background image

Q175C Condensing Boiler 

Q175C SP 

2/2011 

© 2011 Rinnai Corporation 

SPECIFICATIONS 

Rinnai is continually updating and improving products; therefore, specifications are subject to change without prior 
notice. Local, state, provincial and federal codes must be adhered to prior to installation. 

Standard Features 

• 

Onboard outdoor reset control system with sensor standard 

• 

Prebuilt plumbing kit with insulated Low Loss Header 

• 

Priority DHW standard (3 way valve not included) 

• 

Domestic hot water plate warming 

• 

Built in DHW 6.6 gallon indirect tank 

• 

Modulating Ceramic premix burner 

• 

5:1 turn down ratio 

• 

Spark ignition 

• 

Exceeds SCAQMD 1146.2 Low NO

x

 requirements 

• 

Stainless Steel Water tube condensing heat exchanger 

• 

Direct Vent sealed combustion 

• 

Concentric and twin pipe venting adapters included 

• 

Approved for room and closet installations 

Optional Accessories 

• 

RS100 Single zone controller 

• 

Flue Gas temperature sensor 

• 

Room Air Filter 

• 

NG to LP conversion Kit 

• 

LP to NG Conversion Kit 

General Specifications  

 Units 

 

 

Water content 

gal 

 1.8 

Max. supply boiler 
temperature 

°F 176 

Max operating pressure 

psi 

45 

Relief valve rating 

MBH 

375  

Relief valve pressure rating 

psi 

30 

Dry weight 

lbs 

196 

Min inlet gas pressure NG 

"W.C. 

4.0" 

Max inlet gas pressure NG 

"W.C. 

10.5" 

Min inlet gas pressure LP 

"W.C. 

8.0" 

Max inlet gas pressure LP 

"W.C. 

14.0” 

Max equivalent exhaust vent 
length 

ft 80 

Max equivalent combustion 
air vent length 

ft 80 

Approved venting materials 

  

Polypropylene, 

Stainless Steel, 

PVC, CPVC  

Performance Specifications

 

  

Units 

 

 

Fuel Type 

  

NG/LP 

Input MBH 

175 

Heating Capacity 

MBH 

161 

AFUE (I=B=R) 

95.7 

Part Load Efficiency (EN677) 

98.5 

DHW flow rate 75ºF 

Δ

Gpm 4.1 

Electrical Specifications

 

 Units 

 

 

Electrical Voltage Mains 

 V/Hz 

120/60 

Electrical Voltage Controls 

24 

Power Consumption Max Load 

210 

Power Consumption Stand by Load 

14 

Recommended Circuit breaker rating 

15 