The Reliable Automatic Sprinkler Co., Inc.,
103 Fairview Park Drive, Elmsford, New York 10523
Model KFR56 Series
Quick Response
Standard Spray
Bulletin 036
Bulletin 036
Model KFR56 Sprinkler Types
Standard Upright
Standard Pendent
Horizontal Sidewall
Model KFR56 Recessed Sprinkler Types
Recessed Pendent F1/F2/FP
Recessed Horizontal Sidewall F1/F2/FP
Model KFR56 Concealed Sprinkler Types
Concealed Pendent CCP
Listing & Approvals
1. Underwriters Laboratories Inc. and Certified for
Canada (cULus)(All orientations).
2. Factory Mutual Approvals (FM) - (Pendent & Recessed
Pendent at current time).
UL Listing Category
Sprinklers, Automatic & Open (VNIV)
Quick Response Sprinkler
Product Description
Reliable Model KFR56 Series Sprinklers are quick re-
sponse sprinklers which combine the durability of a stan-
dard sprinkler with the attractive low profile of a decorative
sprinkler.
The automatic sprinklers utilize a soldered link and
have demonstrated response times in laboratory tests
which are five to ten times faster than standard response
sprinklers. This quick response enables these sprinklers
to apply water to a fire much faster than standard sprin-
klers of the same temperature rating.
The temperature rating of the sprinkler is identified by
marking on deflector: for visual temperature identifica-
tion, the 212°F soldered links are factory marked with
green stripe as shown in Figure 1.
Application
Quick response sprinklers are used in fixed fire protec-
tion systems: Wet, Dry or Preaction. Care must be exer-
cised that the orifice size, temperature rating, deflector
style and sprinkler type are in accordance with the latest
published standards of the National Fire Protection As-
sociation or the approving Authority Having Jurisdiction
(AHJ). Models KFR56 sprinklers are intended for instal-
lation as specified in NFPA 13 in both light and ordinary
Hazard applications. Quick response sprinklers and
standard response sprinklers should not be intermixed.
Pendent
Recessed
Pendent/F1/F2
Upright
Horizontal Sidewall
(HSW)
Recessed
Horizontal Sidewall F1/F2
Recessed
Pendent/FP
CCP Concealed
Pendent
Recessed
Horizontal Sidewall FP
(HSW)
Installation
Quick response sprinklers are intended for installation
as specified in NFPA 13. Quick response sprinklers and
standard response sprinklers should not be intermixed.
The Model KFR56 Recessed Quick Response Sprin-
klers are to be installed as shown. The Model F1, F2 & FP
Escutcheons illustrated are the only recessed escutch-
eons to be used with the Model KFR56 Sprinklers. The
use of any other recessed escutcheon will void all ap-
provals and negate all warranties.