Summary of Contents for PM3000

Page 1: ...r PM3000 Recommended Read through this short guide before configuring your PM3000 Synergy Systems Inc 4101 Pierce Drive Shelby Township MI 48316 PH 800 338 4505 Fax 248 656 6078 Email sales synergy mi com www powerqualityrecorders com ...

Page 2: ... chosen configuration To load your config touch Continue Next Configure Available Configs Scroll down and select your config then click on Load 4 Hook up your logger Next hook up your logger using the hook up visual on the touch screen or PMScreen for reference To reach it touch the back arrow then Hook up for the correct hook up visual 5 Start recording Once set up on your touch screen or PMScree...

Page 3: ... Timings Memory Mode Length of recording 1 sec to as long as you like FIFO First In First Out FIFO Recycle mode Delayed Start Data to be Captured Detailed recording method Adaptive Store Point Store Detailed recording channels functions to be recorded in detail Flicker intervals short term 1 15 min long term 1 168 hrs Alarms High and Low alarms Option available in PM3000HF models only 3 ...

Page 4: ...re Delta 3el 500 A 16 channels p 13 3ø 3el 33kV THD Flkr 7day 3 Phase 3 Wire Delta 3el 500 A 16 channels p 14 3ø 3w D Pwr 7day 3 Phase 3 Wire Delta 3000 A 8 channels p 15 3ø 4w Y 3V 3I 7day 3 Phase 4 Wire Wye 3000 A 6 channels p 16 3ø 4w Y 3V 3I 14day 3 Phase 4 Wire Wye 3000 A 6 channels p 17 3ø 4w Y 3V only 7day 3 Phase 4 Wire Wye 3000 A 3 channels p 18 3ø 4w Y Flkr 7day 3 Phase 4 Wire Wye 3000 A...

Page 5: ...480 0 2 Il 1000 Amps 1000 0 3 V2 480 Volts 480 0 4 I2 1000 Amps 1000 0 5 Vne 480 Volts 480 0 6 I3 1000 Amps 1000 0 Alarms None 1ø 1V 7day 5 Hook Up Single Phase Channel Functions Input Channels 1 Vln 0 to 480 Vac 2 Il 0 to 3000 Aac Rogowski 3 V2 0 to 480 Vac 4 I2 0 to 3000 Aac Rogowski 5 Vne 0 to 480 Vac 6 I3 0 to 3000 Aac Rogowski Detailed Math Channels 1 RMS of Signal Vln Vac 2 16 Unspecified ...

Page 6: ...Off 7 Pst 1 00Off 8 Plt 0 80Off 16 Hz 50 50 49 50 Hook Up Single Phase Channel Functions Input Channels 1 Vln 0 to 480 Vac 2 Il 0 to 400 Aac Rogowski 3 V2 0 to 480 Vac 4 I2 0 to 400 Aac Rogowski 5 Vne 0 to 480 Vac 6 I3 0 to 400 Aac Rogowski Detailed Math Channels 1 RMS of Signal Vln Vac 2 RMS of Signal Ia Aac 3 THD Traditional of Signal Van 4 Value all Harmonics of Signal Ia Aac 5 Flicker sensatio...

Page 7: ...ps 1000 0 Alarms None Hook Up Single Phase Channel Functions Input Channels 1 Vln 0 to 480 Vac 2 Il 0 to 3000 Aac Rogowski 3 V2 0 to 480 Vac 4 I2 0 to 3000 Aac Rogowski 5 Vne 0 to 480 Vac 6 I3 0 to 3000 Aac Rogowski Detailed Math Channels 1 RMS of Signal Vln Vac 2 RMS of Signal Il Aac 3 THD Traditional of Signal Vln 4 Value all Harmonics of Signal Il Aac 5 Real Power V A ChVln ChIl 1000 kW 6 React...

Page 8: ...2 Phase 2 Element Wye Channel Functions Input Channels 1 Van 0 to 480 Vac 2 Ia 0 to 3000 Aac Rogowski 3 Vbn 0 to 480 Vac 4 Ib 0 to 3000 Aac Rogowski 5 V3 0 to 480 Vac 6 I3 0 to 3000 Aac Rogowski Detailed Math Channels 1 RMS of Signal Van Vac 2 RMS of Signal Vbn Vac 3 Unspecified 4 RMS of Signal Ia Aac 5 RMS of Signal Ib Aac 6 Unspecified 7 2 Phase 3 Wire Real Power Inputs 1 2 3 4 kW 8 2 Phase 3 Wi...

Page 9: ...80 Volts 480 0 6 Ic 1000 Amps 1000 0 Alarms None Hook Up 3 Phase 1 Element Wye Channel Functions Input Channels 1 Vab 0 to 480 Vac 2 I1 0 to 3000 Aac Rogowski 3 V2 0 to 480 Vac 4 I2 0 to 3000 Aac Rogowski 5 V3 0 to 480 Vac 6 Ic 0 to 3000 Aac Rogowski Detailed Math Channels 1 RMS of Signal Vab Vac 2 5 Unspecified 6 RMS of Signal Ic Aac 7 3 Phase 1 Element Real Power Inputs 1 6 kW 8 3 Phase 1 Elemen...

Page 10: ...ne Hook Up 3 Phase 2 5 Element Wye Channel Functions Input Channels 1 Van 0 to 480 Vac 2 Ia 0 to 3000 Aac Rogowski 3 Vbn 0 to 480 Vac 4 Ib 0 to 3000 Aac Rogowski 5 V3 0 to 480 Vac 6 Ic 0 to 3000 Aac Rogowski Detailed Math Channels 1 RMS of Signal Van Vac 2 RMS of Signal Vbn Vac 3 Unspecified 4 RMS of Signal Ia Aac 5 RMS of Signal Ib Aac 6 RMS of Signal Ic Aac 7 3 Phase 2 5 Element Real Power Input...

Page 11: ...50 50 49 50 Hook Up 3 Phase 3 Wire Delta 3el Channel Functions Input Channels 1 Vab 0 to 480 Vac 2 Ia 0 to 500 Aac 0 500 mV 3 Vbc 0 to 480 Vac 4 Ib 0 to 500 Aac 0 500 mV 5 Vca 0 to 480 Vac 6 Ic 0 to 500 Aac 0 500 mV Detailed Math Channels 1 RMS of Signal Vab kV 2 RMS of Signal Vbc kV 3 RMS of Signal Vca kV 4 RMS of Signal Ia Aac 5 RMS of Signal Ib Aac 6 RMS of Signal Ic Aac 7 Flicker sensation on ...

Page 12: ...0 80 Off 16 Hz 50 50 49 50 Hook Up 3 Phase 3 Wire Delta 3el Channel Functions Input Channels 1 Vab 0 to 480 Vac 2 Ia 0 to 500 Aac 0 500 mV 3 Vbc 0 to 480 Vac 4 Ib 0 to 500 Aac 0 500 mV 5 Vca 0 to 480 Vac 6 Ic 0 to 500 Aac 0 500 mV Detailed Math Channels 1 RMS of Signal Vab kV 2 RMS of Signal Vbc kV 3 RMS of Signal Vca kV 4 RMS of Signal Ia Aac 5 RMS of Signal Ib Aac 6 RMS of Signal Ic Aac 7 THD Tr...

Page 13: ...50 49 50 Hook Up 3 Phase 3 Wire Delta 3el Channel Functions Input Channels 1 Vab 0 to 480 Vac 2 Ia 0 to 500 Aac 0 500 mV 3 Vbc 0 to 480 Vac 4 Ib 0 to 500 Aac 0 500 mV 5 Vca 0 to 480 Vac 6 Ic 0 to 500 Aac 0 500 mV Detailed Math Channels 1 RMS of Signal Vab kV 2 RMS of Signal Vbc kV 3 RMS of Signal Vca kV 4 RMS of Signal Ia Aac 5 RMS of Signal Ib Aac 6 RMS of Signal Ic Aac 7 Flicker sensation on Vab...

Page 14: ...50 50 49 50 Hook Up 3 Phase 3 Wire Delta 3el Channel Functions Input Channels 1 Vab 0 to 480 Vac 2 Ia 0 to 500 Aac 0 500 mV 3 Vbc 0 to 480 Vac 4 Ib 0 to 500 Aac 0 500 mV 5 Vca 0 to 480 Vac 6 Ic 0 to 500 Aac 0 500 mV Detailed Math Channels 1 RMS of Signal Vab kV 2 RMS of Signal Vbc kV 3 RMS of Signal Vca kV 4 RMS of Signal Ia Aac 5 RMS of Signal Ib Aac 6 RMS of Signal Ic Aac 7 THD Traditional of Si...

Page 15: ...Delta Channel Functions Input Channels 1 Vab 0 to 480 Vac 2 Ia 0 to 3000 Aac Rogowski 3 V2 0 to 480 Vac 4 I2 0 to 3000 Aac Rogowski 5 Vcb 0 to 480 Vac 6 Ic 0 to 3000 Aac Rogowski Detailed Math Channels 1 RMS of Signal Vab Vac 2 Unspecified 3 RMS of Signal Vcb Vac 4 RMS of Signal Ia Aac 5 Unspecified 6 RMS of Signal Ic Aac 7 3 Phase 3 wire YD Real Power Inputs 1 2 3or5 6 kW 8 3 Phase 3 wire YD Reac...

Page 16: ... Volts 480 0 6 Ic 1000 Amps 1000 0 Alarms On Alarm Values High Low 1 Vac 253 0 216 2 2 Vac 253 0 216 2 3 Vac 253 0 216 2 Hook Up 3 Phase 4 Wire Wye Channel Functions Input Channels 1 Van 0 to 480 Vac 2 Ia 0 to 3000 Aac Rogowski 3 Vbn 0 to 480 Vac 4 Ib 0 to 3000 Aac Rogowski 5 Vcn 0 to 480 Vac 6 Ic 0 to 3000 Aac Rogowski Detailed Math Channels 1 RMS of Signal Van Vac 2 RMS of Signal Vbn Vac 3 RMS o...

Page 17: ...0 Volts 480 0 6 Ic 1000 Amps 1000 0 Alarms On Alarm Values High Low 1 Vac 253 0 216 2 2 Vac 253 0 216 2 3 Vac 253 0 216 2 Hook Up 3 Phase 4 Wire Wye Channel Functions Input Channels 1 Van 0 to 480 Vac 2 Ia 0 to 3000 Aac Rogowski 3 Vbn 0 to 480 Vac 4 Ib 0 to 3000 Aac Rogowski 5 Vcn 0 to 480 Vac 6 Ic 0 to 3000 Aac Rogowski Detailed Math Channels 1 RMS of Signal Van Vac 2 RMS of Signal Vbn Vac 3 RMS ...

Page 18: ...0 0 4 Ib 1000 Amps 1000 0 5 Vcn 480 Volts 480 0 6 Ic 1000 Amps 1000 0 Alarms On Alarm Values High Low 1 Vac 253 0 216 2 2 Vac 253 0 216 2 3 Vac 253 0 216 2 Hook Up 3 Phase 4 Wire Wye Channel Functions Input Channels 1 Van 0 to 480 Vac 2 Ia 0 to 3000 Aac Rogowski 3 Vbn 0 to 480 Vac 4 Ib 0 to 3000 Aac Rogowski 5 Vcn 0 to 480 Vac 6 Ic 0 to 3000 Aac Rogowski Detailed Math Channels 1 RMS of Signal Van ...

Page 19: ... 80 Off Hook Up 3 Phase 4 Wire Wye Channel Functions Input Channels 1 Van 0 to 480 Vac 2 Ia 0 to 3000 Aac Rogowski 3 Vbn 0 to 480 Vac 4 Ib 0 to 3000 Aac Rogowski 5 Vcn 0 to 480 Vac 6 Ic 0 to 3000 Aac Rogowski Detailed Math Channels 1 RMS of Signal Van Vac 2 RMS of Signal Vbn Vac 3 RMS of Signal Vcn Vac 4 RMS of Signal Ia Aac 5 RMS of Signal Ib Aac 6 RMS of Signal Ic Aac 7 Flicker sensation on Van ...

Page 20: ...5 Plt 0 80 Off 16 Hz 50 50 49 50 Hook Up 3 Phase 4 Wire Wye Channel Functions Input Channels 1 Van 0 to 480 Vac 2 Ia 0 to 3000 Aac Rogowski 3 Vbn 0 to 480 Vac 4 Ib 0 to 3000 Aac Rogowski 5 Vcn 0 to 480 Vac 6 Ic 0 to 3000 Aac Rogowski Detailed Math Channels 1 RMS of Signal Van Vac 2 RMS of Signal Vbn Vac 3 RMS of Signal Vcn Vac 4 RMS of Signal Ia Aac 5 RMS of Signal Ib Aac 6 RMS of Signal Ic Aac 7 ...

Page 21: ...6 2 7 8 0 Off 8 8 0 Off 9 8 0 Off Hook Up 3 Phase 4 Wire Wye Channel Functions Input Channels 1 Van 0 to 480 Vac 2 Ia 0 to 3000 Aac Rogowski 3 Vbn 0 to 480 Vac 4 Ib 0 to 3000 Aac Rogowski 5 Vcn 0 to 480 Vac 6 Ic 0 to 3000 Aac Rogowski Detailed Math Channels 1 RMS of Signal Van Vac 2 RMS of Signal Vbn Vac 3 RMS of Signal Vcn Vac 4 RMS of Signal Ia Aac 5 RMS of Signal Ib Aac 6 RMS of Signal Ic Aac 7...

Page 22: ...ac Rogowski 3 Vbn 0 to 480 Vac 4 Ib 0 to 3000 Aac Rogowski 5 Vcn 0 to 480 Vac 6 Ic 0 to 3000 Aac Rogowski Detailed Math Channels 1 RMS of Signal Van Vac 2 RMS of Signal Vbn Vac 3 RMS of Signal Vcn Vac 4 RMS of Signal Ia Aac 5 RMS of Signal Ib Aac 6 RMS of Signal Ic Aac 7 Displacement Power Factor V A Van Ia PF 8 Displacement Power Factor V A Vbn Ib PF 9 Displacement Power Factor V A Vcn Ic PF 10 R...

Page 23: ... 4 Ib 0 to 3000 Aac Rogowski 5 Vcn 0 to 480 Vac 6 Ic 0 to 3000 Aac Rogowski Detailed Math Channels 1 RMS of Signal Van Vac 2 RMS of Signal Vbn Vac 3 RMS of Signal Vcn Vac 4 RMS of Signal Ia Aac 5 RMS of Signal Ib Aac 6 RMS of Signal Ic Aac 7 3 Phase 4 wire Real Power Inputs 1 2 3 4 5 6 kW 8 3 Phase 4 wire Reactive Power Inputs 1 2 3 4 5 6 kVr 9 3 Phase 4 wire Apparent Power Inputs 1 2 3 4 5 6 kVA ...

Page 24: ...c Rogowski 3 Vbn 0 to 480 Vac 4 Ib 0 to 3000 Aac Rogowski 5 Vcn 0 to 480 Vac 6 Ic 0 to 3000 Aac Rogowski Detailed Math Channels 1 RMS of Signal Van Vac 2 RMS of Signal Vbn Vac 3 RMS of Signal Vcn Vac 4 RMS of Signal Ia Aac 5 RMS of Signal Ib Aac 6 RMS of Signal Ic Aac 7 Real Power Factor V A Van Ia PF 8 Real Power Factor V A Vbn Ib PF 9 Real Power Factor V A Vcn Ic PF 10 3 Phase 4 wire Real Power ...

Page 25: ...ts 480 0 4 I2 1000 Amps 1000 0 5 V3 480 Volts 480 0 6 I3 1000 Amps 1000 0 Alarms None Hook Up Uncommitted Channel Functions Input Channels 1 V1 0 to 480 Vac 2 I1 0 to 3000 Aac Rogowski 3 V2 0 to 480 Vac 4 I2 0 to 3000 Aac Rogowski 5 V3 0 to 480 Vac 6 I3 0 to 3000 Aac Rogowski Detailed Math Channels 1 RMS of Signal V1 Vac 2 RMS of Signal V2 Vac 3 RMS of Signal V3 Vac 4 RMS of Signal I1 Aac 5 RMS of...

Page 26: ...nels 1 V1 0 to 480 Vac 2 I1 0 to 3000 Aac Rogowski 3 V2 0 to 480 Vac 4 I2 0 to 3000 Aac Rogowski 5 V3 0 to 480 Vac 6 I3 0 to 3000 Aac Rogowski Detailed Math Channels 1 RMS of Signal V1 Vac 2 RMS of Signal V2 Vac 3 RMS of Signal V3 Vac 4 RMS of Signal I1 Aac 5 RMS of Signal I2 Aac 6 RMS of Signal I3 Aac 7 Flicker sensation on V1 Pfs 8 Flicker sensation on V2 Pfs 9 Flicker sensation on V3 Pfs 10 Fli...

Page 27: ...Amps 1000 0 5 V3 480 Volts 480 0 6 I3 1000 Amps 1000 0 Alarms None Hook Up Uncommitted Channel Functions Input Channels 1 V1 0 to 480 Vac 2 I1 0 to 3000 Aac Rogowski 3 V2 0 to 480 Vac 4 I2 0 to 3000 Aac Rogowski 5 V3 0 to 480 Vac 6 I3 0 to 3000 Aac Rogowski Detailed Math Channels 1 RMS of Signal V1 Vac 2 RMS of Signal V2 Vac 3 RMS of Signal V3 Vac 4 6 Unspecified 7 3 Phase Volts NPS PPS ratio Inpu...