Model XL Commercial Horizontal Sidewall
Sprinkler
Model XL Commercial Pendent Sprinkler
Flat
Conical
Features
•
Quick response performance
•
Commercial applications
•
Listed for light and ordinary hazards
Product Description
The Model XL Commercial is a quick response sprinkler with
a fusible solder link thermal element designed for standard
coverage applications.
The flush style of this sprinkler conceals all operating parts
with the exception of the heat sensing link. When the solder
of the sensing link melts the operating mechanism releases
and allows the deflector to be extended for distributing water.
These sprinklers are listed for a maximum service pressure of
175 psi (12.0 bar).
Installation
Care must be exercised that orifice size, temperature rating,
and sprinkler spacing are in accordance with this bulletin
and the latest published standards of the National Fire
Protection Association, and approved by the Authority Having
Jurisdiction.
Apply a PTFE-based thread sealant or thread sealant tape to
the sprinkler threads. Using the Model ZX-Pendent or ZX-
Sidewall Wrench (see figure 2), install the sprinkler into the
fitting and verify the sprinkler is properly oriented.
Recommended installation torque is 8-14 lb-ft (11-19 N
.
m).
Do not tighten sprinklers over the maximum recommended
torque. Exceeding the maximum recommend torque may
cause leakage or impairment of the sprinklers.
Shipping caps should be removed only after walls are
finished and when escutcheons are being installed. Each
installed sprinkler must include an escutcheon, and only
the escutcheons shown in this bulletin shall be used with
the Model XL Commercial sprinkler. The use of any other
escutcheon will void all approvals and negate all warranties.
www.reliablesprinkler.com
Model XL Commercial Pendent Sprinkler Summary
Table A
Sprinkler Model
Orientation
Listing or
Approval
Max. Working Pressure
psi (bar)
Sprinkler Identification
Number (SIN)
XL Commercial
Pendent, Flush
cULus, LPCB
175 (12.0)
R4514
Horizontal
Sidewall, Flush
R4534
Use care to avoid damaging the sprinklers before, during and
after installation. Inspect all installed sprinklers to insure that
they have not been damaged. Replace all sprinklers which
have any sign of damage.
cULus Listed, LPCB
Model XL Quick Response
Commercial Sprinklers
Bulletin 145 October 2020