 Installation and Operations Manual V1.4 Ramtech Electronics 2018

LED Codes

Base Station Warning Codes

The Base Station will alert you to various system faults using the codes below:

WES

3

 Troubleshooting Guide

Green LED 

Active units with no faults will flash their green LEDs once every 4 seconds 

to indicate that the unit is operational.

Amber LED 

Each WES

3

 unit monitors itself for a number of faults. These are indicated 

via the amber LED, which will flash in grouped patterns with longer than 

usual gaps in between them.

Units displaying one of these patterns require further investigation and 

should not be relied upon as part of the fire alarm and detection system 

until the fault has been corrected. Use the chart below to determine the 

nature of the issue:

Warning Code

Warning

Description

Self-Clearing

SMS Setting

MED

Medical Alert

Medical assistance required at Unit NNN

No

8

BAT

Low Battery

Unit NNN has a low battery

No

5

DET

Detector Tamper

Unit NNN has had detector head removed

Yes

3

EXT

External Tamper

Unit NNN has been removed from wall/ceiling

Yes

4

FLT

Flat Battery

Unit NNN has turned off, its battery is flat

No

5

INT

Internal Tamper

Unit NNN has been opened

No

2

LAT

Latched

Call point button on unit NNN is still depressed

Yes

10

REM

Removed 

Unit NNN has been deactivated and removed

No

9

SIG

Low Signal

Unit NNN has a low radio signal

Yes

6

TST

System Test

Unit NNN initiated a System test

Yes

7

NEW

Unexpected Unit

Unit NNN added since last system poll

No

Via WES App

GON

Unit Missing

Unit NNN removed since last system poll

No

Via WES App

Group Flash 1 - Low Battery

Group Flash 2 - Low signal

Group Flash 3 - Unpaired

Group Flash 4 - Tamper

Group Flash 5 - Re-arm or Unit latched

If a detector has raised the alarm, its red LED indicator will flash during a fire 

alarm.

It is recommended that the fire system is tested weekly or whenever a 

significant change has been made to the installation or the building under 

construction. WES

3

 is equipped with a system test function that allows you to 

test the radio link between units without activating an audible fire alarm. 

You can therefore ensure each unit in the system has a robust radio link with 

sufficient capacity to allow for environmental fluctuations without disturbing 

the site.