Installation and Operations Manual V1.4 Ramtech Electronics 2018
LED Codes
Base Station Warning Codes
The Base Station will alert you to various system faults using the codes below:
WES
3
Troubleshooting Guide
Green LED
Active units with no faults will flash their green LEDs once every 4 seconds
to indicate that the unit is operational.
Amber LED
Each WES
3
unit monitors itself for a number of faults. These are indicated
via the amber LED, which will flash in grouped patterns with longer than
usual gaps in between them.
Units displaying one of these patterns require further investigation and
should not be relied upon as part of the fire alarm and detection system
until the fault has been corrected. Use the chart below to determine the
nature of the issue:
Warning Code
Warning
Description
Self-Clearing
SMS Setting
MED
Medical Alert
Medical assistance required at Unit NNN
No
8
BAT
Low Battery
Unit NNN has a low battery
No
5
DET
Detector Tamper
Unit NNN has had detector head removed
Yes
3
EXT
External Tamper
Unit NNN has been removed from wall/ceiling
Yes
4
FLT
Flat Battery
Unit NNN has turned off, its battery is flat
No
5
INT
Internal Tamper
Unit NNN has been opened
No
2
LAT
Latched
Call point button on unit NNN is still depressed
Yes
10
REM
Removed
Unit NNN has been deactivated and removed
No
9
SIG
Low Signal
Unit NNN has a low radio signal
Yes
6
TST
System Test
Unit NNN initiated a System test
Yes
7
NEW
Unexpected Unit
Unit NNN added since last system poll
No
Via WES App
GON
Unit Missing
Unit NNN removed since last system poll
No
Via WES App
Group Flash 1 - Low Battery
Group Flash 2 - Low signal
Group Flash 3 - Unpaired
Group Flash 4 - Tamper
Group Flash 5 - Re-arm or Unit latched
If a detector has raised the alarm, its red LED indicator will flash during a fire
alarm.
It is recommended that the fire system is tested weekly or whenever a
significant change has been made to the installation or the building under
construction. WES
3
is equipped with a system test function that allows you to
test the radio link between units without activating an audible fire alarm.
You can therefore ensure each unit in the system has a robust radio link with
sufficient capacity to allow for environmental fluctuations without disturbing
the site.