background image

Inside US: +1 (877) 432-9908

Bulletin No. G12-H

Outside US: +1 (717) 767-6511

Drawing No. LP0910

www.redlion.net

Revised  2019-08-30

-1-

Model G12 - Graphite®  12" Color Touchscreen Operator Interface Terminal 

C

US LISTED

UL

R

IND. CONT. EQ.

E302106

FOR USE IN HAZARDOUS LOCATIONS: 

Class I, Division 2, Groups A, B, C, and D 

Class II, Division 2, Groups F and G 

Class III, Division 2
T4

C

US

UL

R

LISTED

IND.CONT. EQ.

E317425

II 3 G Ex ic nA IIC T4 Gc
II 3 D Ex tc IIIC T135°C Dc
-20°C ≤ T

AMB

 ≤ 60°C

DEMKO 14 ATEX 1387X
IECEx UL 15.0035X

See the Red Lion website at www.redlion.net for full user manual, 
Crimson

®

 software and software manual.

SAFETY SUMMARY

All safety related regulations, local codes and instructions that appear

in  the  manual  or  on  equipment  must  be  observed  to  ensure  personal
safety  and  to  prevent  damage  to  either  the  instrument  or  equipment
connected  to  it.  If  equipment  is  used  in  a  manner  not  specified  by  the
manufacturer,  the  protection  provided  by  the  equipment  may  be
impaired.

Do not use the controller to directly command motors, valves, or other

actuators  not  equipped  with  safeguards.  To  do  so  can  be  potentially
harmful to persons or equipment in the event of a fault to the unit.

ORDERING INFORMATION

SPECIFICATIONS

Must use a Class 2 circuit according to National Electrical Code (NEC),

NFPA-70  or  Canadian  Electrical  Code  (CEC),  Part  I,  C22.1  or  a
Limited  Power  Supply  (LPS)  according  to  IEC/EN  60950-1  or
Limited-energy circuit according to IEC/EN 61010-1.
Power connection via removable three position terminal block.

BATTERY: 

Lithium coin cell. Typical lifetime of 6 years nominal.

To  maintain  UL  rating,  replacement  battery  must  be:  Rayovac

BR2032-BA or Panasonic BR2032.

WARNING - EXPLOSION HAZARD - DO NOT D
EQUIPMENT UNLESS POWER HAS BEEN SW
OR AREA IS KNOWN TO BE NON-HAZARDOU

CAUTION: Risk of Danger.

Read complete instructions prior to installation 
and operation of the unit.

WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT 
EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF 
OR AREA IS KNOWN TO BE NON-HAZARDOUS.

WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT 
EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF 
OR AREA IS KNOWN TO BE NON-HAZARDOUS.

WARNING - EXPLOSION HAZARD - SUBSTITUTION OF 
COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, 
DIVISION 2.

DESCRIPTION

PART NUMBER

12" Color Touch Screen, Indoor Use

G12C0000

12" Color Touch Screen, Indoor Use, Additional Ethernet and 
Serial Port

G12C1100

12” Color Touch Screen, Outdoor Use, Additional Ethernet and 
Serial Port

G12S1100

POWER:

G12C

G12S

Input Voltage (V)

10

24

30

10

24

30

Typical Power HMI only (W):

13 

14 

15 

16

17

17

Maximum Power HMI only (W):

19 

20 

20 

22

22

23

Available Power for Modules (W):

33 

33

Max Power HMI With Module(s) (W):

52 

54 

55 

56

57

57

12.10 (307.3)

8.20

(208.3)

2.06 (52.4)

8.4

(215)

(MOUNTING CLIPS INSTALLED)

12.3 (314)

2.97 (76)

Module sold

separately

DIMENSIONS In inches (mm)