MC16-PAC-2-KIT Installation Manual.doc   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2019-05-30 

 

1/2 

 

Roger Access Control System 

MC16-PAC-2-KIT Installation Manual 

Firmware version: n/a 

Document version: Rev. B 

 

 

This  document  contains  minimum  information  that  is  necessary  for  initial  setup 
and  installation  of  the  kit.  The  detailed  description  of  configuration  parameters 
and  functionalities  of  all  components  is  specified  in  respective  Operating 
manuals available a

www.roger.pl

I

NTRODUCTION

 

MC16-PAC-2-KIT  is  designed  to  control  two  doors  in  RACS  5  system.  Both 
doors can be read-in or read-in/out type when equipped with MCT series readers 
(RS485). The kit includes MC16-PAC-2 access controller, MCX2D expander and 
ME15 metal box with PS2D power supply unit. The box is adapted to installation 
of  7Ah  battery  for  emergency  supply.  All  elements  of  controlled  door  including 
readers and door locks can be supplied from the kit. 

C

ONFIGURATION WITH 

R

OGER

VDM

 PROGRAM

 

Low  level  configuration  with  RogerVDM  software  mainly  concerns  MC16 
controller.  Additionally  it  is  necessary  to  define  individual  addresses  for  MCT 
series readers according to their installation manuals. 

MC16 programming procedure with RogerVDM software: 

1.  Connect the controller to Ethernet network and define the IP address of your 

computer  in  the  same  subnetwork  as  the  controller  with  192.168.0.213 
default IP address. 

2.  Start  RogerVDM  program,  select 

MC16  v1.x

  device,  the  latest  firmware 

version and 

Ethernet

 communication channel. 

3.  Select from the list or enter manually the IP address of controller, enter 1234 

communication key and start the connection with the controller. 

4.  In the top menu select 

Tools

 and then 

Set communication key

 to define your 

own password for the controller. 

5.  In the main window specify your own IP address of the controller. 
6.  Optionally  enter  comments  for  controller  and  its  object  to  facilitate  their 

identification during further configuration of the system. 

7.  Optionally backup settings clicking 

Send to File…

 

8.  Click 

Send to Device

 to update the configuration of controller and disconnect 

by selection of 

Device

 in the top menu and then 

Disconnect

M

EMORY RESET

 

Memory  reset  procedure  resets  all  settings  to  default  ones  and  results  in 
192.168.0.213 IP address and empty communication key. 

MC16 memory reset procedure: 

1.  Disconnect power supply 
2.  Short CLK and IN4 lines. 
3.  Restore power supply, all LEDs will flash and wait min. 6s. 
4.  Remove connection between CLK and IN4 lines, LEDs will stop pulsating and 

LED2 will be on. 

5.  Wait approx. 1.5 min till LED5+LED6+LED7+LED8 are pulsating. 
6.  Restart the controller (switch power supply off and on) 
7.  Start RogerVDM and make low level configuration. 

F

IRMWARE UPDATE

 

New  firmware  can  be  uploaded  to  the  controller  with  RogerVDM  software.  The 
latest firmware file is available a

www.roger.pl

MC16 firmware update procedure: 

1.  Connect with the controller using RogerVDM software. 
2.  Backup settings by clicking 

Send to File…

 

3.  In the top menu select 

Tools

 and then 

Update firmware

4.  Select firmware file and then click 

Update

5.  After firmware update wait till LED8 is pulsating. 
6.  Make or restore low level configuration in RogerVDM software. 

Note: During the firmware update process, it is necessary  to ensure continuous 
and  stable  power  supply  for  the  device.  If  interrupted,  the  device  may  require 
repair by Roger. 

P

OWER SUPPLY

 

The kit is supplied from PS2D power supply unit. The metal box offers space for 
installation of typical  7Ah backup battery  which is connected to BAT+ and BAT- 
terminals of MCX2D expander. 

 

Fig. 1 MC16-PAC-2-KIT 

 

The installation can be done only by qualified person with all 
necessary certificates concerning connection and maintenance 
of 230VAC and low voltage networks. 

 

Prior to starting the installation it is necessary to ensure that 
230 VAC circuit is disconnected. All works inside the box must 
be carried out with 230VAC supply voltage disconnected. 

 

It is forbidden to use the kit without properly executed and 
operational earthing system. 

T

AMPER DETECTOR

 

The metal box is  equipped  with  door  contact  which  can be connected to  one of 
the  inputs  (e.g.  IN8)  and  GND  terminal  of  the  controller.  The  anti-sabotage 
function  can  be  assigned  to  the  input  within  high  level  configuration  of  the 
system. 

A

PPENDIX

 

Table 1. MC16 screw terminals 

Name 

Description 

BAT+, BAT- 

Not used in kit 

AC, AC 

Not used in kit 

AUX-, AUX+ 

12VDC input power supply 

TML-, TML+ 

Not used in kit 

IN1-IN8 

Input lines 

GND 

Ground 

OUT1-OUT6 

15VDC/150mA transistor output lines 

A1,B1 

RS485 bus 

CLK, DTA 

Not used in kit 

A2,B2 

Not used 

NO1, COM1, NC1 

30V/1.5A DC/AC (REL1) relay 

NO2, COM2, NC2 

30V/1.5A DC/AC (REL2) relay 

 

Table 2. MCX2D screw terminals 

Name 

Description 

BAT+, BAT- 

Backup battery 

VIN+, VIN- 

13.8VDC input power supply 

AUX+, AUX- 

13.8VDC/0.2A  output  power  supply  (for  general 
purpose) 

VOUT+, VOUT- 

13.8VDC/0.2A output power supply (for controller) 

A, B 

RS485 bus (for controller) 

Ax, Bx 

RS485 bus (for readers) 

TMLx+, TMLx- 

13.8VDC/0.2A output power supply (for readers) 

VDRx+, VDRx- 

13.8VDC/1.0A output power supply (for door lock) 

LCKx 

15VDC/1A transistor output line (door lock) 

BELLx 

15VDC/1A  transistor  output  line  (alarm  signalling 