Page 1: ......

Page 2: ......

Page 3: ...ion Hazardous materials such as CFCs HCFCs or asbestos have not been used in this product The packaging is made of recyclable material Please dispose of the individual elements according to the current legislation in force in the country where the product is to be employed Please refer to Table 1 for identifying the materials DESCRIPTION MATERIAL Pallet Wood FOR Packaging box Corrugated cardboard ...

Page 4: ...ASUREMENTS 16 SYSTEM STATUS 17 MENU ENTRIES 19 COMMAND PANEL 19 SYSTEM OFF ON COMMAND 19 BYPASS COMMAND 20 BATTERY TEST COMMAND 21 TEMPORARY ALARM SUPPRESSION 21 GLOBAL SYSTEM INFORMATION 21 MAIN SETUP PAGE 22 LANGUAGE SETTING 23 DISPLAY SETTING 23 System clock 24 Screen saver and buzzer 24 Change password 25 SYSTEM LOG PAGE 25 EXPERT LEVEL 26 GENERAL SYSTEM SETTINGS 27 GENERAL CONFIGURATION 27 Op...

Page 5: ...L BYPASS 38 RESTORE THE ON LINE MODE AFTER MANUAL BYPASS 39 LOAD ON STATIC BYPASS AFTER MANUAL BYPASS 40 SYSTEM OFF COMMAND 40 OPTIONS 41 EXTERNAL BATTERY CABINET 41 BATTERY ROOM VENTILATION 42 SETTING THE RATED BATTERY CAPACITY SOFTWARE CONFIGURATION 42 EXTERNAL BATTERY TEMPERATURE PROBE 42 FOUR SWITCH VERSION 42 REMOTE MAINTENANCE BYPASS 43 PARALLEL 44 OPTIONAL SLOT BOARDS 44 EXTERNAL BATTERY CA...

Page 6: ...obe Connector for external battery temperature kit B_BOX R E P O Battery box REPO Remote power off for the battery cabinet breaker trip coil SWMB Manual Bypass Switch Maintenance bypass breaker SWIN Mains Input Switch Mains input breaker SWBYP Bypass Input Switch Bypass line input breaker SWOUT Output Switch Output switch disconnector B Positive battery voltage current temp B Negative battery volt...

Page 7: ...conversion technology in accordance with VFI SS 111 classification as set out in standard IEC EN 62040 3 and it provides the very highest levels of performance such as HIGH EFFICIENCY up to 94 5 in ON LINE double conversion mode ULTIMATE TECHNOLOGIES Sentryum applies the advanced technologies such as DSP Digital Signal Processor dual core microprocessor three level inverter circuits to provide max...

Page 8: ...S receives energy from the mains supply the DSP will ensure that the connected batteries remain charged The DSP also monitors the amplitude and frequency of the mains voltage the amplitude and frequency of the voltage generated by the inverter the load applied the internal temperature and the condition of the connected batteries The block diagrams below show each of the components that make up the...

Page 9: ...Switches from left Input Separate bypass input maintenance bypass output C Battery start button COLD START H Signal terminal cover D Slots for optional accessory communication card I Power Terminal cover E Parallel card L Wire output cover Maintenance bypass SWMB bypass input SWBYP and output SWOUT switches are only available in SW version ...

Page 10: ...r enabling the system to be monitored and configured The two ports cannot be used simultaneously The USB port is to be used as an alternative to the RS232 serial interface USB port function is only guaranteed when using a cable no longer than 1 5 m If a longer cable is required the use of the RS232 serial interface is suggested In any case it is recommended not to use a cable longer than 10 m D SL...

Page 11: ...m the input frequency This configuration automatically disables the bypass line FREQUENCY CONVERTER mode can be operated with and without connected batteries WARNING Do NOT switch on the SWMB manual bypass switch when the UPS is in FREQUENCY CONVERTER mode To prevent maintenance bypass operation the user shall keep the SWMB switch handle blocked OPERATING STATES The UPS may be in a different statu...

Page 12: ... UPS is to be performed exclusively by qualified staff There may be voltages present within the UPS even when the input output and battery disconnectors are open Removal of the UPS panels by non qualified staff may result in injury to the operator and damage the equipment For further instructions in relation to the manual bypass function please refer to the Switching the system to manual bypass ch...

Page 13: ... date and time In the event of an alarm an exclamation mark will also be present indicating the number of alarms active at that time From the top of the status bar the user can access the anomaly alarm log by pressing the Exclamation point icon The Exclamation point icon will only be visible if an anomaly warning lock or command occurs Icon indicating the existence and number of alarms that are ac...

Page 14: ...Phase 2 load level Battery status Phase 3 load level System status Manual bypass switch closed SWMB In general the color and the shape of the icons provide instant information to the status of the system Grey communication lost Com Lost Orange anomaly Light blue normal status Flashing red alarm Blue Temporary bypass status ...

Page 15: ... the input to the system Battery Area of the display reserved for displaying the main electrical values related to the battery Bypass input Area of the display reserved for displaying the main electrical values related to the bypass line Output Area of the display reserved for displaying the main electrical values related to the output of the system NAVIGATION Menu expansion reduction tab icons th...

Page 16: ... as shown in the examples below The user can return on the home page at any time by tapping the Home icon on the status bar The following are some examples of the home page whilst displaying various operating conditions Home page displaying UPS in ON LINE mode normal operation load on inverter Single switch version Home page displaying UPS in ON LINE mode normal operation load on inverter Four swi...

Page 17: ... 15 Home page displaying BATTERY WORKING status Home page displaying MANUAL BYPASS SWITCH CLOSED Home page with alarm drop down list opened ...

Page 18: ... the icons in the Home page Pressing one of the four section icons Input 1 Bypass 2 Battery 3 Output 4 will open the relative measurements page Mains Input page displays the status and the parameters relating to the system input Bypass section page displays the status and the parameters of the system bypass line ...

Page 19: ...st the symbol is negative if the battery is under charge The charge level is estimated by an algorithm that computes the energy flowing to and from the batteries and the voltage level The autonomy is calculated based on the actual power supplied to the load and the charge level Output status page displays the status and the parameters of the system output SYSTEM STATUS Pressing the System icon wil...

Page 20: ...s and programmed using the configuration software Sensor status page displays the temperature of the system and of the power heatsinks The Ext Bat value will be shown if a Battery Cabinet external temperature probe is installed and set by the configuration software Internal status page displays the status of the UPS internal contacts the status of power stages and the DC bus voltage ...

Page 21: ... depending on the pre set access level Buzzer toggle button UPS info Settings menu Event log COMMAND PANEL To access the Command Panel tap the Command launcher icon From this page it is possible give commands to the UPS System commands and Battery commands SYSTEM OFF ON COMMAND Tap the System Off On icon to switch the system on System commands page ...

Page 22: ...ll be switched into bypass If the system is in Stand by mode the command is disabled Press the bypass command O to switch the load back onto the inverter WARNING In this condition a power outage will lead to a loss supply to the connected load The UPS will behave in different ways depending on the operational status it is in Bypass command when running in ON LINE mode the system is switched to byp...

Page 23: ...rge level and the load safety are not compromised Press the Battery test icon to execute the battery test A confirmation is required The progress bar will show the progress of the battery test TEMPORARY ALARM SUPPRESSION If the system buzzer is beeping due to a prolonged fault state the user can silence the alarm by pressing the Buzzer toggle button For further information refer to the buzzer para...

Page 24: ...configuration This page shows the general configuration of the UPS Output voltage the set UPS r m s output voltage in Volts Output frequency the set UPS output frequency in Hz Mode the operating mode set by the user Auto restart Information about status of auto restart setting enable disable Battery low time the set remaining battery time for which the buzzer will alert the user about the imminent...

Page 25: ...figuration page DISPLAY SETTING Display configuration pages To save any configuration setting Press the Save icon and confirm to store any new values Press return icon button to go back to the main setup page Save confirmation page After pressing the save icon confirm the overwriting of the new values into the system memory ...

Page 26: ...ate and time again SCREEN SAVER AND BUZZER This page enables the user to Define the display inactivity period to turn off the display backlight Disable enable the alarm buzzer Default Buzzer ENABLED Screen saver and buzzer configuration page NOTE After the timeout the backlight of the screen will be turned off and the access level will be set as the higher non password protected level The touch sc...

Page 27: ...cess the system log In this page the user can view the UPS event history The rise and fall indicate respectively when the alarm related to the event happened and when it was cleared System log page By using the arrows the user can scroll up and down through the event list The UPS will record the last 960 events occurred The older ones are then overwritten ...

Page 28: ...sword is required Insert the preset password expert to access the Expert level Expert level selection page Expert password page NOTE 1 If the display goes into standby backlight off the access level will be changed to the higher non password protected level 2 The password may be different to the default setting if it has been previously configured refer to the Password change paragraph 3 To exit t...

Page 29: ...arious options for the UPS General configuration page 1 operating mode configuration OPERATING MODE The user can choose the operational mode refer to the Chapter Operating modes for further details regarding these modes AUTO RESTART If during battery operation the system switches off due to the end of autonomy a remote shutdown command or due to a self shutdown when the power is restored the syste...

Page 30: ...box The first selection is customizable by writing the voltage in the text box If a low output voltage is selected the percentage of power derating is shown on the right NOTE The voltage setting is available only when the UPS is in stand by General configuration page 2 Output voltage and frequency setting FREQUENCY SETTING To set the desired output frequency tap on the corresponding select box Pre...

Page 31: ...ry test function This page enables the user to schedule the automatic battery tests in order to regularly monitor the battery health Battery testing configuration page It is possible to schedule the battery test in three different ways Every n hours the UPS will start the battery test at regular intervals not necessarily at the same time of the day NOTE the maximum adjustable period is 273 hours a...

Page 32: ...on to the Expert level it is possible to create another two levels POWERUSER LEVEL The PowerUser level allows the default commands and settings as provided by the factory configuration All these available commands and settings are previously described Setting the PowerUser password prevents access to the Command launcher Settings menu and Event log menu to unauthorised users USER LEVEL User level ...

Page 33: ... change based on the used access level When a password protective level is activated a pre set password permits to access the available command for that level If the display goes in standby backlight off the access level will be raised to the higher non password protected level PASSWORD CHANGE Touch one of the three user icons matching the access level for which it is intended to set or change the...

Page 34: ...atus and any anomalies are reported by a buzzer which emits a modulated sound according to the various UPS operating conditions The different types of sound are described below Sound A This sound is emitted to confirm any touch screen command Sound B This sound is emitted when the UPS switches to bypass Sound C This sound is emitted when the UPS switches to battery status When the battery end of d...

Page 35: ...ttery low warning 10 min 1 60 1 min step Expert Auto Restart Enables the auto restart function ON OFF ON Expert Output voltage Selection of the output voltage Phase Neutral 120V 120 127V custom 115V 110V Expert Output frequency Selection of the inverter frequency 60Hz 50Hz 60Hz Expert Automatic battery test Enables and schedules the automatic battery test OFF OFF ON Programmable Expert User passwo...

Page 36: ...attery low with closed contact between pin 8 and pin 6 Otherwise closed contact between pin 8 and pin 5 OUT 4 Fault or Lock F L Fault or lock alarm with closed contact between pin 7 and pin 8 Table 3 Default configuration for output signals INPUT SIGNALS CONFIGURATION FACTORY DEFAULT Table 3 1 below lists the default configuration of the programmable input signals as provided for factory default s...

Page 37: ...am to the UPS Before any attempt to turn the system on it is mandatory to check the power supply and connection of PE neutral phases and external battery wires Refer to the Installation manual WARNING If the UPS is not going to be used for a long period in order to isolate the UPS from all of the DC sources disconnect all external battery cabinets SYSTEM ON DIRECT COMMAND Close the mains input bre...

Page 38: ...tton and keep it pressed for at least 5 seconds The system will turn on in the STAND BY WITH CB OFF mode The status led will light up and the display will start NOTE if no actions are taken within one minute the system will automatically shut down to avoid discharging the batteries Verify that no anomalies are present on the status bar except for the anomalies referring to the absence of input and...

Page 39: ...PS goes into Battery Working status and that the output voltage remains present and stable by checking the system output page The buzzer should start to inform the user that the UPS is running from battery LOAD FORCED ON BYPASS Press the Menu icon and select the Command launcher icon Press the Bypass command 1 icon to switch the system into static bypass A confirmation is required Check that the U...

Page 40: ...nt activating the maintenance bypass will shut off the power supply to the load 3 During this phase with a load powered via the maintenance bypass any disturbances on the mains power supply line of the UPS will directly affect the connected load The load is connected directly to the incoming mains The UPS is no longer active Below is a list of the operations to be performed in order to carry out m...

Page 41: ... ok and no anomalies will be present except A11 Cover of maintenance switch is open NOTE Before opening the maintenance bypass switch check the display if the bypass line is represented with a white stripe it means that the load is supplied by the manual bypass alone If the maintenance bypass switch is opened in this condition the power to the load will be lost If the bypass line is represented wi...

Page 42: ...s open From the Command Panel page press the Bypass command ON icon to force the static bypass on NOTE Perform this step even if the bypass status appears to be already ON Confirm the Bypass ON Command by selecting OK Verify that the system status changes to LOAD FORCED ON BYPASS Open the Manual bypass switch SWMB Put back in place the Maintenance Bypass interlock paddle Verify the output voltages...

Page 43: ... placed close to each other in order to avoid loops For EMI reasons if possible place the UPS and Battery Cabinet side by side in order to keep the cable length as short as possible 3mts maximum suggested If it is not possible due to space limitations maximum admitted length is 25mt If extended length is required please contact your local service center Check that the battery voltage of the Batter...

Page 44: ... VRLA type batteries Igas 8 in fast charging for VRLA type batteries SETTING THE RATED BATTERY CAPACITY SOFTWARE CONFIGURATION Having installed one or more BATTERY CABINETS the UPS must be configured to the correct rated capacity value To perform this operation use the dedicated configuration software reserved to service personnel only EXTERNAL BATTERY TEMPERATURE PROBE An optional temperature pro...

Page 45: ...ons given in POWER CONNECTION INFORMATION paragraph of the Installation manual Use a double insulated cable with a cross section of 1mmsq to connect the SERVICE BYPASS terminal to the auxiliary contact of the remote maintenance bypass disconnect switch Whenever the UPS is equipped with an internal isolation transformer check the compatibility between the remote maintenance bypass and the neutral a...

Page 46: ...the web site EXTERNAL BATTERY CABINET BREAKER REMOTE TRIP By connecting the battery box REPO wires to this dedicated UPS output it is possible to trip the battery breaker when the UPS Emergency Power Off button is activated to disconnect the battery circuit from UPS In order to make this connection connect a double insulation two poles wire AWG13 2 5mm2 to the B_BOX REPO connector refer to section...

Page 47: ...tand by with CB on S40 ON LINE mode S42 Economy mode S45 Frequency converter mode S50 Battery Working S52 Battery low S60 Temporary bypass S61 On bypass due to inverter lock S64 Manual bypass active S90 Load off S91 Emergency power off S92 Disconnected from the load Table 4 UPS status list COMMANDS These codes indicate that a command has been activated CODE DESCRIPTION C04 Battery test mode C05 Ma...

Page 48: ...open A11 Cover of maintenance switch open A18 Bypass voltage out of range Table 7 UPS alarm list Parallel systems Anomaly These anomalies are present only if the input signals are configured and programmed FAULTS Faults are problems more critical than Anomalies in that if they persist they may bring the UPS to a stop CODE DESCRIPTION F01 Line phase error F02 Bypass phase error F03 Input N loss F04...

Page 49: ...r relay open L19 Wiring error L20 CAN communication fault L21 Output circuit fault L22 Power module overtemperature L23 CPU communication fault L24 Overload fault L25 MCU communication fault L26 DSP firmware version not compatible L27 Input output phases non compatible L28 Bypass SCR short circuited back feed protection L29 Bypass SCR open circuited L30 Voltage waveform abnormal in L1 phase L31 Vo...

Page 50: ... IS OPEN Close the input breaker SWIN NO NEUTRAL CONNECTION The UPS cannot work without a neutral connection WARNING If this connection is missing damage could be caused to the UPS and or the load Connect the mains to the terminals as indicated in the Installation manual UPSTREAM PROTECTIVE DEVICE OPEN Reset the protective device Warning check that there is no overload or short circuit at the outp...

Page 51: ...ONE OR MORE PHASES ARE SWAPPED Check the input and bypass terminal connections THE ALARM LIST SHOWS ONE OR MORE OF THE FOLLOWING CODES A18 PROTECTIVE DEVICE UPSTREAM FROM THE BYPASS LINE OPEN ONLY IF BYPASS IS SEPARATE Reset the upstream protective device WARNING check that there is no overload or short circuit at the output of the UPS BYPASS SWITCH OPEN SWBYP ONLY IF BYPASS IS SEPARATE FROM MAINS...

Page 52: ...HE UPS VENTILATION SLITS OBSTRUCTED OR TOO CLOSE TO WALLS Activate the maintenance bypass SWMB if present without powering off the UPS in this way the fans cool the heat sink more quickly Eliminate the cause of the over temperature and wait for the temperature of the heat sink to drop Switch off the maintenance bypass FAULT IN TEMPERATURE PROBE OR UPS COOLING SYSTEM Insert the maintenance bypass S...

Page 53: ...sonalized preventive maintenance options BATTERIES Thanks to an advanced battery care system our UPS preserve the batteries health both during charging and discharging phase For example an algorithm to avoid deep discharge is implemented Anyway environmental condition and usage affect battery life Ambient temperature number of blackout or outages number of depth discharges frequency of charge and ...

Page 54: ...rest factor allowed at rated load 3 1 Precision of frequency in free running mode 0 01 Inverter overload 110 60 min 125 10 min 150 1 min Bypass overload 110 Infinite 125 60 min 150 10 min 200 2 sec Technology High frequency IGBT with digital control BATTERIES Rated voltage Vdc 120 Maximum recharging current A 36 Battery charger algorithm Two levels with temperature compensation Technology Digitall...