Publication 1794-IN049D-EN-P - January 2009

Installation Instructions

FLEX I/O 2 Input Frequency Module 

 

Cat. No. 1794-IJ2, 1794-IJ2K, and 1794-IJ2XT

(Modules with a K in the last position of the catalog number are 
conformally coated to meet noxious gas requirements of ISA/ANSI-71.040 
1985 Class G3 Environment.)

European  Hazardous Location Approval

The following frequency input modules are European Zone 2 approved: 
1794-IJ2, 1794-IJ2K, and 1794-IJ2XT

Important User Information

Solid state equipment has operational characteristics differing from those of electromechanical 
equipment. 

Safety Guidelines for the Application, Installation and Maintenance of Solid State 

Controls

 (Publication  

SGI-1.1

 available from your local Rockwell Automation sales office or 

online at 

http://literature.rockwellautomation.com

) describes some important differences 

between solid state equipment and hard-wired electromechanical devices. Because of this 
difference, and also because of the wide variety of uses for solid state equipment, all persons 
responsible for applying this equipment must satisfy themselves that each intended application 
of this equipment is acceptable.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential 
damages resulting from the use or application of this equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because 
of the many variables and requirements associated with any particular installation, Rockwell 
Automation, Inc. cannot assume responsibility or liability for actual use based on the examples 
and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, 
circuits, equipment, or software described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of 
Rockwell Automation, Inc. is prohibited.

Throughout this manual we use notes to make you aware of safety considerations.

WARNING

Identifies information about practices or circumstances that can cause an 
explosion in a hazardous environment, which may lead to personal injury 
or death, property damage, or economic loss.

IMPORTANT

Identifies information that is critical for successful application and 
understanding of the product.

ATTENTION

Identifies information about practices or circumstances that can lead to 
personal injury or death, property damage, or economic loss. Attentions 
help you:

identify a hazard

avoid a hazard

recognize the consequence

ATTENTION

Environment and Enclosure

This equipment is intended for use in a Pollution Degree 2 industrial 
environment, in overvoltage Category II applications (as defined in IEC 
publication 60664-1), at altitudes up to 2000 meters (6562 ft) without 
derating.
This equipment is considered Group 1, Class A industrial equipment according 
to IEC/CISPR Publication 11. Without appropriate precautions, there may be 
potential difficulties ensuring electromagnetic compatibility in other 
environments due to conducted as well as radiated disturbance.
This equipment is supplied as open-type equipment. It must be mounted 
within an enclosure that is suitably designed for those specific environmental 
conditions that will be present and appropriately designed to prevent 
personal injury resulting from accessibility to live parts. The enclosure must 
have suitable flame-retardant properties to prevent or minimize the spread of 
flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) 
if non-metallic. The interior of the enclosure must be accessible only by the 
use of a tool. Subsequent sections of this publication may contain additional 
information regarding specific enclosure type ratings that are required to 
comply with certain product safety certifications.
In addition to this publication, see:

Industrial Automation Wiring and Grounding Guidelines, for additional 
installation requirements, Allen-Bradley publication 

1770-4.1

.

NEMA Standards publication 250 and IEC publication 60529, as 
applicable, for explanations of the degrees of protection provided by 
different types of enclosure.

WARNING

If you insert or remove the module while backplane power is on, an 
electrical arc can occur. This could cause an explosion in hazardous location 
installations.
Be sure that power is removed or the area is nonhazardous before 
proceeding.

WARNING

If you connect or disconnect wiring while the field-side power is on, an 
electrical arc can occur. This could cause an explosion in hazardous location 
installations. Be sure that power is removed or the area is nonhazardous 
before proceeding.

ATTENTION

Personnel responsible for the application of safety-related Programmable 
Electronic Systems (PES) shall be aware of the safety requirements in the 
application of the system and shall be trained in using the system.

ATTENTION

Do not remove or replace a Terminal Base unit while power is applied. 
Interruption of the backplane can result in unintentional operation or machine 
motion.

ATTENTION

FLEX I/O is grounded through the DIN rail to chassis ground. Use zinc plated 
yellow-chromate steel DIN rail to assure proper grounding. The use of other 
DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, 
or are poor conductors, can result in improper or intermittent grounding. 
Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and 
use end-anchors appropriately.

ATTENTION

Preventing Electrostatic Discharge

This equipment is sensitive to electrostatic discharge, which can cause 
internal damage and affect normal operation.  Follow these guidelines when 
you handle this equipment:

Touch a grounded object to discharge potential static.

Wear an approved grounding wriststrap.

Do not touch connectors or pins on component boards.

Do not touch circuit components inside the equipment.

Use a static-safe workstation, if available.

Store the equipment in appropriate static-safe packaging when not in 
use. 

ATTENTION

To reduce susceptibility to noise, power analog modules and digital modules 
from separate power supplies.  Do not exceed a total length of 9.8 ft (3m) for 
dc power cabling.

European Zone 2 Certification (The following applies when the product bears the Ex 
or EEx Marking)

This equipment is intended for use in potentially explosive atmospheres as defined by European 
Union Directive 94/9/EC and has been found to comply with the Essential Health and Safety 
Requirements relating to the design and construction of Category 3 equipment intended for use 
in potentially explosive atmospheres, given in Annex II to this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by compliance 
with EN 60079-15 and EN 60079-0.