User Manual  

WP Web HMI Series

®

 

 

 

 

 

 

 
 

 

 

 

Summary of Contents for WP Web HMI Series

Page 1: ...User Manual WP Web HMI Series ...

Page 2: ...RODUCT NOMENCLATURE ORDERING PART NUMBER 8 DISPLAY SPECIFICATIONS 8 CPU MEMORY AND POWER SUPPLY 9 POWER RATING 9 COMMUNICATION INTERFACES 10 RJ45 ETHERNET PORT 10 USB SLAVE PORT 10 USB HOST PORT 11 DEFAULT PRODUCT SETTINGS 11 ENVIRONMENTAL SPECIFICATIONS AND APPROVALS 11 POWERING UP THE WP WEB HMI SERIES 12 GETTING STARTED WITH THE WEB HMI 12 MAIN SETTINGS 12 ENTERING INTO DEVICE SETTINGS 12 ADMIN...

Page 3: ...user should check and confirm the suitability of the product before using in any specific application The diagrams and examples in this manual are included for illustration purposes only RENU Electronics assume no responsibility or liability regarding actual use based on the diagrams or examples shown Reproduction of the contents of this manual in any form in part or in whole is strictly prohibite...

Page 4: ...ust be used for any emergency stop operations Do not use the external power supply source that does not comply with the specified power requirements of the product it may cause malfunction or permanent damage to the product Do not attempt to open dismantle or modify the product doing so will void the warranty This product is supplied as open type equipment and it must be mounted within an enclosur...

Page 5: ...support and proper sealing against water and dust The panel surface must be flat devoid of any imperfection to maintain adequate seal and IP rating The maximum panel thickness on which this HMI can be mounted is 6mm 0 2mm Panel Cutout Dimensions Model Height mm Width mm WP6043TN 80 111 WP6070TN 127 175 WP6101TN 178 256 ATTENTION ATTENTION Panel cutout Before cutting out the panel disconnect all el...

Page 6: ... RENU Electronics Pvt Ltd Page 6 of 22 WP6070TN WP6101TN ...

Page 7: ...se sealing compounds Place the unit in the panel cutout and tighten the mounting screws evenly torque 0 4Nm to maintain water and dust resistance ATTENTION ATTENTION Mounting Web HMI on Panel Do not push directly on the LCD display of the HMI when placing the unit into the panel as it may damage the display Push on the bezel or the border of the LCD display Connecting Power Web HMI series require ...

Page 8: ...ormation is as follows Display Specifications Web HMI series products support high quality color TFT display range Size 4 3 Color TFT WQVGA Web Panel Analog Resistive Touch Screen Resolution 480 x 272pixels Colors 16M Brightness 400cd m2 Backlight life 30 000Hrs Size 7 Color TFT WVGA Web Panel Analog Resistive Touch Screen Resolution 800 x 480pixels Colors 16M Brightness 350cd m2 Backlight life 30...

Page 9: ...ry and Power Supply Power Rating Unit Voltage Current Wattage WP6043TN 24VDC 220mA 5 5W WP6070TN 24VDC 250mA 6W WP6101TN 24VDC 350mA 8 5W CPU ARM Cortex A9 with GPU 2D GPU 3D support eMMC 4GB RAM 1GB Power Supply 24VDC 15 with isolation RTC Built in ...

Page 10: ... 100 Mbps 1x 10 100 Mbps 1x 10 100 Mbps Note The USB Device port is placed for development purposes only RJ45 Ethernet Port The Web Panel HMI series devices come with an in built RJ45 Ethernet port The RJ45 port is a shielded female jack with link and activity LEDs Pin number Signal 1 TX 2 TX 3 RX 4 NC 5 NC 6 RX 7 NC 8 NC USB Slave Port The Web HMI comes with a USB slave device port that is USB 2 ...

Page 11: ...e Screen Touch Beeper On Default Language English Environmental Specifications and Approvals Feature Specifications Operating Temperature 0 to 50 C Storage Temperature 20 to 85 C Relative Humidity 10 to 95 non condensing Shock IEC 60068 2 27 25g 11ms 6 shocks per axis total 18 shocks X Y Z Vibration IEC 60068 2 6 5 to 150Hz 3g peak X Y Z EMC EN 55011 2009 A1 2010 EN 61131 2 2007 EN 61000 6 2 2005 ...

Page 12: ... connect a USB flash drive to the device Getting started with the Web HMI Main Settings Settings Description Configuration button This button is used to enter into device configuration Device Settings button Settings for Network Calibration Password and Brightness can be accessed using this button URLs Settings button Device Information button Update button Entering into device settings 1 At power...

Page 13: ... password The factory default password for the device is 1234 Clicking on the textbox brings up the On Screen Keyboard OSK Enter the password and click on OK to continue Network Settings The first tab on the left is the device settings tab Clicking on it Network Setting screen will appear On this screen the IP of the device can be set The device defaults to acquire a dynamic IP from the network wh...

Page 14: ... This setting is used to set the calibration of the touch screen of the device The device is already calibrated at the factory before shipping In case re calibration needs to be done this setting screen can be used to calibrate the touch screen 1 On the network settings screen click on the right arrow at the bottom right corner to view the calibration settings 2 Click on the Calibrate Device butto...

Page 15: ...sks for a final confirmation before restarting the device in calibration mode 4 After entering into the calibration mode the following screens open up Follow the directions given on the screen to calibrate the touch screen by touching and releasing the crosshairs 1st stage 2nd stage 4th stage 3rd stage 5th stage ...

Page 16: ...password 3 Click on Save to save the changes or click on Reset to clear all text boxes CAUTION If any other button is pressed before clicking on the Save button all changes will be lost Make sure to click on Save before continuing Brightness Control This option gives the user to select option of controlling the brightness of the Web HMI 1 To open the Brightness control screen click on the highligh...

Page 17: ...as required by clicking on the brightness control button ATTENTION ATTENTION Home button and Left Arrow The user can exit the settings screens by clicking on the Home button placed at the bottom center of the screen The user can go to the previous screen by clicking on the Left Arrow placed at the bottom left corner of the screen ...

Page 18: ...e entered as http 192 168 1 100 5 After entering the URLs or IP addresses select the URL that the browser should open upon restart by clicking on the respective radio button 6 Click on Save to save the changes before clicking on the Home button 7 Upon device restart the browser will browse the selected URL If the URL or the IP address is not available then an Error 404 Page not found will be shown...

Page 19: ...ghts button on the right corner of the device information page displays the Open source licenses used in the product Update The Update screen can be opened by clicking on the last tab on the left On this page the user can update the browser or firmware 1 To update the browser firmware insert a USB flash drive containing the updated version 2 Click on Update Browser or Update Firmware Note The Web ...

Page 20: ...rowser On powering up the Web HMI shows the screen as shown below Do not click on the Configuration button and let the timer of 5 seconds time out The browser will open up the URL that was selected in the Web Application settings and will open up as shown below ...

Page 21: ...the right to change or discontinue specifications and features without prior notice RENU Electronics is not responsible for any damage to the Web HMI or any other device used in this process This document is solely for the purpose of providing the user a general direction of configuring the Web HMI All other products brand names company names and logos used here in are for identification purposes ...

Page 22: ... RENU Electronics Pvt Ltd Page 22 of 22 NOTES ...