Plasterboard Installation Instructions I        November 2017        © Malcolm Ravenscroft Ltd      www.ravenscroft.co.nz  
All Rights Reserved, NZ Patent No. 328088 , Australian Patent No. 730742 

BSD-PW Fire Damper 

         Plasterboard Wall  

               Installation Instructions 

 

Important: 

 

The  following  instructions  refer  to  mounting  the  BSD-PW  fire  damper  in  plasterboard  (Gib)  wall 
applications. 

AS1682.2-1990  requires  fire  dampers  to  be  installed  in  the  same  method  as 

tested

. These installation details are derived from the test. 

 

The Australian & NZ Building Codes require fire dampers to comply with AS 1682-1990 Part 1 & 2, 
and  AS1530.4-1990  as  the  Acceptable  solution.  The  BSD-PW  complies  with  the  Australian  &  NZ 
Building  Codes  as  an  Alternative  solution  (incorporating  AS1682  as  a  guideline).  Verification  as 
follows: 

BRANZ  Test  No.  FP2376  results  confirm  the  plasterboard  mounting  system  for  the 

BSD-PW will satisfy AS1530.4 -1990 for 120 minutes.

 

BSD-C fire dampers have been tested for installation in masonry walls & floors overseas and have 
achieved  a  fire  rating  of  2  hours.  Refer  to  Ravenscroft’s  for  further  detail.  Separate  installation 
instructions  are  available  for  concrete/masonry  wall  options.  Do  not  use  the  BSD-PW  for  ceilings 
without consultation with Ravenscroft’s. 

Wall & Hole Preparation Instructions: 

  The  BSD-PW  fire  damper  unit  mounts  into  a  wall  cavity  hole  and  is  secured  with 

approved 

fasteners only.

 Supporting framework within the wall cavity is not required

. The BSD-PW can 

also be fastened to both the wall framing and plasterboard. This is recommended where possible 
to insure a more robust installation. 

  The 400 BSD-PW have mounting flanges sized to overlap a 600 mm stud spacing. The damper 

would then screw directly into the studs with intermediate fasteners into plasterboard. 

  When checking the location of the duct penetration, check that there is 

adequate space

 for the 

flanges and where the framing is. Refer to the following table for damper, hole and flange sizes. 

BSD-PW 
Size 

Hole 
Diameter 

Square Flange 
Size 

BSD-PW 
Size 

Hole 
Diameter 

Square  
Flange Size 

125 

165 

225 

250 

290 

350 

150 

190 

250 

300 

340 

410 

175 

215 

275 

400 

440 

650 

200 

240 

300 

 

 

 

  Use the radius guide provided to mark from the hole centre outwards to the hole diameter. Also 

mark the diameter of flange corner fastener holes. This is important to ensure the damper can be 
located in the centre of the hole with a concentric expansion space all around.  

  Once the damper centre location is found, use a 

long

 drill to mark the centre of 

both

 sides of the 

wall  simultaneously.    This  damper  flange  system  will  not  accommodate  any  misalignment.  It  is 
therefore very important that the 

centre pilot holes are drilled perpendicular to the wall

  Holes  must  be 

cut  accurately

  with  a  jig  saw  or  a  key  hole  saw.  The  hole  sizes  listed  include 

suitable clearance for expansion. Holes of excessive size will not comply with Standards as the 
flange may not overlap the hole sufficiently. 

  Remove the loose flange from the unit. Insert the damper through the hole and fit the flange over 

the spigot protruding from the other side. Mark the flange location and rivet holes on the damper 
body.  

  To

 prevent damage

 to the wall board, remove the damper from the wall to drill rivet holes. 

  It is much easier and cleaner to 

check 

the holes are correct by refitting the damper to the wall at 

this stage before the fire mastic sealant is applied. 

  You are now ready to apply fire mastic sealant and fix the damper to the wall. 

 

 