background image

Installation, Operation and Maintenance Instructions

This manual is provided to acquaint you with the 

dehumidifier so that installation, operation and maintenance 

can proceed successfully. Ultimate satisfaction depends on 

the quality of installation and a thorough understanding 

of this equipment. The dehumidifier is built around tested 

engineering principles and has passed a thorough inspection 

for quality of workmanship and function.

Quest Dry

Installation, Operation and Maintenance Instructions

4201 Lien Rd 

Phone 608-237-8400

Madison, WI 53704 

Toll-Free 1-877-420-1330

www.QuestClimate.com info@QuestClimate.com 

– Read and Save These Instructions –

Specifications subject to change without notice.

1

TS-1052 

05/18 Rev. B

50Hz Quest 155

50Hz Quest 155:

•  Industry-leading efficiency
•  Patented, optimized air-to-air heat exchanger
•  High-efficiency, long-life impeller fan
•  MERV-13 filtration
•  Auto-restart after power outages
•  Low voltage control

Water Removal Rates Per Day @ 26.7°C (80°F) 60% (AHAM)

 

 

Dehumidifier  Liters Pints/Gallons

 

Quest 155 

71 

150/18.7

Summary of Contents for 155

Page 1: ...nship and function Quest Dry Installation Operation and Maintenance Instructions 4201 Lien Rd Phone 608 237 8400 Madison WI 53704 Toll Free 1 877 420 1330 www QuestClimate com info QuestClimate com Read and Save These Instructions Specifications subject to change without notice 1 TS 1052 05 18 Rev B 50HzQuest155 50Hz Quest 155 Industry leading efficiency Patented optimized air to air heat exchange...

Page 2: ...P N 4028610 7 5 Control Options 7 5 1 On Board Dehumidistat 7 5 2 External Control 8 5 2A DEH 3000R 8 5 2B Honeywell Remote Humidistat 9 6 Maintenance 9 7 Service 9 7 1 Warranty 9 7 2 Technical Description 9 7 3 Troubleshooting 10 7 4 Refrigerant Charging 11 7 5 Impeller Fan Replacement 11 7 6 Compressor Capacitor Replacement 12 7 6A Checking Compressor Motor Circuits 12 7 6B Replacing a Burned ou...

Page 3: ...th reduced physical sensory or mental capabilities or lack of experience or knowledge unless they have been given supervision or instruction concerning the use of the appliance by a person responsible for their safety Children should be supervised to ensure that they do not play with the appliance Never operate electrical equipment near or in standing water Do not stick your fingers or other objec...

Page 4: ...d air infiltration problems should be addressed 2 Registrations The Quest 155 conforms to CE standards 3 Specifications 26 7 C 60 RH 4037400 XX Quest 155 Blower 415 CFM 0 0 WG Power Watts 800 Supply voltage 230 VAC 1 Phase 50 Hz Current Draw Amps 3 5 Energy Factor L kWh 3 74 Operating Temp 5 C Min 35 C Max Water Removal L Day 71 Air Filter MERV 13 Size 41cm x 51cm x 5cm Drain Connection 3 4 Thread...

Page 5: ...th gravity flow Do not place the Quest Dehumidifier directly on structural building members without vibration absorbers or unwanted noise may result The Quest Dehumidifier may be suspended with steel hanger straps or a suitable alternative from structural members unit must be supported from underneath Don t hang from sides or ends Remember to place a drain pan under the unit if it is suspended abo...

Page 6: ... wrench to secure the drain port An optional condensate pump kit may be installed if a lift is required to dispose of the condensate The condensate pump kit can be ordered directly from the factory See the optional parts list for information on the kit When installing the drain hose make sure the feet are extended such that the dehumidifier is 7cm off the ground Then coil the drain hose under itse...

Page 7: ...877 420 1330 or go to www questhydro com product category accessories to order 5 Control Options The Quest Dehumidifier can be controlled by its on board dehumidistat or with an external control using its low voltage terminal block 5 1 On board dehumidistat The humidity control is an adjustable switch that closes when the relative humidity of the air in which it is located rises to the dial set po...

Page 8: ... 24V and DEHU terminals or turn the dehumidistat clockwise towards drier To turn the fan on make contact between 24V and FAN terminals To power a 24V HVAC accessory connect the accessory to the COM terminal and the 24V terminal NOTE 18 ga wire needed between the Quest dehumidifier and the external control Quest offers two external control options 5 2A DEH 3000R NOTE 22 ga wire needed for sensor Co...

Page 9: ... panel from the end of the Quest Dehumidifier The filter should be readily visible and can be removed by pulling it straight out of the Quest Dehumidifier At minimum we recommend changing the filter every 3 to 6 months 7 Service WARNING Servicing the Quest with its high pressure refrigerant system and high voltage circuitry presents a health hazard which could result in death serious bodily injury...

Page 10: ... from the accumulator and compresses it to a high pressure and temperature to repeat the process 7 3 Troubleshooting Neither fan nor compressor running Dehumidification is being called for No fan call 1 Unit unplugged or no power to outlet 2 Humidity control set too high 3 Loose connection in internal or control wiring 4 Defective Compressor relay 5 Defective control transformer Compressor is not ...

Page 11: ...ect the 24V and DEHU pigtails from the main unit together the compressor and impeller fan should run 4 If these tests work the main unit is working properly You should check the control panel and field control wiring for problems next 5 Remove the control panel from the mounting box and detach it from the field installed control wiring Connect the DEHU 24V and FAN terminals from the control panel ...

Page 12: ...the red and yellow wires from compressor terminals R S Using an ohmmeter check continuity between the points listed below 4 Compressor terminals C and S No continuity indicates an open start winding The compressor must be replaced Normal start winding resistance is 3 to 7 ohms 5 Compressor terminals C and R No continuity indicates an open run winding The compressor must be replaced Normal run wind...

Page 13: ...at caused the burn out Consult the factory for advice 6 Install the replacement compressor with a new capacitor and an oversized liquid line filter In a running burn out install an oversized suction line filter drier between the accumulator and compressor Thoroughly flush the accumulator with refrigerant to remove all trapped sludge and to prevent the oil hole from becoming plugged A standing burn...

Page 14: ... resume dehumidifying 7 8 Defrost Thermostat The defrost thermostat is attached to the refrigerant suction tube between the accumulator and the compressor It will automatically shut the compressor off if the low side refrigerant temperature drops due to excessive frost formation on the evaporator coil The impeller fan will continue to run causing air to flow through the evaporator coil and melt th...

Page 15: ... YEL 11 24 BLU 25 24V YEL 9 RED 14 15 RED 15 16 COM DEHU FAN DAMPER COMMON DEHUMIDISTAT WHT 22 24V BLU 2 BLU 19 BLU 23 GRN 17 GRN 12 BLU YEL 6 COMP RELAY BLOWER RELAY 3A BREAKER COMP RELAY RELAY RELAY COIL BLOWER RELAY COIL COIL COMP BLOWER DEFROST SWITCH XFMR LINE RED 5 RED 5 BLU 2 RED 14 RED 16 RED 13 GRN GRN 10 GRN 4 4038112 BLK 1 BRN 3 BRN BLK 7 BLK BLOWER CAPACITOR COMP CAPACITOR YEL 18 24 YE...

Page 16: ...ressor 4036967 1 Defrost Switch NOT SHOWN Item Part No Qty Description 7 4028254 1 Impeller 8 4033032 02 1 Capacitor Run 45 MFD 370V 9 4035235 01 1 Capacitor Fan 5 MFD 370V Dry 10 4020924 1 Relay SPDT 24V 15A 11 4022484 1 Relay SPST 24V 30A 12 4031406 1 XFMR 240V 50 60Hz 24V 40VA 4036559 1 Circuit Breaker NOT SHOWN 2 3 4 5 6 7 8 9 10 11 12 1 PART NO QTY DESCRIPTION 4036668 2 Bracket Hanging 2 Requ...

Page 17: ...1 877 420 1330 50Hz Quest 155 Installation Operation and Maintenance Instructions 17 www QuestClimate com info QuestClimate com ...

Page 18: ...eans The end user is responsible for normal care This warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or installation accident acts of nature or any other cause beyond Therma Stor LLC s reasonable control LIMITATIONS AND EXCLUSIONS If any Quest 155 Dehumidifier part is repai...

Page 19: ...nal es responsable por el cuidado normal Esta garantía no cubre cualquier defecto avería etc que resulte del uso indebido abuso falta de cuidado normal corrosión congelación manipulación modificación reparación o instalación no autorizada o indebida accidentes eventos naturales o cualquier otra causa más allá del control razonable de Therma Stor LLC LIMITACIONES Y EXENCIONES Si cualquier parte del...

Page 20: ...1 877 420 1330 Quest 155 de 50 Hz Instrucciones de instalación uso y mantenimiento 17 www QuestClimate com info QuestClimate com ...

Page 21: ...terruptor de descongelación NO MOSTRADO Artículo Nº de parte Cantidad Descripción 7 4028254 1 Propulsor 8 4033032 02 1 Condensador 45 MFD 370V 9 4035235 01 1 Condensador del ventilador 5 MFD 370V Seco 10 4020924 1 Relé SPDT 24V 15A 11 4022484 1 Relé SPST 24V 30A 12 4031406 1 XFMR 240V 50 60Hz 24V 40VA 4036559 1 Disyuntor NO MOSTRADO 2 3 4 5 6 7 8 9 10 11 12 1 Nº de parte Cantidad Descripción 40366...

Page 22: ...L 11 24 BLU 25 24V YEL 9 RED 14 15 RED 15 16 COM DEHU FAN DAMPER COMMON DEHUMIDISTAT WHT 22 24V BLU 2 BLU 19 BLU 23 GRN 17 GRN 12 BLU YEL 6 COMP RELAY BLOWER RELAY 3A BREAKER COMP RELAY RELAY RELAY COIL BLOWER RELAY COIL COIL COMP BLOWER DEFROST SWITCH XFMR LINE RED 5 RED 5 BLU 2 RED 14 RED 16 RED 13 GRN GRN 10 GRN 4 4038112 BLK 1 BRN 3 BRN BLK 7 BLK BLOWER CAPACITOR COMP CAPACITOR YEL 18 24 YEL 1...

Page 23: ...ato de descongelación El termostato de descongelación está ajustado al tubo de succión de refrigerante entre el acumulador y el compresor Apagará automáticamente el compresor si la temperatura del refrigerante del lado inferior cae debido a la formación excesiva de hielo en la bobina del evaporador El propulsor del ventilador continuará funcionando provocando que el aire fluya a través de la bobin...

Page 24: ...stema Varios cambios de líquido y filtro secador de succión serán necesarios para limpiar el sistema 5 Corrija la falla del sistema que causó el cortocircuito Consulte con la fábrica por consejos 6 I nstale el compresor de repuesto con un nuevo condensador y una mayor línea de filtrado de líquidos En un cortocircuito mientras funciona instale una mayor línea de filtrado secado entre el acumulador ...

Page 25: ...tilizando un voltímetro AC Si el voltaje es correcto siga al paso 3 Si no hay voltaje puede haber una conexión floja en el circuito del compresor Pruebe cada componente por continuidad Consulte la sección apropiada si sospecha de un defecto 3 Desconecte la unidad y luego desconecte los cables rojo y amarillo de las terminales R y S del compresor Utilizando un ohmímetro para comprobar la continuida...

Page 26: ...problema 1 Desconectar las conexiones de cableado de control de la unidad principal 2 Conecte entre sí las coletas 24V y FAN de la unidad principal debería funcionar sólo el ventilador Desconecte los cables 3 C onecte entre sí las coletas 24V y DEHU de la unidad principal sólo deberían funcionar el compresor y el propulsor 4 S i estas pruebas funcionan la unidad principal funciona correctamente Ah...

Page 27: ...l acumulador evita que el refrigerante líquido alcance el compresor El compresor evacúa el frío gas refrigerante del acumulador y lo comprime a alta presión y temperatura para repetir el proceso 7 3 Solución de problemas No funciona ningún ventilador o compresor Se requiere deshumidificación No funciona el ventilador 1 Unidad desconectada o toma corriente sin electricidad 2 Configuración de contro...

Page 28: ...rma innecesaria Para acceder al filtro de aire remueva el panel de acceso al filtro del extremo del deshumidificador Quest El filtro debería ser visible y puede removerse jalando directamente del Deshumidificador Quest Recomendamos como mínimo cambiar el filtro cada 3 6 meses 7 Inspección PRECAUCIÓN Inspeccionar el Quest con su sistema refrigerante de alta presión y circuito de alto voltaje repres...

Page 29: ...ntacto entre las terminales 24V y DEHU o gire el humidistato en contra de las agujas del reloj hacia seco Para encender el ventilador haga contacto entre las terminales 24V y FAN Para alimentar un accesorio 24V HVAC conecte el accesorio a la terminal COM y a la terminal 24V NOTA Se requiere un cable 18 ga entre el deshumidificador Quest y los controles externos Quest ofrece dos opciones de control...

Page 30: ...endedor llame al 1 877 420 1330 o ingrese a www questhydro com product category accessories para comprar 5 Opciones de controles El deshumidificador Quest puede controlarse mediante su humidistato integrado o con controles externos utilizando su terminal de bajo voltaje 5 1 Humidistato integrado El control de humedad es un interruptor ajustable que se cierra cuando la humedad relativa del aire en ...

Page 31: ...ara asegurar el drenaje Un equipo de bombeo de condensado opcional puede instalarse si se requiere elevación para eliminar el condensado El kit de bombeo de condensado puede encargarse directamente a la fábrica Consulte la lista de partes opcionales por información sobre el kit Al instalar la manguera de drenado asegúrese que las patas estén extendidas de tal manera que el deshumidificador esté 7c...

Page 32: ...e el deshumidificador Quest directamente sobre vigas estructurales del edificio sin absorbentes de vibración caso contrario podría resultar en sonido no deseado El deshumidificador Quest puede mantenerse elevado con ganchos tirantes de acero o con una alternativa adecuada desde las vigas estructurales la unidad debe sostenerse desde debajo No lo cuelgue desde los lados o extremos Recuerde colocar ...

Page 33: ...onarse 2 Registro El Quest 155 cumple con los estándares CE 3 Especificaciones a 26 7 C 60 HR Quest 155 4037400 XX Soplador 415 CFM a 0 0 WG Potencia Watts 800 Voltaje de entrada 230 VAC 1 Fase 50 Hz Consumo de corriente Amperes 3 5 Factor energético L kWh 3 74 Temperatura operacional Mínimo 5ºC Máximo 35ºC Remoción de agua l día 71 Filtro de aire MERV 13 Tamaño 41cm x 51cm x 5cm Conexión de drena...

Page 34: ...apacidades físicas sensoriales o mentales reducidas o con falta de experiencia o conocimiento a menos que hayan sido instruidos sobre el uso del dispositivo por una persona responsable de su seguridad Los niños deben estar bajo supervisión para asegurar que no jueguen con el dispositivo Nunca utilice equipo eléctrico cerca del o sobre el agua No inserte sus dedos u otros objetos a través de la rej...

Page 35: ...ciones de controles 7 5 1 Humidistato integrado 7 5 2 Controles externos 8 5 2A DEH 3000R 8 5 2B Humidistato Honeywell remoto 9 6 Mantenimiento 9 7 Inspección 9 7 1 Garantía 9 7 2 Descripción técnica 10 7 3 Solución de problemas 10 7 4 Carga de refrigerante 11 7 5 Reemplazar el propulsor del ventilador 12 7 6 Reemplazar el compresor condensador 12 7 6A Comprobar los circuitos del motor del compres...

Page 36: ...cciones de instalación uso y mantenimiento 4201 Lien Rd Teléfono 608 237 8400 Madison WI 53704 Línea gratuita 1 877 420 1330 www QuestClimate com info QuestClimate com Lea y conserve estas instrucciones Las especificaciones pueden cambiar sin previo aviso 1 TS 1052 Modificación B el 05 18 Quest 155 DE 50Hz Quest 155 de 50Hz Eficiencia líder en la industria Intercambiador de calor aire a aire optim...