on Clip 2 

Flow coil:

 Keep current arrow on coil, arrow points to consumer! 

Rinse L1: Black conductor (=GND) clamp 19; White conductor clamp 20 

Rinse L2: Flow I2 (I1+I2+I3=0) is calculated, so does not need to be 
measured and therefore no coil required! For this reason, no power is 

logged in the Memo for this phase2. 

Rinse L3:Black conductor (=GND) on clip 15; White conductor on clamp 16 

Power supply voltage:

 Neuter on Clamp 6; Phase on Clip 5 

Note 

:

  by-loop-Clamp to next meter:Clamp7= Clamp 5; Clip 8= Clamp6 

Modbus connection:

 Clamp A (=14) and B (=13)  and GROUND (=12 GND) 

EMM.630 CT: N connection 

 

 

On display: 

set as 3phase/3guider:  SYS 3P4 

Reference voltage

:  L1 on Clamp 4;;  L2 on Clamp 3;  L3 on Clamp 2; 

N=Clamp 1 

Flow coil:

 Keep current arrow on coil, arrow points to consumer! 

Rinse L1: Black conductor (=GND) on Clip 19; White conductor on Clip 20 

Rinse L2: Black conductor (=GND) on Clip 17; White conductor on Clip 18 
Rinse L3: Black conductor (=GND) on Clip 15; White conductor on Clip 16 

Power voltage module:

 Neuter on Clamp 6; Phase on Clip 5 

Note: Loop-Clip to Next Meter Clip 7= Clip 5; Clip 8= Clamp6 

Modbus connection: 

Clamp A (=14) and B (=13)  and GROUND (=12 GND) 

2: Configuration on the display:  

This module is partly pre-configured and only needs to be entered: 

 

UNIQUE 

 

Modbus address, number between 1... 247 

 

the type of power supply mono,3x230V,N, standard at 
3x380+N 

 

the type of coil: be careful, 

this can only be done once and cannot 

be adjusted afterwards!!!

 

How to get into SETUP:  

 

(watch video tutorial)  

https://www.2-wire.net/en/product/3f-

energy-meter-ct-mid-modbus-emm-630-ct/

Push the bottom  button 4 (enter→)until PASS  0000  appears, fill in default 
password PAS 1000 by pressing the button 2 (M↑) to 1, briefly press button 
4 (enter) for next number or press enter for a long time to move to next 
setting. Go  through button 3 (P√) through the set values and adjust the 
necessary

 

Modbus values. Briefly press 

 

button 1 (U/I 

 

←))

 

to leave menu. 

Modbus parameters to be set: 9600 8N1 

 

Modbus address : Id001... Id247 

 

Baudrate: b 9600  

 

Parity: Prty n (parity none) 

 

Data: 8 bit 

 

Stopbit: 1 

Secondary current of the coil 1Ampere or 5Ampere: SET 

Ct2 5

 

 At 

 

the 

 

EMM.630CT-MID this can only be set 

once!!

 

Multiplication factor = primary/ to secondary flow 

strength of the coil, E.g. 100A/5A=20: Ct rATE 0020 

With the 

 

EMM.630CT-MID this can only be set once! 

In case Rogowski: CT1 should be set to 1kA, in the 

EMM.630 MCT-RC meter you can still change settings 
afterwards  

ATTENTION: 
1.

 

The values SET Pt2 400

 

 and 

 

Pt rAtE 0001

 

 

are 

for high voltage and can only be adjusted 

once.

 

Leave it on DEFAULT!

 

!  

2.

 

The backlight of the display can be set to 
0/5/10/30/60/120.  
0 stands for continuous, 5/10/30/60/120 
means switch off after the set period . Here 
better choose 5/10/30 to increase the service 
life. 

3: Configuration in the web server 

In the web server, go to /configuration/modules: 